Professional Documents
Culture Documents
ABSTRACT
I N T R O D U C T I O N A N D SCOPE
341
342 G . R . Koerner et al.
INSTRUMENTATION
Moisture sensors
Moisture sensors were installed in each test plot in order to assess the general
moisture condition of the soil subgrade and hydration of the bentonite
within the GCLs. Two types o f sensors were used in the project--a gypsum
block sensor (used in the soil subgrade) and a fiberglass mesh sensor (used
within the GCL). Figure 1 shows a diagram of each type o f moisture sensor.
Both sensors operate on a resistance basis. The fiberglass sensors contain
two wire screens embedded in porous fiberglass mesh. The resistance to flow
Instrumentation for monitoring field performance of the Cincinnati GCL test plots 343
•I25 mm
0
mm
40 m
25 mm
CREST
in •1
211 n2
• Cluster o!
• MIDDLE Moisture Sensors
3• •3 • Extensometers
4• •4
5• TOE n5
were installed. They were placed in the subsoil, at the subsoil-GCL inter-
face, and in a few instances, above the GCL. A cross-section of the
moisture sensor installation in the test plots (except for plots A, F, N, and
P) is shown in Fig. 3. Figure 4 shows how the moisture sensors were
installed in plots A, F, and N.
The gypsum blocks and digital meter (5910-A) were obtained from Soil
Moisture Equipment Corporation of Santa Barbara, California. The fiber-
glass sensors were obtained from Techsas, Inc. of Houston, Texas. The cost
data are shown in Table 1.
•...5:.`....::.i.:.:••..:.••:...:...:.:.:.•.:...:.:.:•:.:.:•:...::•:.:.:.:.:.•.:...:;..:...:.:.:•:.5•.:...
`~Z.:~i!.:~Z!..:Zi.Z:!.:~:i.`~!..:Z!.:~:i.~:!.~Z!.:~:i.ZZ!.~:!.i.:~Z.X!i.~§~ii:~i-~zi-:
:!.~.~r
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!!!!!!!!!!!iiiill
GM---------I1~~
QcL ~ ~///////////////////////////////////////////////////A
lass
Gypsu
Block
GT/GN/GT----I~
iiii ii ii i i i I i i ii impl iI1¢ i i i i i i i I i i i i i i i i I I i i ii i i I I i I I I
GM-~I~
"~'- ~ql--Flberglass
GCL ~ ~
I:IIOCK
TABLE 1
Equipment List for the Moisture Sensors
Soil A
Soil B
jAj
Soil C
,/
Crest
Toe
cLo L;H
PLO~ F G H I J K L M N
Fig. 5. Subsoil on the 2:1 slope.
346 G.R. Koerner et al.
pressure o f 17 kPa was applied to the specimen. A gypsum block was inserted
within the subsoil, and a fiberglass moisture sensor was placed at the inter-
face o f the G C L and the subsoil. The subsoil was incrementally wetted, and
after the moisture gauge reading equilibrated, the resistance reading and
moisture content of the soil were recorded.
The calibration curve for the gypsum block in the site subsoils is shown in
Fig. 6, and the calibration curve for the fiberglass moisture gauge with the
site subsoils is shown in Fig. 7.
The procedure for calibration o f the fiberglass moisture sensor with
bentonite involved placing a fiberglass sensor between two prewetted pieces
of Gundseal so that the sensor was surrounded by bentonite. Moist sand was
placed below and above the membranes o f the GCLs, and a pressure of
17 kPa was applied to the specimen. After the moisture gauge reading equi-
librated, the resistance reading and the moisture content of the bentonite
were recorded.
The calibration curve for the fiberglass moisture sensor with bentonite is
shown in Fig. 8. The scatter is due to the use of 15 different sensors in the
development of the calibration curve. Not only did each type of moisture
sensor need to be calibrated to the different types of soil, but each individual
moisture sensor should have its own individual calibration curve since the
moisture sensors have slight mechanical differences.
Because o f the scatter in Fig. 8, this calibration curve can best be used to
determine whether the bentonite is relatively dry or relatively hydrated and
the trending o f the bentonite to become wetter or drier. The calibration curve
100
mmm~o Amm oA • •
90 • •
80 A 0
c
:5 70
FI- 60
50 A o
O9
(9
40
30 A
0 • 0
20
10
A
m0 •
0 -I~ IIPA, ,' ,' I
0 5 10 15 20 25 30
Water Content (%)
100
90 A
80 Ai I
.E
m
"O
70 0
rr 6O
c 50 0
Z~
co
~ 40
m 30
0
~ 2O
A 0
10 /~ A A
El
A
0
0 5 10 15 20 25 30
Water Content (%)
120
.~ 1O0
{. 2, e0 C I
regression I
;
5,
60 • •
40 • •
o
2O
0 -'I" ., mn ,m , , ,
0 50 100 150 200 250 300
Water Content (%)
Extensometers
Extensometer assembly
Seven-strand stainless steel wire (average diameter 0.76 mm) was used for the
extensometers. The wire was rated at 600 N breaking strength, but separate
tests resulted in an average breaking strength of 684 N. Table 2 presents a
parts list of items used in the assembly of the extensometers.
Extensometers used for this project were assembled in an open bay of
the EPA's Center Hill facility in Cincinnati, Ohio. A 38-m-long, 6-m-wide
reach of floor space was used. Extensometer preparation required
approximately 30 min per extensometer. A total of 280 extensometers were
prepared for this project. Extensometers were prepared as outlined in the
following steps:
• A 30-m-long polyethylene tubing was uncoiled so that it was straight and
anchored to a dead weight bumper.
• With the aid of a pair of sheet metal vise grips, the tubing was stretched
tight while the stainless steel cable was pushed into it. The cable had to be
pushed into the tubing smoothly so that it was not crimped or bent. The
stiffer the cable, the easier it was to force through the 30-m-long tube. An
alternative to pushing the cable through the conduit was to pull it through
with an electrician's fish tape made of spring steel. If the tolerance
between the internal diameter of the tube and the width of the steel allows,
pulling is often more reliable and faster than pushing the cable.
Instrumentation for monitoring field performance of the Cincinnati GCL test plots 349
TABLE 2
Extensometer Parts List
Monitoring
Stations - ~ Crest of Slope
~ ~._ 0 Upper attachment
~_Overlap ~ 6m " Lower attachment
o, ,o0e
Anchor .... ,.~, .. _~"" ~ Right Panel
Trench 3 0 1~''2
m ~ ; a ne/
Attachment
Fig. 9. Schematic diagram of extensometers of a typical test plot.
• The G C L rolls were deployed down the slope and then folded in half
along their length (downslope) direction.
• The locations o f the extensometers were marked on the lower G C L
surface with spray paint. In addition to these spots, lines at 6.0-m
intervals from the crest o f the slope were drawn across the entire width
o f the G C L . These lines on both the top and b o t t o m of the G C L were
used as reference marks during construction and perhaps will be used as
a forensic tool when the test plots are excavated. N o t e that movement
o f these lines is compared with survey marks to track movement during
construction. The contrasting paint mark also provided good photo-
graphic references.
• The bundle of five 30-m extensometers was uncoiled by rolling it down the
slope and separating the individual extensometers in the field.
• Each prepared 30-m extensometer constituted two extensometers. For
example, extensometer no. 1 and no. 5 were made from a single 30-m
extensometer. In the same manner, extensometer no. 2 and no. 4 were
made from a 30-m extensometer, and likewise two no. 3 extensometers
were made in the same fashion. In utilizing the prepared extensometers in
this fashion, two bundles of five 30-m extensometers made the 20 field
extensometers for an entire G C L layout.
• As shown in Figs 10 and 11, a pair of hooks were embedded in the
Instrumentation for monitoring field performance of the Cincinnati GCL test plots 351
el Cable
Benton
Deforrr
Cat
Geotextile
Fig. 11. Cross-section of G C L cable attachment showing how internal shear deformation is
measured.
exposed geosynthetic surface of the GCL, and then the stainless steel cable
was pulled tight and tied off on a reference stake at the crest of the slope.
Quick-setting (5min) epoxy was applied to the area where the fish
hooks embedded into the geotextile of the GCL and allowed to dry for
10min.
A 0-3 m by 0.6 m rectangle of l-ram HDPE geomembrane was then placed
on the subgrade to provide a smooth slip zone for the extensometer
connection. Note that this slip sheet was only placed for the lower
extensometers.
352 G.R. Koerner et al.
• After the epoxy set, the GCL panels were unfolded and laid flat on the
slope. At the crest of the slope, each GCL panel was slit approximately
4 m long at mid-width. The slit enabled the lower five extensometers to
exit from beneath the GCL and project a straight line to the monitoring
station.
• In the same fashion as the lower extensometers, the upper extensometers
were set and then tied off at the reference stake, It should be mentioned
that the ends of the extensometer conduits near the crest of the slope were
tagged as extensometer no. 1 through no. 5 via the appropriate number of
bands around the conduit made with black electrical tape.
One band represented the no. 1 extensometer, and five bands represented the
no. 5 extensometer. In addition, the upper extensometers were marked with
orange paint to differentiate them from the lower extensometers.
A team of five technicians installed the extensometers at the site. Extens-
ometer installation appeared to be the time-limiting factor in the construc-
tion sequence of the test plots. The five technicians could install 60
extensometers on a good day. This translates into a top speed of three GCL
plots per day.
Monitoring stations used for this project were assembled at Drexel Univer-
sity in Philadelphia, PA and shipped to the site. As can be seen in Fig. 9,
each GCL panel had its own monitoring station. Therefore, there were two
monitoring stations per test plot. Figure 12 shows that each monitoring
station held ten extensometers. In so doing, both upper and lower extens-
ometers of a single panel could be read at any one monitoring station.
All the parts needed for the monitoring station were obtained from a
general hardware store. Table 3 presents a parts list of the items used in the
assembly of the monitoring stations. Each monitoring station required
approximately 2h to assemble. A total of 28 monitoring stations were
prepared for this project. Monitoring stations were prepared as outlined in
the following steps.
• A wood platform was constructed from a 0.6 m by i.2 m sheet of plywood
and a 50 mm by 75 mm wooden stiffener screwed around the perimeter of
the plywood.
• The platforms were primed and painted.
• Yardsticks with grommeted ends were glued and nailed to the platform in
clusters of five.
• Eyelets were screwed into place at the base of the yardsticks, and holes
were drilled through the platform at the grommet location.
Instrumentation for monitoring.field performance o[ the Cincinnati GCL test plots 353
Upper
Extensometers
Hr°lcemWmiteht
/ n s ~ ,----Meter Sticks
Lower ~
~!~i~?~...........
ibutor
Fig. 12. S c h e m a t i c d i a g r a m o f e x t e n s o m e t e r m o n i t o r i n g s t a t i o n .
• A cover tarp for protection from the weather was fastened to the top of
the platform with nails.
• Front and back legs were mitered and drilled to fit the platform with
respect to the appropriate slope angle.
The monitoring stations were installed after the test plots were fully
constructed. During panel layout, extensometers were temporarily tied off to
reference stakes in order to facilitate construction. The GCL slopes were
built from the top down. Therefore, construction personnel needed room to
manoeuvre at the crest of the slope. Installation of the monitoring stations
prematurely would have delayed construction and may have resulted in
monitoring station damage. Installation of the monitoring station is outlined
in the following steps.
• The mitered legs of the monitoring station were attached in the field with
lag bolts.
• The location of the monitoring station was spotted so that it would
straddle the 10 extensometers leading to the reference stake with the front
legs of the monitoring station located at the center of the anchor trench.
• With a gas-powered, two-man auger equipped with a 100-ram diameter
auger bit, holes were drilled for the four legs on the monitoring station.
The holes were each 0.6m deep.
354 G.R. Koerner et al.
TABLE 3
Monitoring Station Parts List
• Upon cleaning out the augured holes with a hand auger, the legs were
dropped into position. The monitoring station was leveled and aligned.
• The augured holes encompassing the legs of the monitoring station were
then backfilled with 178 N of dry concrete mix. Residual subgrade moist-
ure adequately hydrated the concrete in a 24-h period.
• After the monitoring station was set, the extensometers were cut free of
the reference stake. The cables of the extensometers were then threaded
through the eyelets of the monitoring station, fitted with an indicator
sleeve, dropped through the grommet at the end of the yard stick and then
attached to a lead weight.
• The indicator sleeve was then crimped at a prescribed distance down the
yardstick. This distance determined the gross movement in the extens-
ometer relative to the reference stake used for construction purposes.
• After all ten extensometer cables were threaded through the correct loca-
tions in the monitoring station, the protective cover was folded over the
monitoring station. Whenever the extensometer readings were taken, the
eight screws holding down the cover were removed so that the cover could
be temporarily folded back.
• Finally, the tarp cover of each monitoring station was labeled with its
appropriate identification letters. For example, 'G-L' would identify test
plot 'G', the left hand panel.
E
E
300
y = - 0.16387 + 0.99425x
/ R^2 = 0.99
200
~a
L
c}- i 1 st Trial
100- i 2 n d Trial
E 3 r d Trial
~a
100 200 300 400
Actual movement (ram)
Fig. 13. E x t e n s o m e t e r c a l i b r a t i o n curve.
800 i!
I
Z
600
/
f i
I
400 I
f
.a
200
/ i
I
J .
0 3 4
Displacement (mm)
Fig. 14. E x t e n s o m e t e r load versus d i s p l a c e m e n t curve.
INSTRUMENT PERFORMANCE
Moisture sensors
. . . . . . . . . . . . . . . . . . .
"-i 20304050607080 i!
10
0
0 100 200 300 400 500
Time (days)
•- 9O I
80
0¢9"~0 -'9-'0-'-':~--- °
/
Plot Lo~ ion: Middle
60
50
~ 4O
~ ao
'°I
1d __ _
O0 200 300 400 500
Time(days)
100 .~L~,,--°-.. ,,~ '. =_ ,,
i
•-
p
80
70
60
5O
40
~ ao
~ 20
10
The data in Fig. 15 show the subsoil to be near saturation at the toe, mid-
height and crest of the slope. The GCL/subsoil interface (here, the lower side
of the G C L is a geomembrane) is wet but not likely saturated (at least the
fiberglass sensor is not saturated). The most interesting point is that the
fiberglass sensor that was against the bentonite side of the GCL, and over-
lain by a geomembrane, indicated near saturated conditions for the toe and
mid-slope locations. Since the sensors and bentonite were 'sealed' between
two geomembranes and the general opinion was that the bentonite should
not have access to sufficient water to hydrate, some question as to the relia-
bility of the sensors was raised.
The GCL was destructively sampled on 8 March 1995 (about 3months
after installation). Moisture contents of the bentonite were measured grav-
imetrically (ASTM D2216) and are shown (in Fig. 16) as per plot location.
The initial (as-installed) moisture content of the bentonite was 15-25%. The
high moisture contents at the toe and mid-slope confirmed the moisture
sensor readings. Fig. 17 illustrates the displacement of the left and right
panels of plot F.
The moisture sensor performance has been satisfactory. The sensors have
been reliable with few failures. Their limitation is that exact moisture content
is not predictable; however, they do enable one to see trends in moisture
change and to suggest when the bentonite is nearing hydration. This was
Top of Slope
27 7 33
Water ~" I ~o7
Content /
(%)
.__..._Deformation
42nn • u Sensor
34 2 8 Cables
m34
27
86
Toe of Slope
Fig. 16. Moisture content of the bentonite in GCL of Plot F sampled on 8 March 1995,
3 months after installation.
360 G . R . Koerner et al.
50
\.
E 350
_,,., 450 1
.~_ 550 ,
650
750 ]
Downslope
I~ .Left Panel~ Right Paneli
Fig. 17. Typical displacement versus time for plot F (Gundseal, bentonite side up, 2:1 slope).
Gauge 5 is the extensometer nearest the toe of the slope.
Extensometers
~g
C i T --~--- No. 5
350
!! o 2 3® I
25
T i m e {days}
~ 0
k/ ~ 100 150 200 250 300 350
25
T i m e (days)
Fig. 18. Differential displacement versus time for plot A ( G u n d s e a l , 3:1 slope) left and right
panels.
figure) panels of Plot 'A'. It is interesting to note that the left panel of plot
'A' shows a small positive response. This positive differential deformation is
indicative of the anticipated response of the top carrier layer of the GCL
moving downslope more than the bottom carrier layer of the GCL. The
results of the right panel of plot 'A' show a small negative response. This
surprising response is indicative of the bottom carrier layer of the GCL
moving downslope more than the top carrier layer of the GCL. This
362 G . R . Koerner et al.
o ~
~7~ 125 CUT ---m-- No., k/J- -"--..~
~ ~ No. 2
~ 250 ---~.--- N(,. 3
500
~ 125
~ 250
~ 375
--*- - No. 3 CUT ~ . "v
---o-- No. 4
500
A No. 5
Fig. 19. Differential displacement versus time for plot F (Gundseal, Bentonite side up, 2:1
slope) left and right panels.
TABLE 4
M a x i m u m Total and Average Differential Deformation of G C L s at Gauge No. 5 at the Toe
of the Slope after 475 days
"An abrupt and complete slide occurred at the g e o m e m b r a n e - G C L interface of the test plots
marked. Consult Koerner et al. (1997) for specifics. The test plots were rendered unusable for
determining mid-plane shear strength after the slides occurred. Therefore, the deformation
data of these plots are limited.
364 G . R . Koerner et al.
reliable and economical. The generated data can be read directly at the
monitoring station and do not require normalization or correction. The
limitations of the extensometer are an accuracy of • 10 ram. Considering the
extent of the instrumentation and the field service conditions, these extens-
ometers are well suited for the task at hand.
The extensometers were relatively inexpensive; the total cost for all extens-
ometers including monitoring stations was $6555. An additional $25000 was
required for field assembly and installation. All 280 extensometers were instal-
led within 2 weeks by six highly skilled and motivated field technicians.
SUMMARY
A total of 120 moisture sensors (60 gypsum block type and 60 fiberglass
wafer type) and 280 extensometers were installed to monitor the field
performance of geosynthetic clay liners (GCL) used at 14 full-scale landfill
test plots. The objective of placing the moisture sensors was to monitor the
moisture contents of the bentonite in the GCLs and that of the subsoils. The
objective of installing the extensometers was to measure the total deforma-
tion of the GCLs with respect to the slope and the differential deformation
of the G C L with respect to itself.
The instrumentation has performed well at this site for 2 years. Both types
of moisture sensors are less sensitive than originally envisioned ( i 5 0 %
moisture content); however, the moisture sensors are being used to track
moisture trends (i.e. onset of wetting and full saturation) rather than precise
moisture contents. Extensometer sensitivity is approximately + 1 0 m m . This
sensitivity implies that the extensometers are better suited for measuring
total deformation than for differential deformation; however, they are more
than adequate for the task of predicting movement trends.
The primary lessons learned at this site with regard to instrumentation are
that redundancy is very important but must be balanced with cost consid-
erations. Data collection from such a large and heavily instrumented site
involves considerable time and accurate accounting. When dealing with a
large test simulation like that discussed in this paper, it can be beneficial to
forgo some instrument sensitivity in exchange for more easily obtained,
comparable data, using robust monitoring equipment.
ACKNOWLEDGEMENTS
The authors wish to thank the US EPA for primary sponsorship of this
project via cooperative agreement CR-821448. The authors also wish to
Instrumentation for monitoringfield performance o/ the Cincinnati GCL test plots 365
thank Robert E. Landreth and David A. Carson for serving as project offi-
cers, and Majdi A. O t h m a n for his help during field installation.
REFERENCES