TEST REPORT Page: 2/4
High Voltage Laboratory
1. Transformer markings
2. Test conditions
Test equipment
Recurrent surge generator, Haefely
Digital oscilloscope, Tektronix, type DPO 4054, 2,5 Gs/sec.
Test voltages
Impulse voltage T1 = 0,5 µs (± 20 %), T2 ≥ 50 µs, Up ≈ 150 V
Test connection
Output of the recurrent surge generator was connected to transformer primary terminal P1. A
low voltage impulse was applied between P1 terminal and earth. The transmitted overvoltage
was measured at the open secondary terminals through a 50 Ω coaxial cable terminated with
the 50 Ω input impedance of an oscilloscope.
fiet10-36/2
No.:…034218
TEST REPORT Page: 3/4
High Voltage Laboratory
3. Test results
According to the recorded primary input and secondary output voltage peak values, instrument
transformer fulfilled the requirements regarding transmitted overvoltage limits defined in
IEC 61869-1:2007, Table 9.
fiet10-36/2
No.:…034218
TEST REPORT Page: 4/4
High Voltage Laboratory