Professional Documents
Culture Documents
ABB
Contents
Introduction 4
Individual Room Temperature Control 5
Heating and Air-conditioning Systems 6
Heating Systems 6
Air-conditioning Systems 7
The Control System 8
Different Types of Control System 9
2-point Control System 9
Continuous PI Control 10
Discontinuous PI Control (PWM control) 11
2-step Heating System 12
Which control system for what heating or
air-conditioning system? 13
Planning/Parameterizing 14
Project Planning 16
Installation Site of the Radiator 16
Installation Site of the Room Thermostat 16
Modes of Operation of a Room Thermostat 18
Parameterizing of the Heating/Cooling System with the ETS 20
Romm Thermostat 6134-102 20
Busch-triton® 6326-101 Room Thermostat 21
2-step Heating 22
Setpoints 2 23
Heating Actuator 25
Individual Modes of Operation for the Individual Rooms 26
EIB in Large Commercial/Public Buildings 28
Requirement-oriented Control of the Inlet Temperature 30
Examples 32 31
Equipment Levels 32
Planning Tables 34
Tipps and Tricks 36
Fault Analysis 38
Introduction
4
Individual Room Temperature Control
Bathroom WC
22 °C 20 °C
Vestibule
16 °C
Children’s Kitchen
room 18 °C
21 °C
Advantage
The advantages of individual room tem-
peratures control are obvious:
5
Heating and Air-conditioning Systems
Heating Systems
Radiator Radiators are the most In the case of radiators, dif-
widely used type of ferentiation is made
heating system. The water between systems with a
is heated to a specific tem- normal inlet temperature
perature in a central boiler (45 – 70°C) and those with
(inlet temperature between a lower inlet temperature
35°C and 70°C). The (30 – 45°C), normal inlet
heated water is conveyed, temperatures being
via a system of pipelines, required for small radiators.
to the radiators, which con- In the last few years, large-
vey heat into the room as a format radiators have also
result of air convection. been being used in
individual cases. In such
The radiator is a system cases, the boiler need only
which reacts relatively supply the radiator with
quickly and is used both in water with a low inlet tem-
residential and perature.
commercial/public
buildings.
Hot-water Fan Heater With this type of hot-water blow the air through the
heating system, the heating coil and into the
heating coil is heated room.
by the hot water flowing
through this. The fans
6
With an electric convector room, similarly to the Electric Convector Heater
heater, a fluid (e.g., oil) is radiator, as a result of air
heated by by means of hea- convection.
ting rods. The heater
conveys heat into the
Air-conditioning Systems
Air-conditioning systems installed in many commer-
are being used more and cial/public buildings,
more frequently, even in because the productivity
our part of the world. In the of the personnel increases
meantime, they are being distinctly as a result.
In the case of fan cooling, There is an inlet and outlet Fan Cooling
the air sucked in at a air vent in each room. The
central point is cooled (to required amount of cool air
approx. 15 - 20°C) and is controlled via a
distributed throughout the positioner and a damper.
building via a system of air
pipes.
In this case, air is cooled These units are also Heat Exchanger
via a cooling compressor offered as mobile versions,
and distributed over the which can be flexibly instal-
room via a fan. led at different locations.
7
The Control System
Room temperature
Example
Several people enter a temperature) is rising.
recreation room This results in a reduction
simultaneously. The room of the control value of the
temperature rises. The control system.
control system Consequently, the
recognizes that the actual thermal output of the
temperature (room radiator is reduced. The
room temperature
returns to the preset
value.
8
Different Types of Control System
2-point Control System
Heating or air-conditioning The 2-point controller is the specific temperature and fallen short of, the heating
systems can be controlled simplest type of control. In off again as soon as a is switched on.
by means of different this case, a control value is specific value has been
types of controller, which not calculated. The control- exceeded. When the
will be described in the ler switches the system on hysteresis is exceeded, the
following chapter. when the room temperatu- heating is switched off and
re has dropped below a when the hysteresis is
Example Room
thermostat
Setpoint 20°C, hysteresis 1 K. continues to radiate stored
The heating is switched on at heat into the room after the Setpoint temperature
19°C and off at 21°C. flow of water has been cut
off. There is a similar system
On the one hand, there is the delay when the heating is
advantage of a simple control switched on. Slow-reaction
and on the other, the heating or cooling systems t
disadvantage of a constantly cannot be controlled via a Control value
transmitted
fluctuating room temperature. 2-point controller, because 1
very wide overswing would
Overswing of the occur and result in considera-
temperature occurs because bly less comfort.
the positioner takes approx. 3
minutes to close completely. 0
In addition, the radiator also t
9
Continuous PI Control*
80 %
60 %
40 %
20 %
0%
t
10
Discontinuous PI Control (PWM control)
In the case of PWM always based on a constant minutes (20% of 15 into a new PWM.
control (pulse-width cycle time. If the controller minutes) and, subsequent-
modulation), the values calculates a control value of ly, a "0" for 12 minutes, is
(0...100%) calculated on 20%, then, if the "cycle transmitted. After expiry of
the basis of the control time of the discontinuous the cycle time, the actual
algorithm are converted control value" is 15 control value of the control-
into a PWM. This is minutes, a logical "1" for 3 ler is again converted
0
0 15 30 45 60
t in minutes
10% on (1.5 min) 60% on (9 min) 40% on (6 min)
90% off (13.5 min) 40% off (6 min) 60% off (9 min)
11
2-step Heating System
The 2-step heating system correspondingly long time (in e.g., a radiator system) is
is very often used in conjunc- some cases, up to several used.
tion with an underfloor hea- hours).
ting system. Underfloor hea- In order to shorten the
ting is a system which heating-up phase, a
reacts very slowly. Heating- supplementary, quick-
up of the room takes a reaction heating system
Supplementary stage
12
Which control system for what heating or air-conditioning system?
Hot water In this case, the hot-water • Continuous PI control • Alternatively, the 2-point
Fan Heaters circuit is controlled. A con- Set change for auto- control can be used here
tinuous control is ideal. matic transmission to as soon as the fan is con-
As a result, the temperatu- 5%. trolled together with the
re of the air stream re- hot-water circuit
mains relatively constant.
• PWM control
Chilled Beams
Cycle time 15 minutes
• 2-point control
Heat Exchanger
Hysteresis 0.5K - 1.5K
13
Planning/Parameterizing
In our Busch
Installationsbus® EIB and
Busch Powernet® EIB
range of products, three
room thermostats are avai-
lable which can be used for
both systems.
14
Thermoelectric The thermoelectric positio- By means of an adaptation
Positioners ners 6164/10 (230 V) and check, it can immediately
6164/10 and 6164/11 6164/11 (24 V) are used, be seen whether the
together with the heating positioner is seated correct-
actuator 6164 U, or a ly on the valve adaptor.
switch actuator, to control Four valve adaptors are
heating systems and available to enable adaptati-
cooled ceilings. The on to the angle-type valves
positioners have a function of the different
indicator, which indicates manufacturers.
the state of the positioner
(open or closed). This
ensures clear functional
definition.
TP Controller EIB 6100 For each of the transmis- In addition, the two
Controller 6910 sion mediums, the Busch devices provide information
Powernet® EIB and Busch information on the statuses
Installationsbus® EIB, a in the building.
time controller is available. The vacation mode, or pre-
With up to 100 time sence simulation, makes it
programs, this is ideal for appear that building is
controlling the temperature occupied, even when no-
in individual rooms. one is there.
15
Project Planning
The functionality and scope sponsor be determined. accordance with his/her capacity of the spatial
of an EIB unit must be de- In the initial discussion present, as well as future, arrangements, the type of
fined and planned in the with the customer, the requirements. In principle, device and the functions
initial phase. In this different applications possi- project planning is simply are defined.
context, it is important that ble should be explained, in the translation of the
the requirements of the order to be able to plan an planned installation into
end consumer/building optimum installation in reality. In this context, the
In order to achieve
Note
uniform heat distribution
All pipes in the system
in the room, the radiator
are to be properly and
should be installed at the
adequately insulated. In
coldest point. This is
well-insulated buildings,
usually under the window.
inadequately insulated
The radiator should be at
pipes alone can heat the
least as wide as the
rooms (when the angle-
window.
type valve is closed).
Control is then no
longer possible.
Attention
When a room thermostat is
used, there must be no
other uncontrolled heating
systems in the room.
approx. 150 cm
16
Room thermostat Near electrical
(RT) opposite the consumers
radiator (heat radiation)
On an Room thermostat
exterior wall a wide distance
from the radiator
radiator
RT
17
Project Planning
The room thermostats In the nighttime mode, the The comfort mode has the
have 4 modes of operation temperature is lowered fur- next highest priority to the
which differentiate, in each ther when heating (or anti-freezing mode, then
case, between 4 tempe- increased when cooling). comes the nighttime mode.
rature levels in the heating In the anti-freeze/heat- If none of the abovemen-
or cooling mode. protection mode, the tioned modes of operation
In the comfort mode, the setpoint temperature is is selected, the room
highest temperature level lowered, e.g., to 7°C, if a thermostat is in standby
(e.g., 22°C) is selected window is opened. It is not mode.
when heating, and the recommendable for the
lowest cooling level (e.g., heating to be switched off
24°C) when cooling. completely, because other-
In standby mode, the wise, the piping system of
setpoint temperature for the heating could freeze.
Nighttime Comfort Anti-freeze/Heat-
the heating is slightly lowe- As far as the room thermo- object object protection object
red (e.g., to 20°C). If the stats are concerned, anti-
controller is in cooling freezing mode takes the Mode of operation
mode, the setpoint tempe- highest priority, i.e., when Anti-freeze 1
rature is increased the anti-freeze mode is Comfort 1 0
accordingly (e.g., to 26°C). active, a switchover cannot
Nighttime 1 0
This mode of operation is be made to another mode
0
intended for short periods of operation. The anti- Standby
of absence. The room can freeze mode must first be
then be heated up (or deactivated (e.g., the Simplified illustration of the modes of operation
cooled down) more quickly window(s) must be closed
as required. again).
Object
Comfort 0 1 X
Nighttime 0 0 1
Standby 0 0 0
18
Switchover to If the comfort object is set
Comfort/Standby Mode to "1", the comfort mode is
via a Central activated; if it is set to "0",
Command/Timer the standby mode or the
nighttime mode (if the night-
time object = 1) is activated.
Switchover to Nighttime In order to changeover If a switchover from the This switchover can be
Mode via a Central from the standby mode comfort mode to the night- made by means of a scene
Command/Timer into the nighttime mode, time mode is made, the application of the timer, or
the nighttime object must comfort object must be set by transmitting two group
be set to "1". to "0" and the nighttime addresses one after the
object to "1". other.
Window Contacts Window contacts are used The room thermostat auto-
to allow additional energy matically switches to a set-
to be saved. If, in addition point temperature of, e.g.,
to the room thermostat, 7°C. The heating system
window contacts are instal- should not be completely
led, the heating system switched off, because it
switches to anti-freeze could freeze in winter.
mode ("1" on the anti-
freeze/heat-protection
object).
19
Parameterizing of the Heating/Cooling System with the ETS
Room Thermostat 6134-102*
Folder** "Configuration of
Heating/Cooling System"
20
Busch triton® 6326-101* Room Thermostat
Folder "Heating"
Folder "Cooling"
21
2-step Heating
Folder "General"
Example
Setpoint temperature 20°C
Setpoint difference of basic step to
additional step: 2 K
Hysteresis (one-sided)
of the additional step: 1 K
22
Setpoints
Parameter "Setpoints"
23
Setpoints
Example
Basic setpoint for heating : 21 °C Comfort value, heating = 21 °C In this example, the
manual setpoint specified
➾
Decrease, standby heating : 2K Standby heating = 19 °C (21°C - 2K)
is "0". Otherwise, in the
Decrease, nighttime heating : 4 K Nighttime heating = 17 °C (21°C - 4K) standby and comfort
Neutral zone : 3K Comfort value, heating = 24 °C (21°C + 3K) modes of operation, this is
added on.
Increase, standby cooling : 2K Standby cooling = 26 °C (21°C + 3K+ 2K)
Increase, nighttime cooling : 4K Nighttime mode, cooling = 28 °C (21°C + 3K+ 4K)
In commercial/public buildings, it is
recommendable to limit, or even block,
local adjustment of the setpoint.
Example
24
Heating Actuator
25
Individual Modes of Operation for the Individual Rooms
Bathroom WC
Vestibule
Kitchen
Children´s room
Note
In the case of an underfloor taken into consideration in
heating system two the time profiles. That is, if
temperature levels usually the living room should be
suffice (comfort and stand- warm about 7.00 a.m., the
by). As the underfloor mode of operation must be
heating system reacts very changed correspondingly
slowly, this should be earlier (e.g., at 6 a.m.).
26
In the following, some profi-
les of modes of operation
are shown by way of exam-
ple. The profiles can be indi-
vidually adapted to the end
consumer’s requirements.
Standby
Nighttime
Nighttime
Standby
Nighttime
Standby
Nighttime
27
EIB in Large Commercial/Public Buildings
Connection of the EIB to a high-level system
In large commercial/public and, if appropriate, con- access control systems, elements between the
buildings, a so-called nects different bus systems can, for example, also be different bus systems).
Management, or Com- with each other. used. These systems are
mand Level is sometimes Apart from the EIB, DDC then connected to the
used. This Command Level (Direct Digital Control) Management, or
controls and visualises all systems, special security Command Level, via
processes in the building systems, lift control and gateways (connecting
The Management System For the boiler system (e.g., As a rule, the gateways are Due to its wide use,
then specifies, e.g., the DDC-controlled), it can, placed at disposal and plan- connection of the EIB is
basic setpoint temperature e.g., be important to ned by the those installing unproblematical.
for the room thermostat. receive information from the Command or Manage-
This information is then the individual room ment Level, so that merely
converted by the gateway regarding the actual, or set- the information flow via the
into an EIB telegram. point temperatures, or the gateway need be agreed
control values. on.
Distributor
TLN 1 TLN 1
e.g., Lift
TLN 2 TLN 2
TLN 3 TLN 3
TLN 4 TLN 4
TLN X TLN X
28
Previous DDC Connection
Example for a room
EIB Gateway Command Level
Summer Compensation
29
Requirement-oriented Control of the Inlet Temperature
Inlet temperature in °C
dy equippped with an inlet Even this adjustment
55
temperature control. In saves energy. However, it
these cases, the inlet tem- has the disadvantage that it
50
perature is adjusted to the does not take into account
outdoor temperature. This the actual heat require- 45
prevents unnecessary heat ment, for, during the night,
loss of the boiler and the the temperature in the 40
piping system in the case rooms is lowered a great
of relatively high outdoor deal, so that a high inlet 35
temperatures (> 8°C). With temperature is no longer 0 5 20
<-15 -10 -5 10 15
these outdoor tempera- necessary.
tures, the boiler of the hea- Outdoor temperature in °C
ting system need not be
operated with high inlet
temperatures.
For quite a long time now, In principal, these controls Circulating pump 1 bit
modern boiler controls are configured as follows.
(DDC’s) for large commer- The optimum inlet tem-
cial/public buildings have perature for the heating Control value Switch
systems is calculated on 1 byte (1 bit) Boiler Boiler actuator
taken this fact into conside- Room 1
ration. the basis of the control inlet-
values of the different Control value temperature P
In the last few years, rooms (up to approx. 30) 1 byte (1 bit) control
Room 2 Inlet
similar boiler controls for and continuously adjusted
the residential sphere, with to the current heat require- Control value
connections to the EIB ments. 1 byte (1 bit)
Room 3
have been being offered by
the leading boiler manufac- In addition, the circulating
turers (e.g., Viessmann, pump is only switched on Return
Buderus and Junkers). when there is a heat requi-
rement. Control value
1 byte (1 bit)
Room x
In conjunction with
individual room temperatu-
re control, this system
offers a maximum saving
in energy as far as heating
systems in the residential
sphere are concerned.
30
Examples
We are prepared to do a lot are installed. These ensure using an additional timer. Residential building
for our well-being. At the that, when a window is Once programmed, each
same time, Residential opened, the heating room is automatically
building we, naturally, do system automatically swit- heated to our desired tem-
not want to "send our ches over to anti-freeze perature. Even the settings
money up in smoke". mode. No matter how long during a vacation and other
A heating system with indi- the ventilation procedure periods of absence can be
vidual room temperature (window) lasts, the heating taken into account.
control is a step in the right system only heats with the
direction. It is even better intensity necessary to
if, apart from the individual prevent the pipes from free-
room temperature control zing (e.g., 7°C). Comfort is
system, window contacts increased even more by
In commercial/public minimize energy consump- The supplementary use of Offices and doctors‘ surgeries,
buildings such as offices tion. Since the people who a presence detector in sports centres, and public buildings
and administrative build- spend time in these rooms commercial/public build-
ings, administrative build- are not usually responsible ings would be a further
ings, doctors‘ surgeries, for the costs, attention is step towards more comfort.
department stores and seldom paid to the effect Apart from the advantages
sports centres, a heating of an open window. described, this system
department stores, system The additional use of a would also take into
with individual room timer ensures that the account all unforeseeable
temperature control results rooms are only heated times where rooms are
in distinctother commer- to the full degree at the set unoccupied. This means
cial/savings and far greater times. In other words, no that, in cases of illness,
comfort. In addition, the unnecessary energy is when sports events are
right room temperature consumed at night, at week- cancelled, or similar situa-
increases the productivity ends, or in accordance tions, the heating system
of the personnel. with the requirement is not heated up to the
profile. maximum room temperatu-
Here too, the use of a re. As a result, further
system with window energy is saved.
contacts is of advantage to
31
Equipment
Levels
In the following, a few
examples are given of the
levels of equipment
(comfort levels) for offices
and living areas.
1. Basic Level
2. Upgraded Level
32
1) The heating actuator 6164 U has an integrated binary input terminal for the connection of window contacts
3. Comfort Level
Room thermostat
Comfort To achieve the comfort level, an air-
mode conditioning system is added, as well
1 bit Heating
1 bit o. Switch Posi- as visualisation of the actual room
Nighttime 1 byte actuator 1) tioner
mode temperature.
1 bit Cooling Switch Posi-
1 bit o. actuator 1) tioner
Window Binary- Anti- 1 byte
contact input 1) freeze
1 bit
Comfort Room
setpoint temp.
2 byte 2 byte
Visualisation
LC-display, controller
4. Exclusive Level
Room thermostat
In addition to the equipment to achieve
Presence Comfort
detector mode the comfort level, in this case, a
1 bit Heating
1 bit o. Switch Posi- presence detector switches the room
actuator 1) tioner
Nighttime 1 byte thermostat to comfort mode when no
mode
1 bit Cooling persons are in the room.
Switch Posi-
1 bit o. actuator 1) tioner
Window Binary- Anti- 1 byte
contact input 1) freeze If underfloor heating is used, the
1 bit
presence detector is not recommenda-
ble, since the underfloor heating reacts
Comfort Room
setpoint temp. very slowly. When a room is entered, it
2 byte 2 byte
would take a long time before this is
heated up to comfort temperature.
33
Planning Tables
Radiator - A system which reacts relatively quickly - Ambient air may be dry
- Most widely used
- Less heat loss at low inlet
temperatures
Hot-water Fan Heater - A system which reacts relatively quickly - Usually only for industrial workshops
- Dry ambient air
Electric Fan Heater - A system which reacts very quickly - High energy consumption
Fan cooling - A system which reacts relatively quickly - Usually only viable for commercial/public
- No visible cooling unit buildings
34
Heating and Air-conditioning Systems
Continuous-action - Connection only via the bus - Only one valve controllable in each case
- High current load of the bus line
- High costs
- No status display
- Not available for Powernet
35
Tips and Tricks
36
In order to switch from the by pressing and releasing Comfort/Standby
comfort mode of operation the rocker. switchover
to the nighttime mode, the • Logic module: As the
comfort object must be set objects always have
to "0" and the nighttime opposite values – in
object to "1". The sequence nighttime mode, the
is unimportant. nighttime object is "1" and
This switchover can be the comfort object "0",
effected as follows: and vice versa – a negati
• Timer: scene application on gate can also be used.
• alpha nea ® touch sensor: • Send two telegrams in
Via the application quick succession via the
"flexible allocation", send controller or the TP
a telegram controller.
37
Fault Analysis
38
ABB