You are on page 1of 38

ABB i-bus® EIB / KNX

ABB
Contents

Introduction 4
Individual Room Temperature Control 5
Heating and Air-conditioning Systems 6
Heating Systems 6
Air-conditioning Systems 7
The Control System 8
Different Types of Control System 9
2-point Control System 9
Continuous PI Control 10
Discontinuous PI Control (PWM control) 11
2-step Heating System 12
Which control system for what heating or
air-conditioning system? 13
Planning/Parameterizing 14
Project Planning 16
Installation Site of the Radiator 16
Installation Site of the Room Thermostat 16
Modes of Operation of a Room Thermostat 18
Parameterizing of the Heating/Cooling System with the ETS 20
Romm Thermostat 6134-102 20
Busch-triton® 6326-101 Room Thermostat 21
2-step Heating 22
Setpoints 2 23
Heating Actuator 25
Individual Modes of Operation for the Individual Rooms 26
EIB in Large Commercial/Public Buildings 28
Requirement-oriented Control of the Inlet Temperature 30
Examples 32 31
Equipment Levels 32
Planning Tables 34
Tipps and Tricks 36
Fault Analysis 38
Introduction

The right room low or too high humidity


temperature contributes and to light or too heavy
decisively towards our fee- clothing. In these cases,
ling of well-being in all concentrations of heat, or
situations. Needs differ heat losses occur in the
greatly in this respect, body. A person feels
depending on where one comfortable when the air
lives and how one temperature, air
personally reacts to tempe- movement, humidity and
ratures. While room wall temperatures are in a
temperatures of 16°C to balanced ratio to their
18°C suffice for the kitchen activity and clothing.
and bedroom, we like to Comfortableness and well-
have a cosy temperature of being are also favourably
21°C in the living room influenced by the
and, perhaps, even 22°C in cleanliness of the air and a
the bathroom. low noise level in the
room.
A feeling of well-being,
both in private life and in With an increasing demand
the work environment, is for comfort and a reduction
extremely important for us in energy consumption,
as human beings. environmental conscious-
Consequently, thermal ness becomes more and
comfort is also very impor- more a part of our lives. In
tant as far as the health private households in
and well-being of people is Germany, approx. 70% of
concerned, because they the energy consumed is
spend 95% of their time in for heating and hot water.
buildings. Calculated on the basis of
the energy consumption in
But the need for comfort the country as a whole,
and cosiness does not cea- 30% of the total energy is
se when we leave our own consumed for heating and
"four walls". All the other hot water alone. The objec-
indoor areas where we tive when planning any
spend time (shopping cent- heating/air-conditioning
res, restaurants, sports system is to achieve the
centres, offices, ....), as dif- desired level of comfort
ferent as they are from one and cosiness while saving
another, should also have as much energy as
an appropriate possible. This is of benefit
temperature. to the environment, our
purse and our well-being.
A person feels uncomforta-
ble when the body’s In the following, it will be
temperature-regulating shown how an individual
system (the skin) is subject room temperature control
to stress, e.g., as a result system can be planned and
of too low or too high air installed without difficulty.
and wall temperatures,
strong air movements, too

4
Individual Room Temperature Control

Apart from a central inlet a room are set (time and/or


temperature control, requirement-dependent)
heating systems must have via the room thermostat
devices for controlling the and the desired temperatu-
temperature in individual re constantly maintained.
rooms. In this context, the
control task "requirement- The objective is to
oriented temperature" beco- accelerate the
mes increasingly important incorporation of heating
as far as our feeling of well- systems in the automatic
being is concerned. building services control
Individual room thermostats system. This creates
fufil this prerequisite. They further potential for saving
ensure that each individual energy and results in much
room has the desired and greater comfort. An additio-
requirement-oriented nal 6% of energy can be
temperature. The different saved by lowering the
degrees of heat required in room temperature by as
little as 1°C.

Bathroom WC
22 °C 20 °C

Vestibule
16 °C

Bedroom Living room


18 °C 21 °C

Children’s Kitchen
room 18 °C
21 °C

Advantage
The advantages of individual room tem-
peratures control are obvious:

• Additional saving in • Improved


energy productivity
• Greater comfort • Increased motivation
• Individual customer • Longer time spent in
requirements can be the rooms
fulfilled

5
Heating and Air-conditioning Systems

In the majority of cases, commercial/public System in the following),


the heating and air- buildings). you can control all
conditioning systems have conventional heating and
already been installed, or With the Busch air-conditioning systems
they are specified by a hea- Installationsbus® EIB and available on the market.
ting, air-conditioning and the Busch Powernet® EIB
ventilation planner (for (both referred to as EIB

Heating Systems
Radiator Radiators are the most In the case of radiators, dif-
widely used type of ferentiation is made
heating system. The water between systems with a
is heated to a specific tem- normal inlet temperature
perature in a central boiler (45 – 70°C) and those with
(inlet temperature between a lower inlet temperature
35°C and 70°C). The (30 – 45°C), normal inlet
heated water is conveyed, temperatures being
via a system of pipelines, required for small radiators.
to the radiators, which con- In the last few years, large-
vey heat into the room as a format radiators have also
result of air convection. been being used in
individual cases. In such
The radiator is a system cases, the boiler need only
which reacts relatively supply the radiator with
quickly and is used both in water with a low inlet tem-
residential and perature.
commercial/public
buildings.

Underfloor/Wall Heating Water flows through a temperature can be


system of pipes installed in lowered overnight is
the floor. As in the case of restricted. That is, the tem-
radiators, the water is hea- perature cannot be
ted to 30 – 45°C in a boiler. lowered beyond a specific
value (e.g., 4 – 6 K) for the
As a rule, the inlet nighttime mode. You can
temperature is adjusted to obtain further information
the outdoor temperature. on this from the heating
That is, when the outdoor engineer responsible for
temperature is low, a servicing the system.
higher inlet temperature is
selected. Adjustment is In principle, wall heating
made directly at the boiler, systems operate in the
to which an outdoor sensor same way as underfloor
is connected. heating systems and,
therefore, will not be dealt
In the case of some under- with separately here.
floor heating systems, the
degree to which the

Hot-water Fan Heater With this type of hot-water blow the air through the
heating system, the heating coil and into the
heating coil is heated room.
by the hot water flowing
through this. The fans

6
With an electric convector room, similarly to the Electric Convector Heater
heater, a fluid (e.g., oil) is radiator, as a result of air
heated by by means of hea- convection.
ting rods. The heater
conveys heat into the

Similarly to a hand-held The system reacts very Electric Fan Heater


hair dryer, air is blown into quickly, since no additional
the room viaheating coils. heat-carrier (e.g., water or
As a result, the room is oil) need be heated up.
heated.

Air-conditioning Systems
Air-conditioning systems installed in many commer-
are being used more and cial/public buildings,
more frequently, even in because the productivity
our part of the world. In the of the personnel increases
meantime, they are being distinctly as a result.

In principle, chilled beams cold air at ceiling Chilled Beams


function in the same way level slowly moves down-
as an underfloor heating wards and cools the room
system. Cold water is con- uniformly. This
veyed through the cooling system is chiefly used in
pipes installed in the ceiling commercial/public
and cools the ceiling. The buildings.

In the case of fan cooling, There is an inlet and outlet Fan Cooling
the air sucked in at a air vent in each room. The
central point is cooled (to required amount of cool air
approx. 15 - 20°C) and is controlled via a
distributed throughout the positioner and a damper.
building via a system of air
pipes.

In this case, air is cooled These units are also Heat Exchanger
via a cooling compressor offered as mobile versions,
and distributed over the which can be flexibly instal-
room via a fan. led at different locations.

7
The Control System

A room thermostat measu- ON/OFF switching


res the actual temperature commands) by means of
and compares this with the the set control algorithm
preselected setpoint on the basis of the
temperature. difference between the
actual and setpoint tempe-
The control value is calcula- rature.
ted (e.g., in percent, or

The control value defines Setpoint + Control Control


the thermal or cooling out- temp. algorithm value
put with which the –
system is to be supplied.
Actual
temp.

The control system of a Solar irradiation


heating unit comprises the
Inlet temp. Outdoor temp. People
room thermostat, the posi-
tioner (if applicable, a Room thermostat
switch actuator), the
radiator, and the room in Setpoint + Control
Angle-
which the temperature is temp. type Radiator Room
algorithm valve
to be controlled –

Room temperature

Many factors influence the


control system,
such as:

• the inlet temperature


• the outdoor temperature
• under certain
circumstances, solar
irradiation
• people Based on the difference
between the actual and
• electrical consumers setpoint temperature, the
control system recognizes
influences, readjusts the
control value and
compensates for the
influences.

Example
Several people enter a temperature) is rising.
recreation room This results in a reduction
simultaneously. The room of the control value of the
temperature rises. The control system.
control system Consequently, the
recognizes that the actual thermal output of the
temperature (room radiator is reduced. The
room temperature
returns to the preset
value.

8
Different Types of Control System
2-point Control System
Heating or air-conditioning The 2-point controller is the specific temperature and fallen short of, the heating
systems can be controlled simplest type of control. In off again as soon as a is switched on.
by means of different this case, a control value is specific value has been
types of controller, which not calculated. The control- exceeded. When the
will be described in the ler switches the system on hysteresis is exceeded, the
following chapter. when the room temperatu- heating is switched off and
re has dropped below a when the hysteresis is

Example Room
thermostat
Setpoint 20°C, hysteresis 1 K. continues to radiate stored
The heating is switched on at heat into the room after the Setpoint temperature
19°C and off at 21°C. flow of water has been cut
off. There is a similar system
On the one hand, there is the delay when the heating is
advantage of a simple control switched on. Slow-reaction
and on the other, the heating or cooling systems t
disadvantage of a constantly cannot be controlled via a Control value
transmitted
fluctuating room temperature. 2-point controller, because 1
very wide overswing would
Overswing of the occur and result in considera-
temperature occurs because bly less comfort.
the positioner takes approx. 3
minutes to close completely. 0
In addition, the radiator also t

In the case of the PWM In fact, if there are several


and the 2-point control radiators in a room, this
system, the room combination is far cheaper
thermostat triggers a than the continuous
switch actuator. The switch controller, because several
actuator opens or closes thermoelectric positioners
the positioner. This can be controlled via a Room thermostat Heating actuator Thermoelectric
(or switch actuator) positioner
combination is more favou- single positioner channel.
rable in terms of cost than
the continuous-action posi-
tioner.

9
Continuous PI Control*

The continuous controller only transmitted if it has


transmits the control value changed by a previously
to the bus in the form of a defined percentage.
1-byte value (0...255). In
order to reduce the bus
load, the control value is

The upper diagram shows, Calculated


control value
by way of example, a
calculated control value. 100 %
The control value is only 80 %
transmitted if it has
60 %
changed by 10% (1, 2, or
5% are also parameteriz- 40 %
able). The lower diagram 20 %
shows at which point in 0%
time the control value is t
transmitted to the bus. Control value
transmitted
100 %

80 %

60 %

40 %
20 %
0%
t

The room temperature is


constantly maintained by
the control algorithm.
The control value transmit-
ted acts on a continuous-
action positioner, which is
mounted on an angle-type Room thermostat Continious-action
valve. This doses the quan- positioner
tity of heat through the
radiator (0 to 100%).

*PI control is a control


engineering term which
describes a controller with a
proportional and an integral
component.

10
Discontinuous PI Control (PWM control)

In the case of PWM always based on a constant minutes (20% of 15 into a new PWM.
control (pulse-width cycle time. If the controller minutes) and, subsequent-
modulation), the values calculates a control value of ly, a "0" for 12 minutes, is
(0...100%) calculated on 20%, then, if the "cycle transmitted. After expiry of
the basis of the control time of the discontinuous the cycle time, the actual
algorithm are converted control value" is 15 control value of the control-
into a PWM. This is minutes, a logical "1" for 3 ler is again converted

The upper diagram shows, The room temperature is Calculated


control value
by way of example, a also constantly maintained
100 %
calculated control value. via the control algorithm. 60 %
The lower diagram shows Averaged out over the 80 % 40 %
the control value converted time, the behaviour of the 60%
10 % 20 %
into a PWM. These control system is the same 40 %
ON/OFF telegrams are as with a continuous 20 %
transmitted to the bus and controller. 0%
operate a switch actuator, Since heating systems 0 15 30 45 60
which acts on a react relatively slowly, in t in minutes
Control value
thermoelectric positioner. almost all cases, a PWM transmitted
1
control suffices. Even a
radiator, which is
considered to be a system
which reacts relatively
quickly, has time constants
of more than 30 minutes
and can, thus, be 0
0 15 30 45 60
controlled via a PWM t in minutes
control without any loss in 10% on (1.5 min) 20% on (3 min) 60% on (9 min) 40% on (6 min)
comfort. 90% off (13.5 min) 80% off (12 min) 40% off (6 min) 60% off (9 min)

If one changes the Calculated Elevation of the


control value Setpoint temperature 90 %
setpoint temperature, the
100 %
control value is 60 %
recalculated and operation 80 %
40 %
in the cycle which has 60%
10 % 20 %
begun continues in 40 %
accordance with the new 20 %
control alue. 0%
0 15 30 45 60
t in minutes
Control value
transmitted
1

0
0 15 30 45 60
t in minutes
10% on (1.5 min) 60% on (9 min) 40% on (6 min)
90% off (13.5 min) 40% off (6 min) 60% off (9 min)

In the case of the PWM and In fact, if there are several


the 2-point control system, radiators in a room, this
the room thermostat combination is far cheaper
triggers a switch actuator. than the continuous control-
The switch actuator opens ler, because several thermo-
or closes the positioner. This electric positioners can be
combination is more controlled via a single Room thermostat Heating actuator Thermoselectric
favourable in terms of cost positioner channel. (or switch actuator) Stellantrieb positioner
than the continuous-action
positioner.

11
2-step Heating System

The 2-step heating system correspondingly long time (in e.g., a radiator system) is
is very often used in conjunc- some cases, up to several used.
tion with an underfloor hea- hours).
ting system. Underfloor hea- In order to shorten the
ting is a system which heating-up phase, a
reacts very slowly. Heating- supplementary, quick-
up of the room takes a reaction heating system

Immediately the setpoint When the room has been Thermal


temperature is increased heated up to a specific tem- output

considerably, the perature (e.g., setpoint tem- Supplementary stage


supplementary stage (quick- perature – 1K, parameteriza- Basic stage
reaction heating system) ble), the supplementary
switches on, together with stage is switched off. In the
the basic stage (e.g., under- meantime, the basic stage
floor heating system). The can supply the room with
room is then essentially the required thermal output
heated-up via the and then takes over comple- 10 min 1h time
supplementary stage, since te control. Thermal behaviour as soon as the basic and supplementary stages
this reacts more quickly and, are simultaneously switched on, e.g., if the heating system in activa-
thus, the thermal output is ted in the morning.
available more quickly.

The basic stage is parame- quite sufficient as far as


terized in the normal way additional heating is
(e.g., in the case of concerned, since this is not
underfloor heating: PWM used to control the
with 30 minutes cycle system, but only for the
time). A 2-point control is heating-up phase.
Basic stage

Supplementary stage

Room Heating actuators Thermoselectric


thermostat (or switch actuators) positioners

12
Which control system for what heating or air-conditioning system?

Recommendations for con- The recommendations are


trolling the different heating also summarized in tabular
and air-conditioning form in the Appendix.
systems will be given in the
following.

Radiator • With a low inlet • PWM control • With a normal inlet


temperature (30 - 45°C): Set the cycle time of temperature (45 - 70°:
PWM or 2-point control the switching control PWM control
value to 15 minutes

• 2-point control Fußboden-/Wand-


Set hysteresis to heizung
0.3K - 1K

Underfloor/Wall This system reacts very slow-


Heating ly, therefore, a PWM con-
trol with a cycle time of 20 -
30 minutes is appro-priate.
Warmwass

Hot water In this case, the hot-water • Continuous PI control • Alternatively, the 2-point
Fan Heaters circuit is controlled. A con- Set change for auto- control can be used here
tinuous control is ideal. matic transmission to as soon as the fan is con-
As a result, the temperatu- 5%. trolled together with the
re of the air stream re- hot-water circuit
mains relatively constant.

• Electric convector heater • Electric fan heater


Electric Heaters
PWM control 2-point control
Cycle time 15 minutes Hysteresis 0.5K - 1.5K

• PWM control
Chilled Beams
Cycle time 15 minutes

Fan Cooling • Continuous PI control • An alternative here is the


Change for automatic 2-point control. However,
transmission: 5% this results in a loss of
comfort, because the
cool air stream is
switched on and off.

• 2-point control
Heat Exchanger
Hysteresis 0.5K - 1.5K

13
Planning/Parameterizing

In our Busch
Installationsbus® EIB and
Busch Powernet® EIB
range of products, three
room thermostats are avai-
lable which can be used for
both systems.

Room Thermostat On the one hand, there is


6134-102 the 6134-102 in the alpha
nea® design

Room Thermostat On the other hand, with


6326-101 the 6326-101, a second
room thermostat is
available in the Busch
triton® design. Apart from
the room thermostat
function, with the three
rocker switches, it can also
be used to switch/dim
lights, as well as to operate
blinds and ventilation
systems.

Room Thermostat As the third, the Busch


6327* triton® 5-gang with room
thermostat rounds off the
range. It is an extended
version of the 6326-101
and has the same room
thermostat functions.
The 6327 has too more
rockers than the 6326-101,
which can be freely
assigned, or assigned to 4
lighting scenes. All rocker
functions can also
be infrared-controlled.

*Available as from Jan. 2001

14
Thermoelectric The thermoelectric positio- By means of an adaptation
Positioners ners 6164/10 (230 V) and check, it can immediately
6164/10 and 6164/11 6164/11 (24 V) are used, be seen whether the
together with the heating positioner is seated correct-
actuator 6164 U, or a ly on the valve adaptor.
switch actuator, to control Four valve adaptors are
heating systems and available to enable adaptati-
cooled ceilings. The on to the angle-type valves
positioners have a function of the different
indicator, which indicates manufacturers.
the state of the positioner
(open or closed). This
ensures clear functional
definition.

Heating Actuator 6164 U The heating actuator is window contacts can be


used to control thermo- connected in order to save
electric positioners which energy when windows are
control heating systems or open.
cooled ceilings. This
control takes place In the case of a Busch
noiselessly via an Powernet® EIB application,
electronic output terminal. the heating actuator can be
In addition to this replaced by a switch actua-
electronic output terminal, tor.
two input terminals are If window contacts are
available for floating intended, a Busch
contacts. For example, Powernet® EIB binary input
terminal can be used for
connecting.

TP Controller EIB 6100 For each of the transmis- In addition, the two
Controller 6910 sion mediums, the Busch devices provide information
Powernet® EIB and Busch information on the statuses
Installationsbus® EIB, a in the building.
time controller is available. The vacation mode, or pre-
With up to 100 time sence simulation, makes it
programs, this is ideal for appear that building is
controlling the temperature occupied, even when no-
in individual rooms. one is there.

Teleswitch REG A link between the switch, e.g., the heating, or


6986/10* telephone network and the sauna, on and off simply
6186 /10 EIB installation is available when one is out and about.
for each of the trans- It is also possible to query
mission mediums. With the different statuses in a
this, it is possible to building via the telephone.

*Start-up with the controller/PowerProject is in preparation

15
Project Planning

The functionality and scope sponsor be determined. accordance with his/her capacity of the spatial
of an EIB unit must be de- In the initial discussion present, as well as future, arrangements, the type of
fined and planned in the with the customer, the requirements. In principle, device and the functions
initial phase. In this different applications possi- project planning is simply are defined.
context, it is important that ble should be explained, in the translation of the
the requirements of the order to be able to plan an planned installation into
end consumer/building optimum installation in reality. In this context, the

Installation Site of the Radiator

In order to achieve
Note
uniform heat distribution
All pipes in the system
in the room, the radiator
are to be properly and
should be installed at the
adequately insulated. In
coldest point. This is
well-insulated buildings,
usually under the window.
inadequately insulated
The radiator should be at
pipes alone can heat the
least as wide as the
rooms (when the angle-
window.
type valve is closed).
Control is then no
longer possible.

Attention
When a room thermostat is
used, there must be no
other uncontrolled heating
systems in the room.

Installation Site of the Room Thermostat


150 cm from the floor and Normal
approx.30 cm
30 cm from the door frame switch
position

approx. 150 cm

16
Room thermostat Near electrical
(RT) opposite the consumers
radiator (heat radiation)

On the same Solar irradiation


wall as the
radiator

On an Room thermostat
exterior wall a wide distance
from the radiator
radiator

RT

17
Project Planning

Modes of Operation of a Room Thermostat

The room thermostats In the nighttime mode, the The comfort mode has the
have 4 modes of operation temperature is lowered fur- next highest priority to the
which differentiate, in each ther when heating (or anti-freezing mode, then
case, between 4 tempe- increased when cooling). comes the nighttime mode.
rature levels in the heating In the anti-freeze/heat- If none of the abovemen-
or cooling mode. protection mode, the tioned modes of operation
In the comfort mode, the setpoint temperature is is selected, the room
highest temperature level lowered, e.g., to 7°C, if a thermostat is in standby
(e.g., 22°C) is selected window is opened. It is not mode.
when heating, and the recommendable for the
lowest cooling level (e.g., heating to be switched off
24°C) when cooling. completely, because other-
In standby mode, the wise, the piping system of
setpoint temperature for the heating could freeze.
Nighttime Comfort Anti-freeze/Heat-
the heating is slightly lowe- As far as the room thermo- object object protection object
red (e.g., to 20°C). If the stats are concerned, anti-
controller is in cooling freezing mode takes the Mode of operation
mode, the setpoint tempe- highest priority, i.e., when Anti-freeze 1
rature is increased the anti-freeze mode is Comfort 1 0
accordingly (e.g., to 26°C). active, a switchover cannot
Nighttime 1 0
This mode of operation is be made to another mode
0
intended for short periods of operation. The anti- Standby
of absence. The room can freeze mode must first be
then be heated up (or deactivated (e.g., the Simplified illustration of the modes of operation
cooled down) more quickly window(s) must be closed
as required. again).

Object

Anti-freeze Comfort Nighttime


Anti-freeze/Heat-protection 1 XX
Betriebsart

Comfort 0 1 X
Nighttime 0 0 1
Standby 0 0 0

Table of priorities: X = status has no influence

If the controller is in stand- mode for a set time of operation: "dew-point


by or comfort mode, one (parameterizable) via the mode". In this mode of
can switch over between local pushbutton. This operation, the room
these modes of operation process is called comfort thermostat can be comple-
via the local pushbutton of extension or party time. tely switched off. The dew-
the controller. In the case of the room point mode has the highest
In nighttime mode, one thermostat 6134-102, priority.
can switch over to comfort there is an additional mode

18
Switchover to If the comfort object is set
Comfort/Standby Mode to "1", the comfort mode is
via a Central activated; if it is set to "0",
Command/Timer the standby mode or the
nighttime mode (if the night-
time object = 1) is activated.

Switchover to Nighttime In order to changeover If a switchover from the This switchover can be
Mode via a Central from the standby mode comfort mode to the night- made by means of a scene
Command/Timer into the nighttime mode, time mode is made, the application of the timer, or
the nighttime object must comfort object must be set by transmitting two group
be set to "1". to "0" and the nighttime addresses one after the
object to "1". other.

Window Contacts Window contacts are used The room thermostat auto-
to allow additional energy matically switches to a set-
to be saved. If, in addition point temperature of, e.g.,
to the room thermostat, 7°C. The heating system
window contacts are instal- should not be completely
led, the heating system switched off, because it
switches to anti-freeze could freeze in winter.
mode ("1" on the anti-
freeze/heat-protection
object).

Presence Detector A presence detector moni- If the presence detector is


Note
tors the presence of connected to the comfort
A presence detector
people in a room. If object, the room is only
is not practical in con-
someone is in the room, a heated up to comfort
junction with an
logical "1", for example, is temperature when in use
underfloor heating
transmitted. If no-one is in and to standby in the
system, because the
the room, this is registered absence of people (or
underfloor heating
with "0". nighttime, if the nighttime
system is too slow-
object = "1"). As a result,
acting.
considerable energy is
saved.

19
Parameterizing of the Heating/Cooling System with the ETS
Room Thermostat 6134-102*

Folder** "Configuration of
Heating/Cooling System"

By means of the parameter "Activation of


heat/cool function", one defines whether a
heating or a cooling system, or both, are to
be controlled.

The parameter "Type of heat/cool function"


selects the different types of controller for
the heating or cooling function.

With the parameter "Adaptation of PI


control to the heating/cooling system",
one can set the control parameters for
continuous and for PWM control. The preset standard parameters for the
different heating/cooling systems achieve
In the case of 2-point control, the very good control results for almost all
hysteresis must be entered here. constellations and need not, therefore,
be changed.

Folder "Output of Control Value"

In the folder "Output of control value",


the cycle time of the discontinuous
control value for a PWM control can be
set (e.g., 15 minutes = 900 seconds =
set > parameter to "90"). With continuous
control, the parameter "Adjustment for
automatic sending" must be parame-
terized (5% is adequate here).

With the parameter "Cyclic time for auto-


matic sending", whether the control
value (applicable for each control) is to be
additionally transmitted, e.g., every 10
minutes, is defined. It is recommendable
to always activate automatic transmis-
sion. If the control value has not been
allocated a value (e.g., during start-up),
the room could continuously heat up, or
cool down.

* When parameterizing is effected via the Controller/


PowerProject, only heating with the PWM control
and 2-step heating is available.

** A folder contains a functional grouping


of parameters within an application.

20
Busch triton® 6326-101* Room Thermostat

Folder "Heating"

With the parameters "Output of control


value" and "Type of heating", the diffe-
rent types of heating can be addressed
(continuous or discontinuous). By
means of a switching controller, a choi-
ce can be made between 2-point and
PWM control.
Otherwise, the procedure in this case
can be analogous to that in the case of
the 6134-102.

Folder "Cooling"

If the room temperature is used for


cooling, the settings can be analogous
to those for heating.

* When parameterizing is effected via the Controller/


PowerProject, only heating with the PWM control
and 2-step heating is available.

21
2-step Heating

In the following chapter,


the settings for 2-step hea-
ting will be explained on
the basis of the Busch
triton® 6326-101.

Folder "General"

2-step heating is selected in the folder


"General".
The cooling function is now replaced
by the 2nd step (additional step). As a
result, the setpoints of the cooling func-
tion are also dispensed with.

Folder "Additional Heating"

The parameter "Setpoint difference


of basic step to additional step" is used
to define at which temperature
difference below the setpoint tempera-
ture the additional step is to be
switched off.
A 2-point control is quite sufficient for
the additional heating, since this is only
switched on and off in the heating-up
phase.

Example
Setpoint temperature 20°C
Setpoint difference of basic step to
additional step: 2 K
Hysteresis (one-sided)
of the additional step: 1 K

The additional heating remains Control value


Additional step
switched on as long as the room
1 (100%) 1
temperature is lower than the "setpoint
temperature" minus the "setpoint
difference of basic step to additional
step": 20°C - 2 K = 18°C.

After this threshold has been passed, 0


0 (0%)
the additional heating is switched off.
The additional heating is only switched 17 18 20 Room temperature
in °C
on again when the room temperature is
lower than the "setpoint temperature"
minus the "setpoint difference of basic
step to additional step" minus
"hysteresis": 20°C - 2 K - 1 K = 17°C.

22
Setpoints

In this folder, the setpoints of the


different modes of operation, which are
selected from the bus via the appropria-
te object, can be set.

Switchover to comfort/standby can also


be effected via the local pushbutton.

Parameter "Setpoints"

The basic setpoint is the comfort setpoint


of the heating mode. The comfort setpoint
for cooling is the basic setpoint plus the Temp Comfort Standby Nighttime Anti-freeze/Heat
"neutral zone between heating and mode mode protection mode
cooling". When an air-conditioning unit is Setpoint, heat protection

used, the neutral zone between heating


and cooling should be set higher than 1 K.
The comfort setpoint should be parame- Setpoints,
cooling Increase,
terized in such a way that the end night
Increase, cooling
consumer feels comfortable when carrying standby
out normal activities in the room. cooling
Neutral zone between
heating and cooling
Decrease,
standby
If one switches into standby, the setpoint Basis setpoint heating Decrease,
is lowered (by, e.g., 2 K) when heating and night
heating
raised when cooling. The room can then be Setpoints,
heating
heated up, or cooled down to the comfort
temperatures relatively quickly.

Setpoint, freeze protection


In nighttime mode, the setpoint is yet
again lowered when heating (by, e.g., 4 K)
and raised when cooling. In nighttime
mode, it is possible to switchover to
comfort mode for the set time if the room
temperature becomes unpleasant for the The manual setpoint specified
end consumer. This process is called "com- (in the standby and comfort modes of
fort extension (party time)" and the control- operation) is added to the setpoint tem-
ler switches back to the nighttime mode perature determined on the basis of the
after expiry of the set time. mode of operation. The result of this
is then the setpoint temperature.
For anti-freeze and heat-protection mode,
the setpoints are always stated absolutely
(e.g., 7°C). The anti-freeze mode has the
highest priority (see chapter "Switchover of
the modes of operation").

23
Setpoints

Example

Basic setpoint for heating : 21 °C Comfort value, heating = 21 °C In this example, the
manual setpoint specified


Decrease, standby heating : 2K Standby heating = 19 °C (21°C - 2K)
is "0". Otherwise, in the
Decrease, nighttime heating : 4 K Nighttime heating = 17 °C (21°C - 4K) standby and comfort
Neutral zone : 3K Comfort value, heating = 24 °C (21°C + 3K) modes of operation, this is
added on.
Increase, standby cooling : 2K Standby cooling = 26 °C (21°C + 3K+ 2K)
Increase, nighttime cooling : 4K Nighttime mode, cooling = 28 °C (21°C + 3K+ 4K)

6134-102 Folder "Setpoints"

In commercial/public buildings, it is
recommendable to limit, or even block,
local adjustment of the setpoint.

In the folder "Setpoints", the setpoint ran-


ge of the adjustment button on the room
thermostat can be limited by means of
this parameter. 3 corresponds to
± 3K, 0 means a complete blockage of
local adjustment.

6326-101 Folder "Manual Setpointing"

In the folder "Manual Setpointing", the


increases/decreases of the room thermost-
at, which are unfavourable in terms of
energy, can be limited.

When heating, an increase is unfavourable


in terms of energy. An increase of 1 K
results in approx. 6% more energy costs
(heating costs).

The reverse is the case when cooling.


Here, a decrease results in higher energy
costs (cooling costs).

Example

Range for manual


+5 K
setpointing = ± 5K
26 °C
Maximum decrease in the setpoint -1 K
when cooling = 1 K

Maximum increase in the setpoint +3 K


when heating = 3 K 20 °C
-5 K

24
Heating Actuator

Here, the type of valve connected is


selected, e.g., de-energized when closed,
in the case of the thermoelectric
positioner 6164/10-

If the output of the heating actuator


does not change for more than a week,
the valve can be opened for a certain pe-
riod. This function prevents corrosion of
the angle-type valve and, thus, saves
repair costs.
With a status object, whether
heating or cooling is required can be
displayed.

Via 3 OR logic objects, the heating


actuator can be put into a specific
controlled position as soon at least one
of the objects has the value "1".

When the heating actuator has not


received a control value within a certain
period of time (monitoring time), it can
be put into a specific position (valve in
the case of a fault). In addition, it is
possible to transmit a fault message,
e.g., for visualisation or display, via a
separate object.
A longer monitoring time than the "cyclic
time for automatic sending of control
output" must be selected on the room
thermostat.

The heating actuator has 2 input


terminals for floating contacts. Here,
e.g., a window contact can be
connected in order to switch the room
thermostat into anti-freeze mode and,
thus, to save energy, when the window
is open.
The second input terminal can be used,
in addition, to connect a conventional
pushbutton, or switch, in order, e.g., to
switch/dim the lighting.

25
Individual Modes of Operation for the Individual Rooms

With the controller or the TP In addition, all statuses of


controller, individual tempera- the rooms (room tempe-
ture control in the individual rature, light ON/OFF ....)
rooms is possible. can be displayed.
100 time programs are at dis-
posal for this.

Bathroom WC

Vestibule

Bedroom Living room

Kitchen

Children´s room

Note
In the case of an underfloor taken into consideration in
heating system two the time profiles. That is, if
temperature levels usually the living room should be
suffice (comfort and stand- warm about 7.00 a.m., the
by). As the underfloor mode of operation must be
heating system reacts very changed correspondingly
slowly, this should be earlier (e.g., at 6 a.m.).

26
In the following, some profi-
les of modes of operation
are shown by way of exam-
ple. The profiles can be indi-
vidually adapted to the end
consumer’s requirements.

Living room Comfort

Standby

Nighttime

700 800 1200 1630 2100

Kitchen, bathroom, Comfort


WC
Standby

Nighttime

630 730 1200 2100

Bedroom, vestibule Comfort

Standby

Nighttime

630 1200 2100

Children’s room Comfort

Standby

Nighttime

700 1200 1900 2100

27
EIB in Large Commercial/Public Buildings
Connection of the EIB to a high-level system

In large commercial/public and, if appropriate, con- access control systems, elements between the
buildings, a so-called nects different bus systems can, for example, also be different bus systems).
Management, or Com- with each other. used. These systems are
mand Level is sometimes Apart from the EIB, DDC then connected to the
used. This Command Level (Direct Digital Control) Management, or
controls and visualises all systems, special security Command Level, via
processes in the building systems, lift control and gateways (connecting

The Management System For the boiler system (e.g., As a rule, the gateways are Due to its wide use,
then specifies, e.g., the DDC-controlled), it can, placed at disposal and plan- connection of the EIB is
basic setpoint temperature e.g., be important to ned by the those installing unproblematical.
for the room thermostat. receive information from the Command or Manage-
This information is then the individual room ment Level, so that merely
converted by the gateway regarding the actual, or set- the information flow via the
into an EIB telegram. point temperatures, or the gateway need be agreed
control values. on.

Command level, computers


Management/
Command Level

Distributor

Gateway Gateway Gateway Gateway DDC

Alarm Access SPS


EIB system control

TLN 1 TLN 1
e.g., Lift
TLN 2 TLN 2

TLN 3 TLN 3

TLN 4 TLN 4

TLN X TLN X

TLN = Participant in a bus line

28
Previous DDC Connection
Example for a room
EIB Gateway Command Level

• Actual temperature and setpoint Control value


Posi-
temperature are scanned cyclically tioner
• From this, the DDC calculates the
control value
Actual temp.
➡ High bus load Control- Algor.
Setpoint temp. algor. 1 boiler
➡ High arithmetic capacity of the DDC boiler
RTR control
Operating mode
Operating
mode
of the
other
rooms

DDC Connection Now


Example for a room

EIB Gateway DDC/Command-


level
• The control value from each room is needed to
Posi-
calculate the boiler control tioner
• The mode of operation of the room
thermostat is specified centrally
Control value
for the whole house (group address)

Control value Algor. boiler


➡ Low bus load (control value is boiler
RT control
in any case, transmitted to the bus) Operating mode
➡ Low arithmetic capacity of the DDC Operating
mode rest of the
other
rooms

Summer Compensation

In order to save energy The following graph 30


Setpoint temperature, cooling, in °C

costs in the summer months, shows, by way of example,


29
the room temperature can an increase in the setpoint
be increased by the Mana- temperature (cooling) as a 28
gement or Command Level function of the outdoor
as a function of the out- temperature. This 27
door temperature (from correction is effected via 26
approx. 30°C upwards). the object of the basic set-
Furthermore, people will point temperature. The 25
not be subject to wide Command Level transmits
24
temperature fluctuations the correct value to all
when they enter or leave room thermostats via the 23
the building. gateway, by means of a 30 34 38 40 > 40
24 26 28 32 36
group address.
Outdoor temperature

29
Requirement-oriented Control of the Inlet Temperature

Some boiler controls for The following graph shows 65


heating systems in the such an adjustment by way
60
residential sphere are alrea- of example.

Inlet temperature in °C
dy equippped with an inlet Even this adjustment
55
temperature control. In saves energy. However, it
these cases, the inlet tem- has the disadvantage that it
50
perature is adjusted to the does not take into account
outdoor temperature. This the actual heat require- 45
prevents unnecessary heat ment, for, during the night,
loss of the boiler and the the temperature in the 40
piping system in the case rooms is lowered a great
of relatively high outdoor deal, so that a high inlet 35
temperatures (> 8°C). With temperature is no longer 0 5 20
<-15 -10 -5 10 15
these outdoor tempera- necessary.
tures, the boiler of the hea- Outdoor temperature in °C
ting system need not be
operated with high inlet
temperatures.

For quite a long time now, In principal, these controls Circulating pump 1 bit
modern boiler controls are configured as follows.
(DDC’s) for large commer- The optimum inlet tem-
cial/public buildings have perature for the heating Control value Switch
systems is calculated on 1 byte (1 bit) Boiler Boiler actuator
taken this fact into conside- Room 1
ration. the basis of the control inlet-
values of the different Control value temperature P
In the last few years, rooms (up to approx. 30) 1 byte (1 bit) control
Room 2 Inlet
similar boiler controls for and continuously adjusted
the residential sphere, with to the current heat require- Control value
connections to the EIB ments. 1 byte (1 bit)
Room 3
have been being offered by
the leading boiler manufac- In addition, the circulating
turers (e.g., Viessmann, pump is only switched on Return
Buderus and Junkers). when there is a heat requi-
rement. Control value
1 byte (1 bit)
Room x
In conjunction with
individual room temperatu-
re control, this system
offers a maximum saving
in energy as far as heating
systems in the residential
sphere are concerned.

30
Examples

Individual room control consumption. The


systems meet the demand following examples are
for optimum comfort with given to describe the com-
a minimum of energy fort levels possible.

We are prepared to do a lot are installed. These ensure using an additional timer. Residential building
for our well-being. At the that, when a window is Once programmed, each
same time, Residential opened, the heating room is automatically
building we, naturally, do system automatically swit- heated to our desired tem-
not want to "send our ches over to anti-freeze perature. Even the settings
money up in smoke". mode. No matter how long during a vacation and other
A heating system with indi- the ventilation procedure periods of absence can be
vidual room temperature (window) lasts, the heating taken into account.
control is a step in the right system only heats with the
direction. It is even better intensity necessary to
if, apart from the individual prevent the pipes from free-
room temperature control zing (e.g., 7°C). Comfort is
system, window contacts increased even more by

In commercial/public minimize energy consump- The supplementary use of Offices and doctors‘ surgeries,
buildings such as offices tion. Since the people who a presence detector in sports centres, and public buildings
and administrative build- spend time in these rooms commercial/public build-
ings, administrative build- are not usually responsible ings would be a further
ings, doctors‘ surgeries, for the costs, attention is step towards more comfort.
department stores and seldom paid to the effect Apart from the advantages
sports centres, a heating of an open window. described, this system
department stores, system The additional use of a would also take into
with individual room timer ensures that the account all unforeseeable
temperature control results rooms are only heated times where rooms are
in distinctother commer- to the full degree at the set unoccupied. This means
cial/savings and far greater times. In other words, no that, in cases of illness,
comfort. In addition, the unnecessary energy is when sports events are
right room temperature consumed at night, at week- cancelled, or similar situa-
increases the productivity ends, or in accordance tions, the heating system
of the personnel. with the requirement is not heated up to the
profile. maximum room temperatu-
Here too, the use of a re. As a result, further
system with window energy is saved.
contacts is of advantage to

31
Equipment
Levels
In the following, a few
examples are given of the
levels of equipment
(comfort levels) for offices
and living areas.

1. Basic Level

The basic equipment (per room) Room thermostat


comprises a room thermostat and a Comfort
switch actuator, which controls a mode
1 bit Heating
thermoelectric positioner. 1 bit o. Switch Posi-
Nighttime 1 byte actuator 1) tioner
mode
Switchover between the standby and 1 bit Cooling
comfort modes of operation can be 1 bit o.
Anti- 1 byte
manually effected via the local control. freeze
1 bit
The comfort temperature can also be
changed via the local control. Comfort Room
setpoint temp.
2 byte 2 byte

2. Upgraded Level

In addition to the basic equipment, a Room thermostat


window contact is connected to the
Comfort
room thermostat via a binary input mode
1 bit Heating
terminal. As soon as a window in the 1 bit o. Switch Posi-
Nighttime 1 byte actuator 1) tioner
room is opened, the room thermostat
mode
switches to anti-freeze mode. 1 bit Cooling
1 bit o.
Window Binary- Anti- 1 byte
Furthermore, a central timer can contact input 1) freeze
1 bit
switch all room thermostats to a speci-
fic mode of operation. For example, in
Comfort Room
the evening, to nighttime mode, in the setpoint temp.
2 byte 2 byte
morning, or in the afternoon, to
comfort mode, and during the day, to
standby mode.

32
1) The heating actuator 6164 U has an integrated binary input terminal for the connection of window contacts
3. Comfort Level

Room thermostat
Comfort To achieve the comfort level, an air-
mode conditioning system is added, as well
1 bit Heating
1 bit o. Switch Posi- as visualisation of the actual room
Nighttime 1 byte actuator 1) tioner
mode temperature.
1 bit Cooling Switch Posi-
1 bit o. actuator 1) tioner
Window Binary- Anti- 1 byte
contact input 1) freeze
1 bit

Comfort Room
setpoint temp.
2 byte 2 byte

Visualisation
LC-display, controller

4. Exclusive Level

Room thermostat
In addition to the equipment to achieve
Presence Comfort
detector mode the comfort level, in this case, a
1 bit Heating
1 bit o. Switch Posi- presence detector switches the room
actuator 1) tioner
Nighttime 1 byte thermostat to comfort mode when no
mode
1 bit Cooling persons are in the room.
Switch Posi-
1 bit o. actuator 1) tioner
Window Binary- Anti- 1 byte
contact input 1) freeze If underfloor heating is used, the
1 bit
presence detector is not recommenda-
ble, since the underfloor heating reacts
Comfort Room
setpoint temp. very slowly. When a room is entered, it
2 byte 2 byte
would take a long time before this is
heated up to comfort temperature.

In addition, with this level of


Visualisation equipment, the comfort temperature
LC display, controller
or touch display can be changed. This is practical, e.g.,
in summer, so that the difference
between the outdoor temperature and
the room temperature is not too great
(summer compensation).

33
Planning Tables

Heating and Air-conditioning Systems (Advantages/Disadvantages)

Heating Systems Advantages Disadvantages

Radiator - A system which reacts relatively quickly - Ambient air may be dry
- Most widely used
- Less heat loss at low inlet
temperatures

Underfloor Heating - No visible radiator - A system which reacts very slowly


- Low convection - The room may become overheated
- Dries the air only slightly as a result of solar irradiation

Hot-water Fan Heater - A system which reacts relatively quickly - Usually only for industrial workshops
- Dry ambient air

Electric Fan Heater - A system which reacts very quickly - High energy consumption

Electric Convector Heater - Noiseless - High energy consumption

Air-conditioning Systems Advantages Disadvantages

Chilled beams - Uniform cooling - Usually only viable for commercial/public


- Non-visible buildings

Fan cooling - A system which reacts relatively quickly - Usually only viable for commercial/public
- No visible cooling unit buildings

Heat exchanger - A system which reacts relatively quickly - Visible


- Mobile units can be used very flexibly
- Retrofitting possible

34
Heating and Air-conditioning Systems

Heating Systems Positioner Regelungsart Zykluszeit Hysterese


(bei PWM) (bei 2-Punkt)

Radiator Thermoelectric PWM 15 min. –


Inlet temperature 45°C - 70°C
Radiator Thermoelectric 2-point – 0,3K –1K
Inlet temperature <45°C PWM 15 min. –

Underfloor/Wall Heating Thermoelectric PWM 20 –30 min. –

Hot-water Fan Heater Continuous-action Continuous – –

Electric Fan Heater Switch actuator 2-point – 0,5 –1,5K

Electric Convector Heater Switch actuator PWM 10 –15 min. –


2-point – 0,3K –1K

Air-conditioning Systems Positioner Regelungsart Zykluszeit Hysterese

Chilled Beams Thermoelectric PWM 15 –20 min. –

Fan Cooling Continuous-action Continuous – –

Heat Exchanger Switch actuator 2-point – 0,5K –1,5K

Advantages and Disadvantages of Continuous-action and Thermoelectric Positioners

Positioner Advantages Disadvantages

Continuous-action - Connection only via the bus - Only one valve controllable in each case
- High current load of the bus line
- High costs
- No status display
- Not available for Powernet

Thermoelectric - Status display - Additional voltage supply necessary


- Low costs
- Bus is not subject to high load
- More valves per actuator channel
- Noiseless in conjunction with heating
actuator 6164 U

35
Tips and Tricks

Useful tips regarding


parameterizing and start-up
are given in abbreviated
form in the following.

Preventing local operation 6134-102 6326-101


of the room thermostat In the case of commercial/ In the folder "General", set
public buildings (schools, the parameter "Manual
department stores, govern- operation of control unit" to
ment institutions, etc.), it is "disabled". This prevents
recommendable to change local operation of the room
"Reaction to pushbutton thermostat.
action" to "Pushbutton wit-
hout function" in the folder
"Configuration of Functionali-
ty", in order to prevent unaut-
horized access.
Enter a "0" under "Scaling of
setpoint adjustment button"
in the folder "Setpoints". This
prevents the adjustment but-
ton on the room thermostat
from functioning”.

Changing the setpoints 6134-102 6326-101


of the room thermostat The setpoints of the 6134- If a change is made to the
102 can be changed locally "room thermostat" mode of
via the adjustment button operation via the auxiliary
of the room thermostat button, the setpoint
within the range ±0...10K temperature selected and
in the comfort and standby the mode of operation of
modes of operation only. the room thermostat appe-
ar in the display. The
setpoint temperature can
be changed via the upper
rocker ("+/-").

"Cleaner Defect" This defect could occur: or standby, depending on


Prior to a vacation, the state of the comfort
switchover is made to anti- object, and the heating
freeze mode (anti-freeze system heats up the
object = 1) either manually house.oder
or via a timer (or, in the
case of Powernet, via the
controller). Remedy
During the vacation, the • During the vacation,
cleaner airs the room (win- cyclically transmit a "1" to
dow open). The reed the anti-freeze object via
contacts act on the anti-fre- a timer.
eze object (once again on
"1"). After the room has
been aired, the window is
closed again (anti-freeze
object on "0"). The con-
troller switches to comfort

36
In order to switch from the by pressing and releasing Comfort/Standby
comfort mode of operation the rocker. switchover
to the nighttime mode, the • Logic module: As the
comfort object must be set objects always have
to "0" and the nighttime opposite values – in
object to "1". The sequence nighttime mode, the
is unimportant. nighttime object is "1" and
This switchover can be the comfort object "0",
effected as follows: and vice versa – a negati
• Timer: scene application on gate can also be used.
• alpha nea ® touch sensor: • Send two telegrams in
Via the application quick succession via the
"flexible allocation", send controller or the TP
a telegram controller.

When the mode of opera- high telegram load can Comfort/Standby/Nightime


tion is changed, the result in large switchover in large
control value and the commercial/public` commercial/public buildings
setpoint temperature (if buildings.
parameterized) are trans- Therefore, only 10 room
mitted by the room thermostats should be
thermostat. switched over at once.
If these group addresses
are required centrally (e.g.,
visualisation, gateway to
command level), a very

Prior to putting the room Start-up


thermostat in operation,
remove the positioner from
the angle-type valvfe. The
angle-type valve is then
open. The room should
now heat up, after a
certain time (1 hour to 3
hours, depending on the
type of heating), to a
temperature which is
distinctly higher than 10°C.
If this is not the case, the
heating installation is
defective.

37
Fault Analysis

If the heating system does


not function as desired
after start-up, the following
procedures can be followed
to locate the fault.

If the room remains cold, 1 Check whether 2 Start recording telegrams


then proceed as follows • the positioner is properly and increase the setpoint
mounted, temperature so that is is
• electrical connection has approx. 4K higher than
been effected correctly the actual room tempera
• the parameterizing is cor ture.
rect
• the room thermostat is in 3 The room thermostat
comfort mode must now transmit "1"
(with 2-point and PWM
control) or a control value
>50% in the case of con
tinuous control.

4 Check whether the


switch actuator has
switched (measure volta
ge) and the thermo-
electric positioner is open.

5 If the positioner is open


and the room is still not
warm, then the heating
installation is defective.

is overheated, the following 1 Check whether 2 If the room temperature


should be checked • the positioner is properly is considerably higher
mounted (this is the (>3K) than the setpoint,
most frequent cause) check whether the
• electrical connection has switch actuator is
been effected correctly switched off (measure
• the parameterizing is cor voltage, record tele-
rect grams).
• the room temperature
(actual temperature) 3 If the positioner is closed
corresponds to the and the radiator is cold,
setpoint temperature. there could be other heat
sources in the room.

38
ABB

You might also like