Professional Documents
Culture Documents
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Wind pressures for a typical open storage building are determined. Figure G10-1
shows the dimensions and framing of the open buildings, and the physical data are
provided in Table G10-1.
10.1 Procedures
Wind loads on MWFRS are obtained using the directional procedure of
Chapter 27, Part 1, of ASCE 7-16, because the example building is an open
building. Although the building height is h < 60 ft and qualifies as a low-rise
building by definition, adaptation of the low-rise pseudopressure coefficients of
Chapter 28, Part 1, of ASCE 7-16 is not appropriate for this example building.
Therefore, the directional procedure of Section 27.3.1 is used.
C&C wind loads are obtained using provisions of Chapter 30, Part 5, of ASCE 7-16
for open buildings.
Building Risk Classification: A storage building of this type has a low risk to
human life; Risk Category I is appropriate for this building. The wind speed map
associated with Risk Category I is in Figure 26.5-1A of ASCE 7-16.
Basic Wind Speed: The basic wind speed in Tulsa, Oklahoma, is 101 mph
(see Figure 26.5-1A of ASCE 7-16 or use the ASCE 7 Hazard Tool).
117
Wind Loads
118 Wind Loads
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Enclosure Classification: The building has all walls open; it qualifies as an open
building. The value of (GCpi) = 0.0 (Table 26.13-1 in ASCE 7-16).
where
qz = Velocity pressure at height z,
Kz = Exposure coefficient at height z and Kh at mean roof height,
Kzt = 1.0 for homogeneous terrain (Section 26.8 of ASCE 7-16),
Kd = 0.85 for buildings (Table 26.6-1 of ASCE 7-16),
Ke = 1.0 for locations less than 1,000 ft in elevation (Section 26.9 of ASCE 7-16),
and
V = 101 mph (Figure 26.5-1C of ASCE 7-16).
ð15Þðtan 15°Þ
Mean roof height = 10 + = 12.0 ft
2
Wind Loads
Open Building with Gable Roof 119
Kz = Kh = 0.57
qh = 0.00256 (0.57) (1.0) (0.85) (1.0) (101)2 = 12.6 psf
p = qh GC N (27.3-2)
where
qh = Velocity pressure evaluated at mean roof height h,
G = Gust effect factor, and
CN = Net pressure coefficient value obtained from Figure 27.3-4 through
Figure 27.3-7 of ASCE 7-16.
Gust Effect Factor: This building has a natural frequency greater than 1 Hz, so
according to Section 26.11 of ASCE 7-16 it can be considered rigid. The gust
effect factor for nonflexible (rigid) buildings in ASCE 7-16 is G = 0.85.
Roof Net Pressure Coefficients: Because the building is open and has a pitched
roof, there are two wind directions to be considered: wind direction parallel to
the slope (normal to ridge), γ = 0° or 180°; and wind normal to the roof slope
(parallel to ridge), γ = 90°. For γ = 0° or 180°, the net pressure coefficients are
obtained from Figure 27.3-5 of ASCE 7-16. For γ = 90°, the net pressure coeffi-
cients are obtained from Figure 27.3-7. The roof net pressure coefficients are
presented in Table G10-2.
Wind Pressure for MWFRS: Calculated wind pressures for MWFRS are summa-
rized in Table G10-3.
p = qh GC N = 12.6 × 0.85 × C N
Figure G10-2 and Figure G10-3 illustrate the design pressures (Case A and
Case B) for wind direction γ = 0° or 180° and γ = 90°, respectively.
Distance from
Wind direction θ° windward edge Case A Case B
Normal to ridge
γ = 0° or 180°; Figure 27.4-5 15 — 1.1 (CNW) 0.1 (CNW)
−0.4 (CNL) −1.1 (CNL)
Parallel to ridge
γ = 90°; Figure 27.4-7 0 0 to 12 ft −0.8 0.8
12 to 24 ft −0.6 0.5
24 to 60 ft −0.3 0.3
Wind Loads
120 Wind Loads
Table G10-3. Design Wind Pressures for MWFRS for Two Cases
(psf)
Distance from
Wind direction, γ windward edge Case A Case B
Normal to ridge
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
γ = 0° or 180°
Windward — 11.8 1.1
Leeward — −4.3 −11.8
Parallel to ridge
γ = 90° 0 to 12 ft −8.6 8.6
12 to 14 ft −6.4 5.4
24 to 60 ft −3.2 3.2
Note: Positive numbers mean toward the surface; negative numbers mean away from the surface.
Wind Loads
Open Building with Gable Roof 121
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Minimum Design Wind Loadings: Section 27.1.5 of ASCE 7-16 requires that the
design wind load for MWFRS of open buildings shall not be less than 16 psf
(net horizontal) multiplied by the area projected on a plane normal to the wind
direction. Depending on the projected area of the roof and supporting structure,
this minimum loading could govern and should be checked. Load Case A
satisfies this minimum requirement.
p = qh GC N (30.7-1)
where
qh = Velocity pressure evaluated at mean roof height h,
G = Gust effect factor value determined from Section 26.11 of ASCE 7-16, and
CN = Net pressure coefficient value obtained from Figures 30.7-1 through 30.7-3
of ASCE 7-16.
Roof Design Pressures: Roof net design coefficients for components are pre-
sented in Table G10-4, using Figure 30.7-2 of ASCE 7-16.
Wind Loads
122 Wind Loads
Wind Pressure for Trusses and Roof Panels: Calculated wind pressures for
trusses and roof panels are summarized in Table G10-5.
p = qh GC N = 12.6 × 0.85 × C N
Zones for the pitched roof of this open building are shown in Figure G10-4.
The panels and trusses are designed for the pressures indicated.
For trusses, two loading combinations need to be considered. The two loading
cases are shown in Figure G10-5. Loading Case 1 is for Wind Directions 1 and 2,
whereas Loading Case 2 is for Wind Direction 2. The loadings shown for trusses
are used for the design of the truss and individual members. For anchorage of
the truss to frame support members, MWFRS loading can be used.
Note: Positive numbers mean toward the surface; negative numbers mean away from the surface.
Section 30.2.2 of ASCE 7-16 requires using a minimum pressure of 16 psf.
Wind Loads
Open Building with Gable Roof 123
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Comment: The pressures determined in this example are limit state design
pressures for strength design. Section 2.3 of ASCE 7-16 indicates the load factor
for the wind load to be 1.0 for loads determined in this example. If allowable
stress design is to be used, the load factor for the wind load is 0.6 as shown in
Section 2.4 of ASCE 7-16.
Wind Loads