Professional Documents
Culture Documents
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
U-Shaped Apartment
Building
For components and cladding, provisions for a low-rise building (h < 60 ft) of
Chapter 30, Part 1, are appropriate to use.
103
Wind Loads
104 Wind Loads
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
(Figure 26.5-1B of ASCE 7-16). Figure G9-2 is a screen capture of the ASCE 7
Hazard Tool result for wind speed in Birmingham, Alabama.
Wind Loads
U-Shaped Apartment Building 105
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Velocity Pressures: The velocity pressures for MWFRS and C&C are computed
using the following equation:
where
Kz = Value obtained from Table 26.10-1 of ASCE 7-16 for both MWFRS and
ASCE 7-16 C&C,
Kzt = 1.0 for homogeneous topography,
Kd = 0.85 for buildings (Table 26.6-1 of ASCE 7-16),
Ke = 1.0 for locations less than 1,000 ft in elevation (Section 26.9 of ASCE 7-16),
V = 109 mph, and
qz = 0.00256Kz(1.0)(0.85)(1.0)(109)2 = 25.8Kz psf.
Values for Kz and the resulting velocity pressures are given in Table G9-2. The
mean roof height is the average of the eave and the peak
h = 30 + ð14.6= 2Þ = 37.3 ft
At the mean roof height, h = 37.3 ft; the velocity pressure is qh = 19.4 psf.
Gust Effect Factor: Under the definition of Section 26.2 of ASCE 7-16,
this building can be identified as a low-rise building. In accordance with
Section 26.11 of ASCE 7-16, a low-rise building can be considered as rigid;
hence, the gust effect factor can be taken as 0.85.
Wind Loads
106 Wind Loads
0 to 15 0.57 14.7
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
20 0.62 16.0
30 0.70 18.1
Mean roof h = 37.3 0.75 19.4
External Pressure Coefficients (Cp) for MWFRS: The values for the
external pressure coefficients for the various surfaces (Table G9-3 through
Table G9-6) are obtained from Figure 27.3-1 of ASCE 7-16 for each of the
surfaces in Figure G9-3. The determination of certain pressure coefficients is
based on aspect ratios. Although this U-shaped building will be broken into
pieces for the application of pressures, the overall dimensions have greater
influence on the MWFRS pressure coefficients than the dimensions of the
individual pieces. Therefore, the overall dimensions L and B are used.
When the wind is normal to Wall W2, the wind blows over the A wing, crosses the
courtyard in the middle of the U, and strikes the C wing. Although some
reduction in the pressures on the C wing may occur because of the shielding
offered by A, it is impossible to predict without a wind tunnel study. Therefore,
the pressures on the C wing are taken as the same as on the A wing. There would
also be reductions in pressures on the C wing if the A wing was taller, but again
L/B
Surface type Surface designation Surface Case or h/L Cp
* The values of smaller uplift pressures (Cp = −0.18) on the roof can become critical when wind
load is combined with roof live load or snow load; load combinations are given in Sections 2.3
and 2.4 of ASCE 7-16. For brevity, loading for this value is not shown here.
Wind Loads
U-Shaped Apartment Building 107
L/B
Surface type Surface designation Surface Case or h/L Cp
L/B
Surface type Surface designation Surface Case or h/L Cp
the amount of the reduction is not possible to predict without a wind tunnel
study. If the wind impacts the A wing at an angle such that the wind would
blow directly into the courtyard, then the C wing could still be affected by the
full force of the wind; therefore, for this example, the judgment has been made
that when the wind is normal to Wall W2, Wall W6 is also a windward wall
(and likewise if the wind is normal to Wall W4, Wall W8 is also treated as a
windward wall).
Wind Loads
108 Wind Loads
L/B
Surface type Surface designation Surface Case or h/L Cp
The windward wall Cp is always 0.8, the Cp values of side walls are −0.7, and the
leeward wall Cp varies with the aspect ratio L/B.
The roof Cp for wind normal to a ridge varies with roof angle and aspect ratio,
h/L. The ratio is h/L ≤ 0.25 for all wind directions. The roof angle θ is always
22.6°, so interpolate between 20° and 25°. The Cp for wind parallel to a ridge
varies with h/L and with the distance from the leading edge of the roof.
Wind Loads
U-Shaped Apartment Building 109
where
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Design pressures
External (psf)
Surface q pressure
Surface type designation z or x (ft) (psf) Cp (psf) (+GCpi ) (−GCpi )
Wind Loads
110 Wind Loads
Design pressures
External (psf)
Surface z or x q pressure
Surface type designation (ft) (psf) Cp (psf) (+GCpi ) (−GCpi )
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Design pressures
External (psf)
Surface Surface q pressure
type designation z (ft) (psf) Cp (psf) (+GCpi ) (−GCpi )
load cases as defined in Figure 27.3-8. Case 1 includes the loadings determined in
this example and shown in Table G9-7 through Table G9-10. A combination of
windward (PW) and leeward (PL) loads are applied for Load Cases 2, 3, and 4 as
shown in Figure G9-4.
Wind Loads
U-Shaped Apartment Building 111
Design pressures
External (psf)
Surface Surface q pressure
type designation z (ft) (psf) Cp (psf) (+GCpi ) (−GCpi )
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Figure G9-4. Design wind load cases for wind normal to Walls W2
and W3.
Wind Loads
112 Wind Loads
For Load Case 2, there are two loading conditions shown; both of them need to
be checked independently. The eccentricities are calculated as follows:
where
qh = 19.4 psf,
(GCp) = External pressure coefficient (Figure 30.3-1 of ASCE 7-16), and
(GCpi) = ±0.18, the internal pressure coefficient for enclosed buildings.
Window unit:
A = 3(4) = 12 ft2 (controls)
Wall stud:
Larger of A = 10(1.33) = 13.3 ft2
or A = 10(10/3) = 33.3 ft2 (controls)
Wind Loads
U-Shaped Apartment Building 113
= 19.4[(−1.09) − (±0.18)]
= −24.6 psf (positive internal pressure controls)
= 19.4[(+0.99) − (±0.18)]
= 22.7 psf (negative internal pressure controls)
The design pressures are the algebraic sum of external and internal pressures.
Controlling negative pressure is obtained with positive internal pressure, and
controlling positive pressure is obtained with negative internal pressure.
The Edge Zone 5 for the walls are arranged at exterior corners (Figure G9-5).
Roof Design Pressures: The C&C roof pressure coefficients for θ = 22.6° are
given in Figure 30.3-2G of ASCE 7-16 and presented in Table G9-13 and
Table G9-14. The pressure coefficients are a function of the effective wind
Wind Loads
114 Wind Loads
Negative
Positive
Zones 1, 2e, 2r, 3 Zone 1 Zones 2e, 2r, 3
A (ft2) (GCp) (GCp) (−GCp)
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
area. The definition of effective wind area for a component or cladding panel is
the span length multiplied by an effective width that need not be less than one-
third the span length (Section 26.2 of ASCE 7-16). The effective wind areas, A, for
the roof trusses are as follows:
The design pressures are the algebraic sum of external and internal pressures.
Controlling negative pressure is obtained with positive internal pressure, and
controlling positive pressure is obtained with negative internal pressure.
Wind Loads
U-Shaped Apartment Building 115
The edge and corner zones for the hip roof are arranged as shown in
Figure G9-6.
Comment: The pressures determined in this example are limit state design
pressures for strength design. Section 2.3 of ASCE 7-16 indicates that the load
factor for the wind loads is 1.0 for loads determined in this example. If allowable
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
stress design is to be used, the load factor for the wind load is 0.6 as shown in
Section 2.4 of ASCE 7-16.
Wind Loads