Professional Documents
Culture Documents
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
8.1 Procedures
For MWFRS, the analytical directional procedure for a building of any height
given in Chapter 27, Part 1, is used to determine design wind pressure. For C&C,
analytical envelope procedure for the low-rise (h < 60 ft) building given in
Chapter 30, Part 1, is used to determine design wind pressure.
91
Wind Loads
92 Wind Loads
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
ð16Þðtan 15°Þ
Mean roof height = 10 + = 12.1 ft
2
Because Kz is constant in the 0 to 15 ft region, Kz = Kh = 0.57 for MWFRS and
C&C (from Table 26.10-1).
Velocity Pressures:
qz = 0.00256 K z K zt K d K e V 2 psf (26.10-1)
For MWFRS and C&C, qz = qh = 0.00256 (0.57) (1.0)(0.85) (1.0) (105)2 = 13.7 psf.
Wind Loads
L-Shaped House with Gable/Hip Roof 93
Gust Effect Factor: This building meets the requirements of a low-rise building
(Section 26.2 of ASCE 7-16); hence, it is permitted to be considered a rigid
building (Section 26.11-1) and
Wall Pressures:
Surface 1: p = 13.7 (0.85) (0.8) − 13.7 (±0.18) = +9.3 ± 2.5 psf (windward)
Surface 2: p = 13.7 (0.85) (−0.7) − 13.7 (±0.18) = −8.2 ± 2.5 psf (side)
Surface 3: p = 13.7 (0.85) (−0.3) − 13.7 (±0.18) = −3.5 ± 2.5 psf (leeward) (for
L/B = 80/40 = 2; Cp = −0.3)
Surface 4: p = −8.2 ± 2.5 psf (side)
Surface 5: p = +9.3 ± 2.5 psf (windward)
Surface 6: p = −8.2 ± 2.5 psf (side)
Roof pressures coefficient: Roof pressure coefficient, Cp, from Figure 27.3-1 of
ASCE 7-16 is shown in Table G8-2.
Wind Loads
94 Wind Loads
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Overhang pressures: From Section 27.3.3 of ASCE 7-16, at wall surfaces 1 and 5
This pressure is to be combined with the top surface pressure. Internal pressure
is of the same sign on all applicable surfaces.
Wind Loads
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Table G8-2. Roof Pressure Coefficient for Wind Direction A (h/L = 0.15)
L-Shaped House with Gable/Hip Roof
Surface
7 8 9 10 11 12
Wind Loads
Cp 0.0* −0.9 −0.9 −0.5 −0.3 Same as Surface 8 −0.5 −0.5 Same as Surface 8
−0.5 −0.18* −0.18* −0.18* −0.18* −0.5* 0.0*
* The values of smaller uplift pressures on the roof can become critical when wind load is combined with roof live load or snow load; load combinations are given in
Sections 2.3 and 2.4 of ASCE 7-16. For brevity, loading for this value is not shown here.
95
96 Wind Loads
Surface
7 8 9 10 11 12
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Wind Direction B:
Wall pressures:
Surface 1: p = −8.2 ± 2.5 psf (side)
Surface 2: p = +9.3 ± 2.5 psf (windward)
Surface 3: p = −8.2 ± 2.5 psf (side)
Surface 4: p = 13.7 (0.85) (−0.5) − 13.7 (±0.18) = −5.8 ± 2.5 psf (leeward) (for
L/B = 40/80 = 0.5; Cp = −0.5)
Surface 5: Although technically this surface is side a wall, it is likely to see
the same pressure as Surface 6.
Surface 6: Same pressure as Surface 4
Roof pressure coefficient, Cp, from Figure 27.3-1 of ASCE 7-16 is shown in
Table G8-3.
This pressure is to be combined with the top surface pressure. Internal pressure
is of the same sign on all applicable surfaces.
Wind Loads
L-Shaped House with Gable/Hip Roof 97
Wind Direction C:
Wall pressures:
Surfaces 1 and 5: p = −5.8 ± 2.5 psf (leeward)
Surfaces 2, 4, and 6: p = −8.2 ± 2.5 psf (side)
Surface 3: p = +9.3 ± 2.5 psf (windward)
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Roof pressures:
Surfaces 7 and 11: p = −5.8 ± 2.5 psf (leeward)
Surfaces 8 and 9: Pressures vary along the roof; same pressures as Surface
8 for Wind Direction A
Surface 10: p = −5.8 ± 2.5 psf (windward)
Surface 12: Same pressures as Surface 9 without internal pressures
This pressure is to be combined with the top surface pressure. Internal pressure
is of the same sign on all applicable surfaces.
Wind Direction D:
Wall pressures:
Surfaces 1 and 3: p = −8.2 ± 2.5 psf (side)
Surface 2: p = −5.8 ± 2.5 psf (leeward)
Surfaces 4, 5, and 6: p = +9.3 ± 2.5 psf (windward)
Roof pressures:
Surfaces 7, 10, and 11: pressures vary along the roof; same pressures as
Surface 8 for Wind Direction A
Surface 8: p = −5.8 ± 2.5 psf (leeward)
Surface 9: p = −5.8 ± 2.5 psf (windward)
Surface 12: This surface will see pressures on top and bottom surfaces; they
will add algebraically.
For θ = 0°, h/L < 0.5, Cp = −0.9
p = 13.7 (0.85) (−0.9) − 13.7 (0.85) (+0.8) = −19.8 psf uplift
Wind Loads
98 Wind Loads
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
comes under the exception specified in Section 27.3.5 of ASCE 7-16. Only Load
Cases 1 and 3 shown in Figure 27.3-8 of ASCE 7-16 need to be considered.
1. Because of asymmetry, all four wind directions are considered when combining
wind loads according to Figure 27.3-8 of ASCE 7-16. For example, when combining
wind loads in Case 3, there are four kinds of combinations of wind loads that need to
be considered, which are shown as in Figure G8-3.
2. Because of the low roof slope, the wind load acting on the roof is negligible here.
Wall Component: Wall studs are 10 ft long and spaced 16 in. apart. The effective
area is
The distance a is
Wind Loads
L-Shaped House with Gable/Hip Roof 99
Design pressure:
Roof trusses are 32 ft long and spaced 2 ft apart. The effective area is
larger of 32 × 2 = 64 ft2
or 32 × 32/3 = 341 ft2 (controls)
Roof framing for the front porch is 8 ft long and spaced 2 ft on center. The
effective area is
larger of 8 × 2 = 16 ft2
or 8 × 8/3 = 21.3 ft2 (controls)
From Figure 30.3-2B of ASCE 7-16, equations from the Chapter 30 Commentary
for gable roofs and θ = 15° yield
(GCp) = +0.3 for Zones 1, 2e, 2n, 2r, 3e, and 3r (Note: Zone 3 covers a very
small area of the truss)
(GCp) = −0.5 for Zones 1 and 2e
(GCp) = −1.0 for Zones 2n, 2r, and 3e
(GCp) = −1.8 for Zone 3r
(GCp) = −2.46 for Zone 2e (porch overhang)
Design pressures for the gable roof are (See Figure G8-4)
From Figure 30.3-2E of ASCE 7-16 for hip roofs, the GCp coefficients are a
function of h/B, which is 12.1/32 = 0.38 < 0.5.
Wind Loads
100 Wind Loads
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
The overhang pressure to be used for reactions and anchorage for the hip roof is
MWFRS pressures should be used for the truss connection loads across the
building span; C&C loads are used for the additional pressure created by the
presence of the overhang.
Roof Panels:
Effective area = 4 × 8 = 32 ft2
From Figure 30.3-2B of ASCE 7-16, for θ = 15° (Note: Zones 2 and 3 are regarded
as overhangs and thus there is no internal pressure component.)
Design pressures:
Wind Loads
L-Shaped House with Gable/Hip Roof 101
Fasteners:
Effective area = 10 ft2:
GCp = + 0.7 for all zones on hip roof, which will control design
GCp = −2.5 for Zones 1 and 2e on gable (with overhang)
GCp = −3.5 for Zones 2n and 2r (with overhang)
Downloaded from ascelibrary.org by UNIVERSITY OF NEW SOUTH WALES on 04/18/20. Copyright ASCE. For personal use only; all rights reserved.
Design pressures:
Comment: The pressures determined in this example are limit state design
pressures for strength design. Section 2.3 of ASCE 7-16 indicates the load factor
for wind load to be 1.0 for loads determined in this example. If allowable stress
design is to be used, the load factor for wind load is 0.6 as shown in Section 2.4 of
ASCE 7-16.
Wind Loads