Design Information :
Project Name :
Client :
Designer :
Company :
Units : Imperial
Notes :
Project Data
The structure is located in Minneapolis, MN, USA categorized as Exposure B (assumed to be homogeneous for the
selected wind direction). The wind load calculation for the structure - Solid freestanding walls and attached signs - is based
on the Directional Procedure (Chapter 29) of ASCE 7. Morever, the structure is classified as Risk Category I. The location is
elevated at 836 ft above mean sea level.
Additional details of the structure are shown in Table below and illustrated in Figure 2:
Parameter Value
Wall/Sign Horizontal
26.2 ft
Dimension,
Wall/Sign Vertical
10 ft
Dimension,
Topographic Effects,
Figure 26.8-1 The topography factor, , have been calculated based on the wind coming from N. was calculated using the
following formulas:
Figure 3. Ground elevation with wind coming from N.
Section 26.9.1 The structure is assumed to be rigid, hence, gust effect factor, , is set to 0.85 based on Section 26.9.1.
Section 27.3 The velocity pressures, , shall be computed using the equation:
Table 27.3-1
Ground to Top
10 0.57 12.52
of Wall/Sign
Figure 29.3-1 of ASCE The net force coefficients, , for Case A and Case B are calculated using Figure 29.3-1 of ASCE 7-16. Note that the values
7-16 are interpolated using known values for each and value:
For Case A:
For Case B:
For Case C:
Distance
from
Initial Final
windward
edge, ft
Equation 29.3-1 of The design wind force, , can be calculated using Equation 29.3-1 of ASCE 7-16.
ASCE 7-16
0 to s 1.974 2100.25
2s to 3s 0.570 376.34
Figure 3. Case A.
Figures 6. Case C.