Residual
• Phase • Ground • Phase
• Ground, SEF • Neg. Seq. • Ground
• Neg. Seq. • Neg. Seq. VWVE 27 3
VWVE 38X 3
67N 50N 51N
WE 3
25
Directional
Neutral
Neutral
Overcurrent
Neutral Time-
Overcurrent WVE 27 3
Overcurrent Synchronism
79 Check WVE 38X 3
27 59
G&W
Autoreclosing
Viper®-G 3
1 Undervoltage Overvoltage
Viper®-S 3
85 Hawker Siddeley
BRM LOC SER RIO MET
Line GVR* 3
Breaker Wear Fault Locator Sequential SEL MIRRORED BITS® High-Accuracy
Monitor Events Recorder Metering Thomas & Betts
EIA-232
EIA-485* 4* Joslyn TriModTM 300R 3
HMI LGC DFR LDP
IRIG-B
1 Other reclosers can be added on request.
Operator Interface Event Reports Load Data
SELOGIC®
Profiling *When equipped with interface module.
*Optional Functions
Recloser
General Specifications
AC Current Inputs Power Supply
1 A nominal 3 A continuous, linear to 20 A symmetrical; Rated range 85—264 Vac, 100—350 Vdc
100 A for 1 second Frequency range 40.1—65 Hz
Burden 0.13 VA @ 1 A, 1.31 VA @ 3 A Burden < 30 VA
AC Voltage Inputs
300 V maximum (PT) 300 VL-N continuous (connect any voltage
up to 300 Vac), 600 Vac for 10 seconds
Burden 0.03 VA @ 67 V, 0.06 VA @ 120 V,
0.80 VA @ 300 V