DATE OF THE REPORT PREPARED BY


PROJECT NAME
23/10/21 WATER RESERVE TANK JACOB ULATE

WATER RESERVE TANK.

IN INSPECTION TO WATER RESERVE TANK. TOGETHER WITH MR ROD PARKER AND MR RICHARD. WE CAN SEE A
WATER LEAK ON THE LEFT SIDE ENTERING. A CLOROX TEST WAS DONE AND CAME OUT POSITIVE FOR CLOROX.

TODAY AT 9:00 A.M. WE PROCEEDED TO SHUT OFF THE ENTRANCE AND EXIT STOPCOCK OF THE RESERVE TANK
AND PROCEEDED TO CARRY OUT THE MEASUREMENTS TO DETERMINE IF THE WATER LEVELS VARY.

IN A PERIOD OF (3) HOURS, THE LEVEL VERIFICATION MEASURES WERE CARRIED OUT AND A VARIATION IN THE
LEVELS COULD BE CONFIRMED, SO IT IS DETERMINED THAT THERE IS A LEAK IN THE WATER RESERVE TANK.

IN THE VERIFICATION OF THE MEASUREMENTS IN THE LEFT TANK IT WAS POSSIBLE TO VERIFY A DECREASE IN
WATER OF .07CM AND IN THE RIGHT TANK A DECREASE IN WATER OF .60 CM.

THE RESERVE TANK HAS TWO SECTIONS WITH AN APPROXIMATE MEASUREMENT OF 11.10 METERS IN LENGTH
AND 2.30 METERS IN WIDTH.

APPROXIMATE WATER LOSS OF 17.10 CUBIC METERS. 4,490.92 GALLONS

APPROXIMATE CALCULATION PER HOUR 5.70 CUBIC METERS 1,505.78 GALONES PER HOUR