Professional Documents
Culture Documents
1 General information
Consumables : n/a
2 Document overview
6 Installation ......................................................................................................................................................................... 4
22/02/2017
PM 2946 2002 00 Page 1 of 16
4 Safety first
22/02/2017
PM 2946 2002 00 Page 2 of 16
5 Safety Precautions
Please follow strictly all the safety precautions as per mentioned in the instruction book and as per local regulation as
applicable.
Nitrogen generators produce high purity nitrogen with oxygen enriched waste air.
The standard oxygen concentration in the air around us is equal to 20,9 %, increased or decreased oxygen concentrations
pose specific risk as indicated in the below table:
22/02/2017
PM 2946 2002 00 Page 3 of 16
6 Installation
The installation must be done with the following components, in the following order:
2 UD+ filter
3 QDT filter
5 Air receiver
6 Nitrogen generator
9 Needle valve
1 2 3 4 5 6 7
A
E
B
C
A D
1 2 3 4 5 7 8 6 9
22/02/2017
PM 2946 2002 00 Page 4 of 16
7 Installation requirements
Proper ventilation of the generator room is required. If natural ventilation is not sufficient, at least 4 air changes/hour are
required.
Natural ventilation can be sufficient if:
A room oxygen level detection with an audible/visual alarm is advisable. When working in rooms where the oxygen content
can rise to a dangerous level, a continuous measurement system is necessary.
Alarm levels should be set below 19.5% and above 22.5%.
Put the measuring equipment in the working area and near to the worker. Personal oxygen alarms are always advised when
working around oxygen generators.
If exposed to an oxygen enriched atmosphere, make sure to ventilate your clothing for at least 15 minutes in normal
atmosphere. Do not come near open flames or do not smoke.
The generator is delivered with label 1622 5408 03. This green label can be used to stick on the Nitrogen vessel to
differentiate with the compressed air vessel.
22/02/2017
PM 2946 2002 00 Page 5 of 16
8 Nitrogen generator connections
NGP+ # 8 – 12 15 – 20 25 – 35 40 – 50 60 – 70 85 100
UD+ filter 2
QDT filter 3
To be verified with NGP 8-100+ product sizing calculator
PDp filter in 4
Air and Nitrogen buffer vessel 5&7 150 L 280 L 500 L 1000 L 1000 L 1500 L 2000 L
Exhaust connection <3m 1x DN70 1x DN70 1x DN70 1x DN70 2x DN70 2x DN70 2x DN70
Exhaust connection >3m 1x DN100 1x DN100 1x DN100 1x DN100 2x DN100 2x DN100 2x DN100
22/02/2017
PM 2946 2002 00 Page 6 of 16
9 Voltage selection
The generator is designed to work on 115V/60Hz and 230V/50Hz. Ex-factory, the generator is wired to operate at 230V.
If the generator needs to work at 115V, the wiring of the transformer inside the cubicle needs to be changed.
Transformer
22/02/2017
PM 2946 2002 00 Page 7 of 16
10 Flow calculation
Based on inlet air pressure and temperature, the performance of the CMS adsorbant inside the generator will change.
Increased temperatures will result in reduced capacity, increased pressure in improved capacity.
In order to have the generator running in optimal conditions, we need to make sure that the customer doesn’t consume more
nitrogen from the nitrogen receiver than what the generator is capable to deliver. This can be achieved by limiting the flow
after the nitrogen receiver by means of a needle valve.
To regulate this consumption, the maximum capacity of the generator needs to be known, this can be calculated with the
AML data and correction factors.
Note: refer to the business portal for the latest AML data
P
4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10 10.5 11 11.5 12 12.5 13
[BAR]
% 0,56 0,63 0,71 0,77 0,85 0,93 1 1,07 1,13 1,19 1,25 1,3 1,35 1,4 1,45 1,5 1,54 1,58 1,61
PPM 0,52 0,6 0,67 0,75 0,83 0,91 1 1,04 1,09 1,11 1,13 1,15 1,16 1,17 1,18 1,2 1,21 1,23 1,25
T
5 10 15 20 25 30 35 40 45 50 55 60
[°C]
PPM 1,02 1,02 1 1 0,96 0,93 0,88 0,83 0,78 0,72 0,67 0,62
10.2 Example
NGP35+ | Purity 99.5% | Working pressure: 11.5 bar | Inlet air temperature 40°C
In this case the generator is capable of delivering 50.37m³/h so we need to make sure this is the maximum flow that can be
consumed by the customer by limiting the flow with a needle valve.
22/02/2017
PM 2946 2002 00 Page 8 of 16
11 Start-up procedure
# Action Information
BA04 detail:
22/02/2017
PM 2946 2002 00 Page 9 of 16
3 The following ball valves in the
generator must be opened:
BA01
BA02
BA05 (if option outlet BA01 and BA02
PDP is selected)
BA06
BA05 – optional outlet
PDP sensor ball valve
5 In case of a stand-alone
refrigerant dryer: switch on the
dryer 10 minutes in advance in
order to cool down the dryer.
22/02/2017
PM 2946 2002 00 Page 10 of 16
6 Start the compressor.
In case of an integrated
refrigerant dryer, start the
compressor with the outlet ball
valve closed for 10minutes so
the dryer has time to cool down.
Menu/Settings/Generator/
Regulation/Purity
NOTE:
There will be a warning when purity
drops below purity set point and
above minimum purity.
During flushing, the generator keeps
on running but the vessel is flushed
over a nozzle until the purity is again
above minimum purity setting.
22/02/2017
PM 2946 2002 00 Page 11 of 16
9 Enter the minimum required
nitrogen purity in controller:
Menu/Settings/Generator
/Regulation/Minimum Purity
22/02/2017
PM 2946 2002 00 Page 12 of 16
11 Check the inlet dew point on the
controller display. If this value
exceeds 5°C, the air receiver
needs to be flushed until a value
below 5°C is reached.
11 On software generation 2
bis (NGP+ from API205450,
produced since 10/2016),
manual ball valve BA03 is
replaced with solenoid valve
Y14.
22/02/2017
PM 2946 2002 00 Page 13 of 16
12 Start the generator.
PR01 – N2 pressure
regulator
22/02/2017
PM 2946 2002 00 Page 14 of 16
14 Make sure the outlet flow
(measured by FT01) does not
exceed the nominal flow of the
nitrogen generator.
Menu/Settings/General/Time
Format dd/mm/yy and hh:mm:ss
22/02/2017
PM 2946 2002 00 Page 15 of 16
17 Perform a complete leak test of Check both the generator and the piping network for leaks.
the installation. The smallest Fill the nitrogen buffer tank to the nominal working pressure.
leak in the nitrogen installation
Stop the generator and wait for one hour while monitoring the pressure in the
can cause the generator to
adsorbent with the nitrogen outlet valve (downstream N2 buffer vessel) closed.
malfunction.
If a pressure drop of more than 100 mbar shows after one hour, leaks are
present and have to be fixed before taking the generator in operation.
12 Commissioning sheet
To write down all parameters and during during the commissioning, excel sheet 246 2003 00 can be used.
22/02/2017
PM 2946 2002 00 Page 16 of 16