Professional Documents
Culture Documents
Authorized licensed use limited to: SIMON FRASER UNIVERSITY. Downloaded on June 06,2016 at 17:06:22 UTC from IEEE Xplore. Restrictions apply.
IEEE
Std 4 0 4 - 1 9 7 7
Sponsor
© Copyright 1977 b y
Authorized licensed use limited to: SIMON FRASER UNIVERSITY. Downloaded on June 06,2016 at 17:06:22 UTC from IEEE Xplore. Restrictions apply.
Approved December 1 2 , 1 9 7 5
I E E E Standards Board
fDeceased
Authorized licensed use limited to: SIMON FRASER UNIVERSITY. Downloaded on June 06,2016 at 17:06:22 UTC from IEEE Xplore. Restrictions apply.
Foreword
This standard has been written to fill a need for standardization of terminology and test require
ments for A C power cable joints.
Because most types of joint are field assembled by personnel with different levels of skill and
experience, the joint is the component of a cable system with the widest range of quality, and,
therefore, the most difficult to categorize. S o m e of the tests, specified for other materials, are not
only inapplicable for joints, but are often impossible to perform.
The test values, listed in this standard, are compatible with levels for other system components,
such as terminations. They are, in general, minimum values. Higher test values have been recom
mended by some users. Before these higher values are used, however, specific agreement should be
obtained from the designers and manufacturers of all system components.
One of the aims of the authors of this standard has been to eliminate the confusion of terminol
ogy connected with this subject. Beginning with the definition of "splice" as the basic conductor
connection, and "joint" as the complete, insulated and protected component, it is hoped that
standardized terms will become specific and unambiguous. The IEEE Dictionary of Electrical and
Electronics Terms, IEEE Std 1 0 0 - 1 9 7 2 (ANSI C 4 2 . 1 0 0 - 1 9 7 2 ) has never covered terms applicable
to power cable usage. The definitions used in this standard will be included in the revision of the
IEEE Dictionary of Electrical and Electronics Terms.
The work of preparing this standard was carried out by the Accessories Subcommittee on In
sulated Conductors of the IEEE Power Engineering Society. The membership of the Subcommittee
was as follows:
Ν. E. Piccione, Chairman
B" W Λ Μ R
- Ε
· L E U C H
R
-W A l l e n
J. J. L o w e
T. A . Balaska G. Ludasi
F. J. Bender M M a l i a
O. I. Berkhan F. M. M c A v o y
° R B e s t
L. B. M c C l u n g
R. A . Burkhardt A . McKean
L
J. W. B r o w n j MedekD
E. C. B u r n u p R. p. M o t t
D . J. Carrigan j Mulligan
A
J. F. Castles ρ Neuger
Η
· c h u
P. L. Pearson
D . R. Clarke ρ ρ Pugh
F. V. C u n n i n g h a m Ε. S. Raila
F
- D e S i o
D . M. R i g n e y
L. J. D y l e w s k i A. Rios
J. D . Freed N. R . Sacks
G. B. Garibay E. L. S a n k e y
R B G e a r
A . Sansores
A. Godoshian p . g Schullerts
A. Gruenwald E. L. S h e l t o n
G. Hamburger R. Sheridan
H. C. Hervig L. H. Spangler
C. H o o g e r h y d e N. R. Spencer
R. R. H o w a r d VV. T. Starr
R. F. H u b e r D R Stevens
C. H. Hunter F. R . S t o c k u m
A . Hvizd, Jr. WK. Switzer
A. R. J a c k s o n Η. N. T a c h i c k
H. J o h n s o n j Tramontano
R. S. Keith ρ Tuttle D
D . W. Kissinger j . R Tuzinski
S
- Kozak R . . Ward A
J. H. L a w s o n A . C. W e s t r o m
R . H. L e e O W i l l i s
A t the time this document was approved the members of the working group were:
A. Gruenwald, Chairman
T. A . Balaska J. Nicholas
D . Clarke W. Richard
A . L. M c K e a n H. O . T h o m p s o n
R . C. Waldron
Authorized licensed use limited to: SIMON FRASER UNIVERSITY. Downloaded on June 06,2016 at 17:06:22 UTC from IEEE Xplore. Restrictions apply.
Contents
SECTION P A G E
1. Scope 7
2 . Service Conditions 7
2.1 Usual Service Conditions 7
3 . Definitions 7
4. Terminology 8
5 . Basic Components for Cable Joints 8
5.1 Connector &
5.2 Insulation 9
5 . 3 Shielding (Screening) 9
5.4 Filling C o m p o u n d 9
5.5 Housing 9
7. Design Tests 9
8. Field Tests 1 1
TABLES
Table 1 Design Test for Joints on Cables with Laminated Dielectrics 10
Table 2 Design Tests for Joints on Cables with Extruded Dielectrics 10
Table 3 Pressure Tightness Tests 1 0
Authorized licensed use limited to: SIMON FRASER UNIVERSITY. Downloaded on June 06,2016 at 17:06:22 UTC from IEEE Xplore. Restrictions apply.
IEEE Standard for Power Cable Joints
Authorized licensed use limited to: SIMON FRASER UNIVERSITY. Downloaded on June 06,2016 at 17:06:22 UTC from IEEE Xplore. Restrictions apply.
IEEE
Std 4 0 4 - 1 9 7 7 IEEE S T A N D A R D F O R
3 . 4 design tests. Tests made on typical joint 5.1 Connector. A metallic device of suitable
designs to obtain data to substantiate the de electric conductance and mechanical strength,
sign. These tests are of such nature that after used to splice the ends of two or more cable
they have once been made, they need not be conductors, or as a terminal connector on a
repeated unless significant changes are made in single conductor. Connectors usually fall into
the material or design which may change the one of the following types:
performance of the joint.
solder
3 . 5 production (routine) tests. Tests made on welded
joint components or subassemblies during pro mechanical
duction for the purpose of quality control. compression or indent.
3 . 6 field tests. Tests which may be made on Conductors are sometimes spliced without con
the cable and accessories after installation. nectors, by soldering, brazing, or welding.
Authorized licensed use limited to: SIMON FRASER UNIVERSITY. Downloaded on June 06,2016 at 17:06:22 UTC from IEEE Xplore. Restrictions apply.
IEEE
POWER CABLE JOINTS Std 4 0 4 - 1 9 7 7
7. Design Tests
6. Joint Rating and Design Criteria The design tests shall include the following:
(Separate joint samples may be required for
The joint rating and the governing design con different design tests.)
ditions include the following:
7.1 Dielectric Tests. 6 0 hertz, impulse, and di
6 . 1 Rated Volage. The rated voltage of a joint rect current withstand tests in accordance with
is the voltage at which it is designed to operate appropriate values listed in either Table 1 or Ta
under usual service conditions. ble 2 dependent upon cable type.
N O T E : Unless o t h e r w i s e specified, the voltage rating is 7.2 Thermal and Mechanical Tests. The con
assigned with the understanding that the j o i n t will b e
applied o n three-phase circuits w h o s e n o m i n a l phase- nector-conductor assembly shall meet all appli
to-phase voltage rating d o e s n o t e x c e e d that o f the cable tests as covered by:
joint.
(a) T D 1 6 1 1 9 5 8 EEI Specification for
6 . 2 Temperature Limitations. The joint shall Straight Compression Type Connectors
be capable of operating with the conductor and for Insulated Copper Conductors.
connector within the joint at the same maxi
(b) T D 1 6 0 EEI Specifications for Solder
m u m temperature limitations as those of the
Sweated Split Tinned Copper Connec
conductors of the cable being joined.
tors.
6 . 3 Rated Internal Pressure. The rated internal (c) T D J 1 6 2 (EEI) or 1 4 . 1 0 - 1 9 6 2 ( N E M A )
pressure of a joint is the nominal internal op Standards for Overhead Distribution
erating pressure. This will depend on the types Connectors for Aluminum Conductors.
of cable being joined and the service condi N O T E : Class A Heat C y c l e Test and Class 2 Partial
tions. T e n s i o n Test shall b e used.
Authorized licensed use limited to: SIMON FRASER UNIVERSITY. Downloaded on June 06,2016 at 17:06:22 UTC from IEEE Xplore. Restrictions apply.
IEEE
Std 4 0 4 - 1 9 7 7 IEEE S T A N D A R D F O R
Table 1
Design Test for Joints on Cables with Laminated Dielectrics
Test Values in k V
Rated k V L o w Frequency Impulse D i r e c t Current
φ to φ 6hr(l) Crest ( 1 ) 15 m i n ( 2 )
2.5 10 60 15
5.0 15 75 25
8.7 23 95 35
15.0 36 110 55
25 53 150 75
35 77 200 100
46 102 250 125
69 118 350 175
92 139 450 225
115 163 550 275
138 191 650 325
161 221 750 375
196 268 900 450
*230 268 900 450
230 315 1050 525
287 335 1300 650
*345 360 1300 650
345 400 1550 775
500 470 1800 990
Table 2
Design Tests for Joints on Cables with Extruded Dielectrics
5 15 75 25 5
8 23 95 35 5
15 36 110 55 5
25 53 150 75 5
35 77 200 100 5
Table 3
Pressure Tightness Tests
10
Authorized licensed use limited to: SIMON FRASER UNIVERSITY. Downloaded on June 06,2016 at 17:06:22 UTC from IEEE Xplore. Restrictions apply.
IEEE
POWER CABLE JOINTS Std 4 0 4 - 1 9 7 7
7.3 Tightness Test on Cable Joint. The cover be used as the test voltages for a given rated
ing or housing of a joint shall withstand the voltage cable system, but are intended only as
applicable liquid or gas pressure test for one a guide for voltage which the joint should be
hour, as determined from Table 3 . Pressure expected to withstand without affecting its di
tests, where applicable, shall be based on values electric characteristics.
agreed on by manufacturer and user. T h e magnitude of the actual test voltage to be
used for the installed cable system shall be de
8. Field Tests termined by reference to applicable IEEE,
A E I C , or IPCEA cable test specifications. The
Acceptance tests or proof tests or both, as
joint supplier shall be consulted before con
defined here and under the provisions outlined,
ducting any field tests which exceed the values
may be made on completed cable systems as a
listed in Table 1 or 2 .
check on workmanship in cable joining and for
possible mechanical damage during installation.
N O T E S : ( 1 ) Transformers, regulators, and o t h e r equip
Field tests are tests which may be made on the
m e n t w h i c h c a n n o t b e d i s c o n n e c t e d from the cable
completely installed cable system b y the user s y s t e m while c o n d u c t i n g the field test s h o u l d be inves
as an installation acceptance or proof test. The tigated t o be sure the withstand strength o f this equip
m e n t is n o t e x c e e d e d . ( 2 ) All values are withstand test
acceptance tests and field tests are not intend
voltages w i t h o u t negative tolerance. ( 3 ) O n assembled
ed to preclude the testing of the cable system multiple c o n d u c t o r j o i n t s o f n o n s h i e l d e d cables, the
on a periodic basis after having been placed in design test voltage shall be applied b e t w e e n each c o n
d u c t o r and g r o u n d with the terminals o n adjacent c o n
service.
d u c t o r s g r o u n d e d . O n shielded cable, the test voltage
Pressure tightness tests may be made in the shall be applied b e t w e e n the c o n d u c t o r and the
field as indicated in Table 3 or at 7 0 percent g r o u n d e d shielding. ( 4 ) T h e values in these Tables are
for general use. It is r e c o g n i z e d that j o i n t s with a high
of the design test for joints with a rated pres er o r l o w e r voltage rating than the c a b l e m a y be used
sure not included in Table 3 . w h e r e different insulation levels are required o r are
The values listed in Tables 1 and 2 are not to acceptable.
11
Authorized licensed use limited to: SIMON FRASER UNIVERSITY. Downloaded on June 06,2016 at 17:06:22 UTC from IEEE Xplore. Restrictions apply.