N GENERAL NOTES
1. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE
SPECIFIED
TERMINAL 2
2. ALL FAS DRAWINGS SHALL BE READ IN CONJUNCTION
WITH ARCHITECTURAL/STRUCTURAL & OTHER MEP
L
SERVICES DRAWINGS. Bangalore
3. EQUIPMENT DIMENSIONS FROM THE GRID LINES
SHALL BE PART OF SHOP DRAWINGS. International Airport
E40 E41 E42 E43 E44 E45 E46 E47 E48 4. ALL TYPICAL INSTALLATION, SUPPORTING DETAILS
SHALL BE PART OF SHOP DRAWINGS.

5. FIRE ALARM LOOP CABLE SHALL BE 2CX1.5 Sqmm,


FIRE SURVIVAL ARMOURED CABLE.
OWNER

6. ONE NUMBER SHORT CIRCUIT ISOLATION MODULE IS


9000 9000 9000 9000 9000 9000 9000 9000
INSTALLED AFTER EVERY 30th DEVICES.INCASE IN
BETWEEN 30 DETECTORS/DEVICES ANY 3RD PARTY
INTEGRATION MODULES ARE PROVIDED, SHORT
CIRCUIT ISOLATOR IS NOT REQUIRED. AS THE
SEE: 1 / SEE: 1 /
CONTROL & MONITOR MODULE CAN WORK AS SHORT
CIRCUIT ISOLATOR Bangalore International Airport Limited
KIA-B03-L&T-R_ KIA-B03-L&T-R_
FA-L4-SPD- 1464 FA-L4-SPD-1464
7. ALL WALL MOUNTED DEVICES IN STAIRWELLS ARE
Project Office
TO BE MOUNTED AT 2400mm ABOVE LANDING OR
K MATCHLINE MATCHLINE NEAREST TREAD UNLESS SHOWN OTHERWISE. Kempegowda International
Airport Bengaluru
8. THE LOCATION OF PROPOSED FIRE ALARM Devanahalli, Bangalore 560 300 India
CONTROL PANEL IS FROM AND RETURN TO

MATCHLINE
KIA-B03-L&T-R_
FA-L4-SPD- 1455
SEE: 1 /
LEVEL - 1 ELECTRICAL CLOSET 1T73-11
LEAD CONSULTANT
9. EACH LOOP SHALL BE CAPABLE OF ACCOMMODATING
MAXIMUM 255 DETECTORS/ DEVICES.

10. FIRE ALARM SYSTEM CONSIDERED AS PER IS: 2189


AND NFPA -72 STANDARDS.

11. INSIDE THE BUILDING,CABLING SHALL BE DONE BY SOM India LLC


USING 2C X 1.5 Sqmm FIRE SURVIVAL CABLE
ARMOURED CABLE(RED) & ACCESSORIES. 14 Wall Street, New York, NY 10005

12. TOTAL 01 DETECTOR/DEVICES FOR FACP-07 LOOP-01 MEPF ENGINEER BAGGAGE CONSULTANT
AS PER THE DRAWING.
ARUP LTD. BNP Associate s
13 THE MODULE LOCATION PROVIDED ARE TENTETIVE 77 Water Street P.O. Box 32746
THE FINAL LOCATION OF THE MODULES WILL BE AS New York, NY 10005 Abu Dhabi, UAE
J
N25 PER THE SITE CONDITION.
LIGHTING CONSULTANT LANDSCAPE

14. FINAL ROUTING OF THE CABLE SHALL BE CLOSELY BPI Grant Associates
COORDINATE AT SITE WITH THE IT CABLE TRAY.
302 5th Ave, 12th FL 22 Milk Street
15. 50% OF SPARES FOR EACH LOOP. New York, NY 10001 Bath, UK BA1 1UT
IT / SECURITY / PA / FAS SIGNAGE / WAYFINDING

2100
16. MAXIMUM LOOP LENGTH OF EACH LOOP SHOULD BE
2 KM. MBII MSD
3100
44 Mobile Drive 2 Young Place
17. BOB : BOTTOM OF BEAM
Toronto, ON M4A 2P2 East Kilbride, GLA G75 0TD
18. TO ACCESS ABOVE FALSE CEILING DETECTORS
FACP_03-1-AASD-060 REQUIRES TRAP DOOR.
9000

ADDRESSABLE LOOP L4-SLC-FAP3-01


19. FOR BELOW FALSE CEILING DETECTORS CABLE
ROUTING ARE SHOWN TENTATIVE.
BIAL DESIGN
20. FOR RESPONSE INDICATOR CABLE DROPPING BASED CHECKED BY APPROVED BY
ON SERVICE SUPPORT AVAILABLITY.
I
21. FOR HVAC UNITS WHICH HAS A CAPACITY EQUAL
TO OR GREATER THAN 2000 CFM ( AHUS/DOAS/MUA/
CAHUS/FCUS/VENTILATION,DUCT SMOKE DETECTOR
SHALL BE PROVIDED IN THE SUPPLY AFTER FILTERS ARCHITECTS & ENGINEERS:
AHEAD OF ANY BRANCH CONNECTION TO AVOID THE
SPREAD OF SMOKE. Engineering Design and Research Center (EDRC),
L&T Construction - Buildings & Factories.
N26
DESIGN BY DRAWN BY CHECKED BY APPROVED BY

AMKR SP PSK Approver

MAIN CONTRACTOR:

REFERENCE DRAWING :

1. FOR TYPICAL INSTALATION DETAILS REFER


H
9000

DWG NO: KIA-B03-L&T-R_GD-XX-SPD-0002.


2. FOR TYPICAL INTERFACING DETAILS REFER FIRE CONTRACTOR:
DWG NO: KIA-B03-L&T-R_GD-XX-SPD-0003

Siemens Ltd.,
LEGEND: #49,Ground Floor, Jyothi Mahal,
ST.Marks Road, Bangalore -560001,
P:+91(080) 33299154
SYMBOLS NAME Unit Qty

DESIGN BY DRAWN BY CHECKED BY APPROVED BY

Addressable optical Smoke detector


with base for True Ceiling Nos. 01
N27 (Non false ceiling area).
L&T JAGA RV PG

Addressable optical Smoke detector Nos. 00


with base for False Ceiling. KEYPLAN

G
A Addressable optical Smoke detector
T00 T10 T20 T30 T40 T50 T60 T70 T80

Nos. 00
with base for True Ceiling T61 T71
T01 T11 T21 T31 T41 T51 T81
(False ceiling area).

T02 T12 T22 T32 T42 T52 T62 T72 T82


9000

Addressable optical Multi sensor


M detector with base for True Ceiling.
Nos. 00 T03 T13 T23 T33 T43 T53 T63
T73
T83

T04 T14 T24 T34 T44 T54 T64 T74 T84

Addressable optical Multi sensor


T05 T15 T25 T35 T45 T55 T65 T75 T85
M detector with base for false ceiling. Nos. 00

T06 T16 T26 T36 T46 T56 T66 T76 T86

HD Addressable Heat Detector Nos. 00 T07 T17 T27 T37 T47 T57 T67 T77 T87

T08 T18 T28 T38 T48 T58 T68 T78 T88


F
N28 Analogue Addressable Control Nos.
FRM 00
Relay Module Isolater

Analogue Addressable Control


CM Relay Module Nos. 00
SEAL & SIGNATURE

Analogue Addressable Monitor 00


MM Nos.
Module
9000

RI Response Indicator Nos. 00

CHECKED BY SIGN DATE CHECKED BY SIGN DATE


Analogue Addressable Dual ARCHITECTURE FPS
MCP Manual Call Point Nos. 00 CIVIL & STRUCTURAL PIPING
ELECTRICAL PHE
E
ELV SYSTEM AIRPORT SYSTEM
DD Duct Smoke Detector Nos. 00
HVAC VHT

BD
Beam Detector Nos. 00 Revision Schedule

Revision

BR
N29 Beam Reflector Nos. 00 Number Revision Description
Revision Date Issued by Issued to

Power Socket Nos. 00

FACP Fire Alarm Control Panel Nos. 00

D LOOP 3 P-7 2C x 1.5 Sqmm Fire


9000

survival cable,Armoured
cable(Fire loop).

FACP DETAILS:

PANEL NO. PANEL LOCATION LOOPS PART PLANS

LEVEL - 3 (64)
FACP - 03 L3 - SERVICE LOOP 1
CORRIDOR (3T64 - 20)
N30 LEVEL - 4
( 53,54,55,64 & 65 )
FA-L4-SPD- 1455

C
KIA-B03-L&T-R_

MATCHLINE
SEE: 1 /

B
QRCODE

DRAWING TITLE

FIRE ALARM - T2 - LEVEL 4 -


Level 4 - RETAIL MEZZANINE - PART PLAN - 65
1 SCALE: 1 : 100
RETAIL MEZZANINE - PART
PLAN 65_SHEET 1 OF 2

A
DRAWING NUMBER

KIA-B03-L&T-R_L4-SPD-1465
SCALE: 1:100 SHEET SIZE - A0

CONSULTANT JOB NO : O18180

© Copyright Bangalore International Airport Limited