Panel name LP-G-R Circuit breaker (32 OR 40) AT/100 AF MCCB Recessed

4x6mm2+1x6mm2
Fed from SMDP Cable Short circuit (L-G) XXXX
CU/PVC/PVC

Disconnect switch
Notes line no. Description C.B C.s.a Lighting load Normal socket load Hand Drayer Power socket R Y B
HVAC
1 LIGHTING 16 (3x3)mm2 270 270
Contactor 2 LIGHTING 16 (3x3)mm2 143.5 143.5
3 LIGHTING 16 (3x3)mm2 270 270
Contactor 4 LIGHTING 16 (3x3)mm2 102.5 102.5
5 LIGHTING 16 (3x3)mm2 66 66
6 LIGHTING 16 (3x3)mm2 210 210
Contactor 7 LIGHTING 16 (3x3)mm2 150 150
8 LIGHTING 16 (3x3)mm2 270 270
9 LIGHTING 16 (3x3)mm2 184.5 184.5
10 LIGHTING 16 (3x3)mm2 184.5 184.5
11 LIGHTING 16 (3x3)mm2 135 135
12 LIGHTING 16 (3x3)mm2 184.5 184.5
13 LIGHTING 16 (3x3)mm2 287 287
ELCB 14 LIGHTING 16 (3x3)mm2 184.5 184.5
15 LIGHTING 16 (3x3)mm2 247.5 247.5
16 LIGHTING 16 (3x3)mm2 157.5 157.5
Contactor 17 LIGHTING 16 (3x3)mm2 240 240
18 Spare 20 0
19 Spare 20 0
20 Spare 20 0
21 Spare 20 0
22 Space 0
23 Space 0
24 Space 0

Disconnect switch Disconnect switch


Total lighting load Normal socket load Power socket R Y B
HVAC HEATER

Total conncetd load 3287 0 0 0 0 1151.5 1039 1096.5

Balance percentage 9.7698653929657

Demand factor 0.9 0.7 0.9 0.5 0.75


Total Demand load 2958.3 0 0 0 0 3.0
Total demand load ( KWatt )
Note :-

1- ALL FEEDERS ARE ( CU/PVC/PVC)


2-PANEL BOARD ARE RECESSED PANEL BOARD
3-INDOOR PANEL BOARD PROTECTED WITH IP42
4-MAIN CIRCUIT BREAKER MUST BE MCCB
Panel name ELP-G-R Circuit breaker (32 OR 40) AT/100 AF MCCB Recessed

4x6mm2+1x6mm2
Fed from ESMDP Cable Short circuit (L-G) XXXX
CU/PVC/PVC

Disconnect switch Disconnect switch


Notes line no. Description C.B C.s.a Lighting load Normal socket load Power socket R Y B
HVAC HEATER
1 LIGHTING 16 (3x3)mm2 88 88
2 LIGHTING 16 (3x3)mm2 135 135
Contactor 3 LIGHTING 16 (3x3)mm2 127.3 127.3
Contactor 4 LIGHTING 16 (3x3)mm3 118.4 118.4
5 LIGHTING 16 (3x3)mm2 213 213
ELCB 6 LIGHTING 16 (3x3)mm2 148 148
ELCB 7 LIGHTING 16 (3x3)mm2 148 148
8 LIGHTING 16 (3x3)mm2 88.8 88.8
9 LIGHTING 16 (3x3)mm2 135 135
Contactor 10 LIGHTING 16 (3x3)mm2 134.8 134.8
11 LIGHTING 16 (3x3)mm2 112 112
ELCB 12 LIGHTING 16 (3x3)mm2 148 148
13 LIGHTING 16 (3x3)mm2 67.5 67.5
Contactor 14 EXIT SIGN 16 (3x3)mm2 56 56
15 Spare 16 0
16 Spare 16 0
17 Spare 16 0
18 Space 0
19 Space 0
Panel name LP-G-L Circuit breaker (32 OR 40) AT/100 AF MCCB Recessed

4x6mm2+1x6mm2
Fed from MDP Cable Short circuit (L-G) XXXX
CU/PVC/PVC

Disconnect switch
Notes line no. Description C.B C.s.a Lighting load Normal socket load Hand Drayer Power socket R Y B
HVAC
1 LIGHTING 16 (3x3)mm2 270 270
2 LIGHTING 16 (3x3)mm2 270 270
3 LIGHTING 16 (3x3)mm2 66 66
Contactor 4 LIGHTING 16 (3x3)mm2 143.5 143.5
Contactor 5 LIGHTING 16 (3x3)mm2 150 150
6 LIGHTING 16 (3x3)mm2 270 270
7 LIGHTING 16 (3x3)mm2 210 210
8 LIGHTING 16 (3x3)mm2 135 135
Contactor 9 LIGHTING 16 (3x3)mm2 270 270
10 LIGHTING 16 (3x3)mm2 240 240
11 LIGHTING 16 (3x3)mm2 202.5 202.5
ELCB 12 LIGHTING 16 (3x3)mm2 240 240
ELCB 13 LIGHTING 20 (3x3)mm2 135 135
14 LIGHTING 20 (3x3)mm2 240 240
15 LIGHTING 20 (3x3)mm2 132 132
16 Spare 20 0
17 Spare 20 0
18 Spare 20 0

Disconnect switch Disconnect switch


Total lighting load Normal socket load HVAC HEATER Power socket R Y B

Total conncetd load 2974 0 0 0 0 998.5 997.5 978

Balance percentage 2.05307961942914

Demand factor 0.9 0.7 0.9 0.5 0.75


Total Demand load 2676.6 0 0 0 0 2.7
Total demand load ( KWatt )
Note :-

1- ALL FEEDERS ARE ( CU/PVC/PVC)


2-PANEL BOARD ARE RECESSED PANEL BOARD
3-INDOOR PANEL BOARD PROTECTED WITH IP42
4-MAIN CIRCUIT BREAKER MUST BE MCCB
Panel name ELP-G-L Circuit breaker (32 OR 40) AT/100 AF MCCB Recessed

4x6mm2+1x6mm2
Fed from EMDP Cable Short circuit (L-G) XXXX
CU/PVC/PVC

Disconnect switch Disconnect switch


Notes line no. Description C.B C.s.a Lighting load Normal socket load Power socket R Y B
HVAC HEATER
Contactor 1 LIGHTING 16 (3x3)mm2 127.3 127.3
2 LIGHTING 16 (3x3)mm2 135 135
3 LIGHTING 16 (3x3)mm2 88 88
ELCB 4 LIGHTING 16 (3x3)mm2 148 148
5 LIGHTING 16 (3x3)mm2 180 180
ELCB 6 LIGHTING 16 (3x3)mm2 148 148
Contactor 7 LIGHTING 16 (3x3)mm2 64 64
Contactor 8 LIGHTING 16 (3x3)mm2 61.5 61.5
Contactor 9 LIGHTING 16 (3x3)mm2 134.8 134.8
10 LIGHTING 16 (3x3)mm2 135 135
ELCB 11 LIGHTING 16 (3x3)mm2 165 165
ELCB 12 LIGHTING 16 (3x3)mm2 186 186
13 LIGHTING 16 (3x3)mm2 89.5 89.5
14 Spare 20 0
15 Spare 20 0
16 Spare 20 0
17 Space 0
18 Space 0

Disconnect switch Disconnect switch


Total lighting load Normal socket load Power socket R Y B
HVAC HEATER

Total conncetd load 1662.1 0 0 0 0 563.8 541.5 556.8

Balance percentage 3.95530329904221

Demand factor 0.9 0.7 0.9 0.5 0.75


Total Demand load 1495.89 0 0 0 0 1.5
Total demand load ( KWatt )
Note :-

1- ALL FEEDERS ARE ( CU/PVC/PVC)


2-PANEL BOARD ARE RECESSED PANEL BOARD
3-INDOOR PANEL BOARD PROTECTED WITH IP42
4-MAIN CIRCUIT BREAKER MUST BE MCCB
Panel name PP-G-R Circuit breaker 80 AT / 100 AF MCCB Recessed

4x25mm2+1x25mm2
Fed from SMDP Cable Short circuit (L-G) XXXX
CU/PVC/PVC

Disconnect switch Disconnect switch


Notes line no. Description C.B C.s.a Lighting load Normal socket load Power socket R Y B
HVAC HEATER
1 NORMAL SOCKETS 25 (3x4)mm2 1000 1000
2 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
3 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
ELCB 4 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
ELCB 5 POWER SOCKETS 20 (3x3)mm2 1000 1500 2500
ELCB 6 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
ELCB 7 POWER SOCKETS 20 (3x3)mm2 1500 1500
8 FLOOR BOX 20 (3x3)mm2 0 0
9 FLOOR BOX 20 (3x3)mm2 1200 1200
10 NORMAL SOCKETS 20 (3x3)mm2 400 400
11 NORMAL SOCKETS 20 (3x3)mm2 1600 1600
12 HAND DRYER 20 (3x3)mm2 1500 1500
13 HAND DRYER 20 (3x3)mm2 1500 1500
ELCB 14 NORMAL SOCKETS 20 (3x3)mm2 600 600
15 NORMAL SOCKETS 20 (3x3)mm2 800 800
16 NORMAL SOCKETS 20 (3x3)mm2 1600 1600
17 POWER SOCKETS 16 (3x3)mm3 1500 1500
18 POWER SOCKETS 20 (3x3)mm2 1500 1500
19 NORMAL SOCKETS 20 (3x3)mm2 1600 1600
20 NORMAL SOCKETS 20 (3x3)mm2 400 400
21 POWER SOCKETS 20 (3x3)mm2 1500 1500
22 NORMAL SOCKETS 20 (3x3)mm2 800 800
23 FLOOR BOX 20 (3x3)mm2 2000 2000
24 FLOOR BOX 20 (3x3)mm2 1800 1800
25 POWER SOCKETS 20 (3x3)mm2 1500 1500
26 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
27 NORMAL SOCKETS 20 (3x3)mm2 800 800
28 FLOOR BOX 20 (3x3)mm2 1200 1200
29 NORMAL SOCKETS 20 (3x3)mm2 1200 1200
30 NORMAL SOCKETS 20 (3x3)mm2 800 800
31 FLOOR BOX 20 (3x3)mm2 1200 1200
32 NORMAL SOCKETS 20 (3x3)mm2 1200 1200
33 POWER SOCKETS 20 (3x3)mm2 1500 1500
34 FLOOR BOX 20 (3x3)mm2 600 600
35 FLOOR BOX 20 (3x3)mm2 1200 1200
36 FLOOR BOX 20 (3x3)mm2 1200 1200
37 DISCONNECT SWITCH 20 (3x3)mm2 540 540
38 DISCONNECT SWITCH 20 (3x3)mm2 310 310
39 DISCONNECT SWITCH 20 (3x3)mm2 150 150
40 DISCONNECT SWITCH 20 (3x3)mm2 450 450
41 DISCONNECT SWITCH 20 (3x3)mm2 360 360
42 DISCONNECT SWITCH 20 (3x3)mm2 270 270
43 DISCONNECT SWITCH 20 (3x3)mm2 250 250
44 DISCONNECT SWITCH 20 (3x3)mm2 100 100
45 HEATER 20 (3x3)mm2 1500 1500
46 Spare 20 0
47 Spare 20 0
48 Spare 20 0
49 Spare 20 0
50 Spare 20 0
51 Spare 20 0
52 Spare 20 0
53 Space 0
54 Space 0
Disconnect switch Disconnect switch
Total lighting load Normal socket load Power socket R Y B
HVAC HEATER

Total conncetd load 0 32200 2430 1500 10500 15140 14970 16520

Balance percentage 9.38256658595642

Demand factor 0.9 0.7 0.9 0.5 0.75


Total Demand load 0 22540 2187 750 7875 33.4
Total demand load ( KWatt )
Note :-

1- ALL FEEDERS ARE ( CU/PVC/PVC)


2-PANEL BOARD ARE RECESSED PANEL BOARD
3-INDOOR PANEL BOARD PROTECTED WITH IP42
4-MAIN CIRCUIT BREAKER MUST BE MCCB
Panel name PP-G-L Circuit breaker 63 AT / 100 AF MCCB Recessed

4x16mm2+1x16mm2
Fed from MDP Cable Short circuit (L-G) XXXX
CU/PVC/PVC

Disconnect switch
Notes line no. Description C.B C.s.a Lighting load Normal socket load Disconnect switch HVAC Power socket R Y B
HEATER
1 POWER SOCKET 25 (3x4)mm2 800 800
2 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
3 NORMAL SOCKETS 20 (3x3)mm2 800 800
4 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
5 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
6 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
ELCB 7 NORMAL SOCKETS 20 (3x3)mm2 1200 1200
ELCB 8 POWER SOCKETS 20 (3x3)mm2 1500 1500
9 NORMAL SOCKETS 20 (3x3)mm2 1400 1400
10 POWER SOCKETS 20 (3x3)mm2 1500 1500
11 NORMAL SOCKETS 20 (3x3)mm2 600 600
12 POWER SOCKETS 20 (3x3)mm2 1500 1500
ELCB 13 POWER SOCKETS 20 (3x3)mm2 1500 1500
14 POWER SOCKETS 20 (3x3)mm2 1500 1500
ELCB 15 NORMAL SOCKETS 20 (3x3)mm2 1200 1200
16 NORMAL SOCKETS 20 (3x3)mm2 600 600
ELCB 17 POWER SOCKETS 16 (3x3)mm3 1500 1500
ELCB 18 POWER SOCKETS 20 (3x3)mm2 1500 1500
19 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
20 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
21 NORMAL SOCKETS 20 (3x3)mm2 1000 1000
ELCB 22 NORMAL SOCKETS 20 (3x3)mm2 600 600
ELCB 23 HAND DRYER 20 (3x3)mm2 1500 1500
24 NORMAL SOCKETS 20 (3x3)mm2 1200 1200
ELCB 25 HAND DRYER 20 (3x3)mm2 1500 1500
26 NORMAL SOCKETS 20 (3x3)mm2 600 600
27 NORMAL SOCKETS 20 (3x3)mm2 400 400
28 NORMAL SOCKETS 20 (3x3)mm2 800 800
29 FLOOR BOX 20 (3x3)mm2 600 600
30 DISCONNECT SWITCH 20 (3x3)mm2 320 320
31 DISCONNECT SWITCH 20 (3x3)mm2 360 360
32 DISCONNECT SWITCH 20 (3x3)mm2 100 100
33 DISCONNECT SWITCH 20 (3x3)mm2 100 100
34 DISCONNECT SWITCH 20 (3x3)mm2 360 360
35 DISCONNECT SWITCH 20 (3x3)mm2 290 290
36 DISCONNECT SWITCH 20 (3x3)mm2 510 510
37 DISCONNECT SWITCH 20 (3x3)mm2 100 100
38 DISCONNECT SWITCH 20 (3x3)mm2 160 160
39 HEATER 20 (3x3)mm2 1500 1500
40 Spare 20 0
41 Spare 20 0
42 Spare 20 0
43 Spare 20 0
44 Space 0
45 Space 0
46 Space 0
47 Space 0
48 Space 0

Disconnect switch
Total lighting load Normal socket load Disconnect switch HVAC Power socket R Y B
HEATER

Total conncetd load 0 20800 2300 1500 10500 11320 11350 12430

Balance percentage 8.93000804505229

Demand factor 0.9 0.7 0.9 0.5 0.75


Total Demand load 0 14560 2070 750 7875 25.3
Total demand load ( KWatt )
Note :-

1- ALL FEEDERS ARE ( CU/PVC/PVC)


2-PANEL BOARD ARE RECESSED PANEL BOARD
3-INDOOR PANEL BOARD PROTECTED WITH IP42
4-MAIN CIRCUIT BREAKER MUST BE MCCB
Panel name UPP-G-R Circuit breaker (32 OR 40) AT/100 AF MCCB Recessed

4x6mm2+1x6mm2
Fed from UPP-R Cable Short circuit (L-G) XXXX
CU/PVC/PVC

Disconnect switch Disconnect switch


Notes line no. Description C.B C.s.a Lighting load Normal socket load Power socket R Y B
HVAC HEATER
1 NORMAL SOCKETS 20 (3x4)mm2 600 600
ELCB 2 NORMAL SOCKETS 20 (3x3)mm2 400 400
3 FLOOR BOX 20 (3x3)mm2 1200 1200
4 FLOOR BOX 20 (3x3)mm2 1200 1200
5 FLOOR BOX 20 (3x3)mm2 1200 1200
6 FLOOR BOX 20 (3x3)mm2 1200 1200
7 NORMAL SOCKETS 20 (3x3)mm2 400 400
8 FLOOR BOX 20 (3x3)mm2 1800 1800
9 NORMAL SOCKETS 20 (3x3)mm2 600 600
10 FLOOR BOX 20 (3x3)mm2 1800 1800
11 NORMAL SOCKETS 20 (3x3)mm2 600 600
12 FLOOR BOX + NORMAL 20 (3x3)mm2 800 800
13 PROJECTOR 20 (3x3)mm2 1500 1500
14 NORMAL SOCKETS 20 (3x3)mm2 1200 1200
15 NORMAL SOCKETS 20 (3x3)mm2 1200 1200
16 Spare 20 0
17 Spare 20 0
18 Spare 20 0

Disconnect switch Disconnect switch


Total lighting load Normal socket load Power socket R Y B
HVAC HEATER

Total conncetd load 0 15700 0 0 0 5500 5200 5000

Balance percentage 9.09090909090909

Demand factor 0.9 0.7 0.9 0.5 0.75


Total Demand load 0 10990 0 0 0 11.0
Total demand load ( KWatt )
Note :-

1- ALL FEEDERS ARE ( CU/PVC/PVC)


2-PANEL BOARD ARE RECESSED PANEL BOARD
3-INDOOR PANEL BOARD PROTECTED WITH IP42
4-MAIN CIRCUIT BREAKER MUST BE MCCB
Panel name UPP-G-L Circuit breaker (32 OR 40) AT/100 AF MCCB Recessed

4x6mm2+1x6mm2
Fed from UPP-L Cable Short circuit (L-G) XXXX
CU/PVC/PVC

Disconnect switch Disconnect switch


Notes line no. Description C.B C.s.a Lighting load Normal socket load Power socket R Y B
HVAC HEATER
1 FLOOR BOX + NORMAL 20 (3x3)mm2 800 800
2 NORMAL SOCKETS 20 (3x3)mm2 600 600
ELCB 3 NORMAL SOCKETS 20 (3x3)mm2 600 600
4 NORMAL SOCKETS 20 (3x3)mm2 600 600
5 Spare 20 0
6 PROJECTOR 20 (3x3)mm2 1500 1500
7 NORMAL SOCKETS 20 (3x3)mm2 600 600
8 PROJECTOR 20 (3x3)mm2 1500 1500
9 Spare 20 0
ELCB 10 NORMAL SOCKETS 20 (3x3)mm2 200 200
11 Spare 20 0
12 Space 0

Disconnect switch Disconnect switch


Total lighting load Normal socket load Power socket R Y B
HVAC HEATER

Total conncetd load 0 6400 0 0 0 2200 2100 2100

Balance percentage 4.54545454545455

Demand factor 0.9 0.7 0.9 0.5 0.75


Total Demand load 0 4480 0 0 0 4.5
Total demand load ( KWatt )
Note :-

1- ALL FEEDERS ARE ( CU/PVC/PVC)


2-PANEL BOARD ARE RECESSED PANEL BOARD
3-INDOOR PANEL BOARD PROTECTED WITH IP42
4-MAIN CIRCUIT BREAKER MUST BE MCCB
Load (KW) IB Ic.b Standard
LP-G-R 3 5.681818 7.102273 32 or 40 AT
ELP-G-R 1.5 2.840909 3.551136 32 or 40 AT
LP-G-L 2.7 5.113636 6.392045 32 or 40 AT
ELP-G-L 1.6 3.030303 3.787879 32 or 40 AT
PP-G-R 33.4 63.25758 79.07197 80 AT
PP-G-L 24.5 46.40152 58.00189 63 AT
UPP-G-R 11 20.83333 26.04167 32 or 40 AT
UPP-G-L 4.5 8.522727 10.65341 32 or 40 AT
Standard
32
40
50
63
80
100