GENERAL NOTES

1.PROPORTION OF CONCRETE: 7. CONCRETE FLOORS AND STEPS ON FILL OR ON GROUND :


All concrete work shall be done on strict accordance with the dept. of public works Concrete from steps on fill shal be placed as follows: the earth or sand fill shall be laid to
specification for concrete and revised proportion as follows a uniform grade below the excavation of the finished floors, being placed in the layers not exceeding
Use Class A (1:2:4) concrete mixture, unless otherwise for footings,beams,columns,steps 15cm in thickness, its layer being thorougly wetted and tampered. the said fill shall be made as
and floors. concrete walls and foundation shall have sufficient strength. Concrete floor surface and other surface
Use Class B (1:2.5:5) concrete mixture, unless otherwise specified for all thicker than exposed after removed of forms shall be kept moist for a period of at least 7 days after being placed.
100mm steps All concrete placed during hot weather shall be protected from the rays of the sun and thoroughly
on fill, floor slabs on fill, concrete wall, concrete drainage and catch basin, and other works wetted at least three times during the first 7 days.
of similar nature.
8. FOUNDATIONS
2.CONSISTENCY: All foundatons shall be Class "A"(1:2:4) concrete mixture with the necessary reinforcement indicated
It is being recognized that an excess of water seriously reduces the strength of concrete, the in the plans. All zocalos shall be 0.15m thick concrete hollow blocks and shall be filled with class "B"
mixture (1:3:5) mortar mixture with the necessary reinforcement as indicated in the plan.
shall be made as dry as possible to produced of workable concrete.
9. FLOORINGS ( See Scheduled Plan)
3. REINFORCING STEEL BARS Unless otherwise noted on the plan, all flooring shall be 0.10m thick concrete slab on fill compacted
Unless otherwise specified plain,reinforcing steel bars shall be deformed bars in accordance gravel with 10mmø Temp bars spaced at 0.5m center to center bothways.
with the
metal reinforcing requirements of standard specifications on highways and bridges as 10. WALLS
adopted by the All exterior and interior wallss shall be of concrete hollow blocks with the necessary reinforcement
goverment. When place in work, it shall be free dirt, paints, spills of other foreign substance. unless otherwise indicated in the plans.

4, WOOD FORMS
Wood forms shall be sound,good quality, free from large loose knots and otherwise suitable
to facilitate
finishing exposed concrete as specified.

5.CURING
Use water curing which shall be affected by keeping the forms at all times sufficiently wet
with clean
water to prevent the joints in th forms of opening. Concrete surface not protected by forms
shall be
protected from the loss of surface moisture by covering with craft paper quilts. Protected
materials shall
be kept thoroughly wet for the duration of curing period which shall not less than 7 days.

6, EXCAVATION FOOTING AND FOUNDATIONS:


The bottoms of all excavation for footing and foundation which shall be undisturbed, earth
properly leveled off, tampered and approved by the Architect Excavations shall be antirlely
free from water during the pouring of concrete.
1 2 3 1 2 3
3400 3400

3400 3400

B1 B2
A A

755
C1
S1
C1 C1
F1 F2 F1 B3
100mm THK.
SLAB ON FILL
W/10mmø RSB
3018

3018
S2 S2

B14

B17

B18

B19
@500 OC BW

2384
Stair
Well

B4 B5
B B
C1 C1 C1 1075

2000
F3 F3
F4 S3 S3
3893

B6 B7

B13

B16

B20
1893
S3 S3

B8 B9
C C
C1 C1 C1 1010

B12

B15

B19
S4 S4
F5 F5
F6 B10 B11

Foundation Plan 2nd Floor Framing Plan


1 2 1 : 60
1 : 60
10mmø Rebars
(See Schedule of Slabs)
1 2 3 L/4 L/2 L/4

3400 3400

a
L/4
B1 B2 a
A
a

a
L/2

a
3018

B14

B17

B19
S2 S2 a

a
L/4
a
B4 B5
B
TOP BARS Note: a= Spacing (See Schedule of slab)
S3 S3
10mmø Full Length Bars
(See Schedule of Slabs)
B6 B7
3893

B13

B16

B20

S3 S3

B8 B9
C
1010

B12

B15

B19

S4 S4

B10 B11

Roof Framing
1 1 : 70

BOTTOM BARS

SLAB DETAIL
NTS
Note : Fc'=3000 psi (21Mpa)
RSB:20MM & Below (Gr.33)
25MM & Above (Gr.40)

SLAB SCHEDULE
Bottom Reinforcement Top Reinforcement

Slab Marked Slab Thickness


Along Short Span Along Long Span Over Long Support Along Short Support
Distribution
Continuous End Continuous End
Full Length Curtailed Full Length Curtailed
Support Support Support Support

S1 115 mm ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C

S2 115 mm ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C

S3 115 mm ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C

S4 115 mm ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C ø10@180 C/C

B B
2 BARS STRAIGHT/CONTINUOUS
L/4 (TOP BARS) L/4
BARS CUT (@SUPPORT)
TOP BARS
Stirrups
Spacing
STIRRUPS

L/6 2 BARS STRAIGHT/CONTINUOUS L/6 SIDE FACE REINFORCEMENT

D
(BOTTOM BARS)
(SFR)
ADDITIONAL BOTTOM
BARS CUT (@MIDSPAN)
Span (L)
BOTTOM BARS

TYPICAL BEAM DETAIL


NTS
@SUPPORT @MIDSPAN
Note : Fc'=3000 psi (21Mpa)
RSB:20MM & Below (Gr.33)
25MM & Above (Gr.40)

BEAM SCHEDULE
SIZE TOP REINFORCEMENT BOTTOM REINFORCEMENT
BEAM
SHEAR STIRRUPS
NUMBERS B D LEFT MID RIGHT RIGHT MID LEFT SFR DIAGONAL REMARKS
2-ø20
2-ø20 +2-ø20 6@50,4@100,REST @200
B1 175 500 2-ø20 2-ø20 +2-ø20 2-ø20 2-ø20 +2-ø20

2-ø20 2-ø20
B2 175 500 2-ø20 2-ø20 +2-ø20 2-ø10EF
+2-ø20 2-ø20 2-ø20 6@50,4@100,REST @200
+2-ø20
B3 175 500 2-ø20 2-ø20 2-ø20 2-ø20 2-ø20 2-ø20 6@50,4@100,REST @200

B4 175 500 2-ø20 2-ø20 2-ø20 2-ø20 2-ø20 2-ø20


+2-ø20 +2-ø20 +2-ø20 6@50,4@100,REST @200

B5 175 500 2-ø20 2-ø20 2-ø20 2-ø20 2-ø20 2-ø20 2-ø10EF


+2-ø20 +2-ø20 6@50,4@100,REST @200

B6 ,B10 175 500 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16 6@50,4@100,REST @200

B7 ,B11 175 500 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16 6@50,4@100,REST @200

B8 175 500 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16


+2-ø16 +2-ø16 +2-ø16 +2-ø16 +2-ø16 6@50,4@100,REST @200

B9 175 500 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16


+2-ø16 +2-ø16 +2-ø16 +2-ø16 +2-ø16 6@50,4@100,REST @200

B12,B19 175 500 2-ø16 2-ø16 2-ø16 2-ø20 2-ø20 2-ø20 4-ø10EF
+2-ø20 +2-ø20 +2-ø20 6@50,4@100,REST @200 CANTILIVERED

B13 175 500 2-ø16 2-ø16 2-ø16 2-ø20 2-ø20 2-ø20


+2-ø16 +2-ø16 +2-ø16 +2-ø20 +2-ø20 6@50,4@100,REST @200

B14 175 500 2-ø16 2-ø16 2-ø16 2-ø20 2-ø20 2-ø20


+2-ø16 +2-ø16 +2-ø16 +2-ø20 +2-ø20 6@50,4@100,REST @200
2-ø20 2-ø20 2-ø20
B15 175 500 2-ø16 2-ø16 2-ø16 +2-ø20 +2-ø20 +2-ø20 6@50,4@100,REST @200 CANTILIVERED
+2-ø16 +2-ø16 +2-ø16
B16 175 500 2-ø20
2-ø20 2-ø20 2-ø20 +2-ø20 2-ø20 2-ø20 6@50,4@100,REST @200
+2-ø16
+2-ø16
B17 175 500 2-ø16 2-ø16 2-ø16 2-ø20 2-ø16 2-ø16 6@50,4@100,REST @200
+2-ø16 +2-ø20
B18 175 500 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16 6@50,4@100,REST @200

B20 175 500 2-ø16 2-ø16 2-ø16 2-ø20 2-ø16


2-ø20 6@50,4@100,REST @200
+2-ø16 +2-ø16 +2-ø16 +2-ø20 +2-ø16
B21 175 500 2-ø16 2-ø16 2-ø16 2-ø16 2-ø16
2-ø20 6@50,4@100,REST @200
+2-ø16 +2-ø16 +2-ø16 +2-ø16 +2-ø16
X
SCHEDULE OF COLUMN
B -682 NGL

D
COLUMN

Y
D

T
X

B = 200
D = 500
REBARS:
12 PCS-20mmø
TYPICAL COLUMN-FOOTING DETAIL
NTS
TIES: 10mmø (3 SET)
6@50,6@100,REST @200 TO Note : Fc'=3000 psi (21Mpa)
MIDHEIGHT RSB:20MM & Below (Gr.33)
25MM & Above (Gr.40)

FOOTING DIMENSION FOOTING REINFORCEMENT


COLUMN 1 FOOTING COLUMN FOOTING
BOTTOM
NUMBERS NUMBERS TYPE
Y X D T
ALONG X ALONG Y

FC1 C1 PAD 1150 950 1200 300 ø16@300 C/C ø16@300 C/C

FC2 C1 PAD 1150 1300 1200 300 ø16@165 C/C ø16@300 C/C

FC3 C1 PAD 1450 1300 1200 300 ø16@300 C/C ø16@300 C/C

FC4 C1 PAD 1850 1650 1200 300 ø16@240 C/C ø16@240 C/C

FC5 C1 PAD 1500 1300 1200 300 ø16@250 C/C ø16@250 C/C

FC6 C1 PAD 1950 1750 1200 300 ø16@195 C/C ø16@195 C/C
B=175 B=175

300 TOP BARS


10mmø TIES@300mm C/C

10mmø HOR.& VERT.


FGL
100

300

D=400

D=400
BARS @60mm C/C B.W
STIRRUPS

300
VARIABLE

3-12mmø RSB CONT.


BACKFILL BACKFILL
W/10mmø TIES SPACED
@300mm C/C

300
CHB CHB
NGL
-600 BOTTOM BARS

300
@MIDSPAN @SUPPORT
3-12mmø
CONT.BARS
STAIR BEAM
10mmø TIES LANDING SLAB
@
300mmC/C

PLAN 12mmø @ 200 C/C


SECTION

300

TYPICAL WALL FOOTING DETAIL TYPICAL 1-10mmø


12mmø BARS @ 100mm C/C

TYPICAL
NTS BEND @ L/4 ALTERNATELY WITH

232
10mmø TEMP. BARS
@250mm C/C
FGL
-1137 GRAVEL

12
5
180 500

12mmø BARS @100mm C/C WITH


10mmø HORIZONTAL BARS@
250mm C/C
400
4 PCS-12mmø

STRUCTURAL STAIRS DETAIL


NTS