Professional Documents
Culture Documents
Refrigeration Technology
Siegfried Haaf, Linde AG, Köln, Federal Republic of Germany
Helmut Henrici, Linde AG, Köln, Federal Republic of Germany
e effective; external heat-transfer area temperatures, and these systems are therefore
el electrical discussed under → Cryogenic Technology.
g geometric
H generator Cold-vapor systems use the latent heat of
HP high-pressure; high-stage evaporation of a liquefied working fluid in a
i indicated; internal heat-transfer area; in- closed cycle to generate cold. The fluid (refriger-
tercooler ant) moves continuously through the cycle. The
I intermediate evaporating refrigerant remains at either con-
IP intermediate-pressure stant pressure or constant temperature as heat
LP low-pressure; low-stage is absorbed from the medium being cooled; it is
p pump then condensed at a higher pressure. The con-
r rich densing pressure is dictated by the conditions
R reflux condenser; refrigerant of heat rejection to the surroundings and by the
t ideal (theoretical) vapor pressure of the refrigerant. To keep the re-
v volumetric frigerant circulating between the two pressures,
w wall; weak energy must be supplied to the system in the
0 evaporator; evaporating form of mechanical work or heat.
Cold-vapor machines include the following
types:
1. Refrigeration [1–3], [28], [32], [34] 1) compressor refrigerating systems,
2) absorption refrigerating systems, and
The technology of generating and using subam- 3) steam-jet refrigerating systems.
bient temperatures is divided into three fields:
refrigeration, low-temperature technology, and Mechanical or electrical energy must be used
cryogenics. The boundaries between these fields to drive compressor refrigerating machines; ab-
are not clear cut. Refrigeration is generally un- sorption and steam-jet refrigerating systems are
derstood to mean from ambient temperature powered by thermal energy.
down to the standard boiling point of ethyl-
ene (ca. 170 K); low-temperature technology is
from 170 K down to the melting point of nitro- 1.1. Compressor Refrigerating Systems
gen (63 K); and cryogenics is below 120 K, as [2], [3], [14], [17], [19], [20], [28], [35–43]
suggested by the Ausschuss für Tieftemperatur-
Terminologie (Committee for Low-Temperature The most frequently used class of cold-vapor
Terminology). This article deals with refrigera- refrigeration machines is the compressor type.
tion; cryogenics is the subject of a separate arti- Figure 1 is a schematic diagram of a single-stage
cle (→ Cryogenic Technology). refrigeration system.
The purpose of refrigeration technology is
to cool materials to subambient temperatures or
hold them at such temperatures. The substance
to be refrigerated is cooled by a working fluid,
which moves in a closed cycle. Most of the cycli-
cal processes employed for refrigeration are re-
versals of processes used in heat engines.
In cold-gas processes, the working fluid is
always in the gaseous state; in cold-vapor pro-
cesses, the working fluid changes state from liq-
uid to gas and back to liquid. Cold-gas processes Figure 1. Single-stage compressor refrigerating system
a) Compressor; b) Condenser; c) Expansion valve; d) Evap-
are energetically less favorable than cold-vapor orator; e) Compressor drive motor
processes at all temperatures of interest for re-
frigeration, i.e., down to ca. − 100 ◦ C. In prac- A refrigerant enters the suction of a compres-
tice, cold-gas machines are important at lower sor (a) at a low pressure p0 , it is compressed to
Refrigeration Technology 3
a higher pressure pc , and is then condensed in The thermal balance of the process is then
a condenser (b) by rejection of heat to the sur-
roundings. The liquefied refrigerant is expanded Q̇0 + P =Q̇c
to pressure p0 in an expansion valve (c). The
where Q̇0 is the rate of cold production (refrig-
amount of refrigerant vapor (flash gas) produced
erating effect) in the evaporator, P is the com-
depends on operating conditions; this part of the
pressor drive power, and Q̇c is the rate of energy
refrigerant cannot be used to generate cold. As it
rejection in the condenser. When referred to the
absorbs heat, the liquid refrigerant evaporates in
mass flow rate, this relation is
the evaporator (d); it then returns to the suction
of the compressor. q0 +w =qc
the specific refrigerating effect (q0 ), and the spe- When frictional losses in the compressor are
cific thermal power (qc ) are defined as follows: taken into account, the effective power con-
sumption Pe is
w = h2 − h1
Pt Q̇0
Pe = =
q 0 = h1 − h4 ηe εt ηe
q c = h2 − h3
The coefficient of performance εt of the ideal Figure 4. Single-stage compressor refrigerating system
with internal heat exchange
process is a) Compressor; b) Condenser; c) Evaporator; d) Expansion
valve; e) Heat exchanger; f) Compressor drive motor
q0 h1 −h4
εt = =
w h2 −h1
The power consumption of the ideal process for Subcooling. The liquefied refrigerant can be
a given refrigerating effect can be determined: subcooled by heat exchange with the cold vapor
from the evaporator. A system with a heat ex-
Q̇0 h2 −h1 changer provided for this purpose is depicted in
Pt = =Q̇0
εt h1 −h4 Figure 4.
Subcooling the refrigerant results in a gain
The necessary rate of heat rejection needed in
in specific refrigerating effect. The increase for
the condenser for the ideal process is
some halocarbon refrigerants is greater than the
Q̇ct =ṁR qct =ṁR (h2 −h3 )
increase in specific compressor work because
compression is started in the superheating re-
In practice, compression is not an isentropic pro- gion instead of at saturation. The process is de-
cess, but a polytropic one in which the entropy scribed by the p – h diagram in Figure 5. This
increases. This nonideal behavior is described heat-exchange step can also be used to prevent
by the indicated efficiency η i of the compressor liquid droplets from being entrained from the
used. The indicated power consumption Pi for a evaporator into the compressor. Valve damage in
refrigerating effect Q̇0 is thus reciprocating compressors can thus be avoided.
Pt Q̇0
Pi = =
ηi εt ηi
Refrigeration Technology 5
the intermediate-pressure tank, along with the The refrigerant mass flow rates, the suction
vapor from expansion, results in the mass flow volume flow rates, and the effective power con-
rate of refrigerant being greater in the high-pres- sumptions for the compressors can be deter-
sure part of the system than in the low-pressure mined from information provided on the single-
part. stage process.
Two-Stage Compression with Two Evapora- Two-Stage Compression with Single-Stage
tors. If additional refrigeration is necessary at Expansion. On grounds of design simplicity,
the temperature corresponding to the intermedi- two-stage expansion is often not used in small
ate pressure, another evaporator can be placed systems with two-stage compression. This pro-
in parallel with the intermediate-pressure tank. cess is depicted in Figures 9 (schematic dia-
Figure 8 shows such a system with one evapo- gram) and 10 ( p – h diagram). In the low-pres-
rator for low pressure (e) and one for interme- sure stage, the vapor is compressed from pres-
diate pressure (d). The additional cooling of the sure p0 to the intermediate pressure pI . The vapor
vapor compressed by the low-stage compressor is then cooled by refrigerant from the condenser,
reduces energy consumption. The power balance which is injected through an expansion valve.
for this two-stage process is as follows:
Refrigerant CAS registry Formula Symbol Mr mp, ◦ C Standard Specific enthalpy of Isentropic Volumetric
number bp, ◦ C evaporation at exponent at p = 0 refrigerating
◦
standard bp, kJ/kg and t = 0 C effect at −15 to
+30 ◦ C, kJ/m3 ∗
p, v , v , h , h , p, v , v , h , h ,
MPa dm3 /kg dm3 /kg kJ/kg kJ/kg MPa dm3 /kg dm3 /kg kJ/kg kJ/kg
−70 0.0109 1.378 9006 −110.7 1356.2 0.0206 0.6706 940.1 123.02 372.97
−65 0.0156 1.389 6449 − 89.1 1365.2 0.0281 0.6765 705.3 127.87 375.52
−60 0.0219 1.401 4702 − 67.4 1374.0 0.0376 0.6825 537.2 132.84 378.07
−55 0.0302 1.412 3486 − 45.7 1382.6 0.0497 0.6888 415.0 137.92 380.59
−50 0.0409 1.424 2625 − 23.8 1391.1 0.0646 0.6954 324.8 143.11 383.09
−45 0.0545 1.436 2004 − 1.9 1399.3 0.0830 0.7021 257.2 148.40 385.55
−40 0.0717 1.449 1551 20.2 1407.3 0.1053 0.7092 205.9 153.81 387.97
−35 0.0931 1.462 1215 42.3 1415.1 0.1321 0.7165 166.5 159.31 390.34
−30 0.1195 1.475 962.6 64.6 1422.5 0.1640 0.7241 135.9 164.90 392.65
−25 0.1515 1.489 770.5 86.9 1429.7 0.2016 0.7320 112.0 170.57 394.89
−20 0.1901 1.504 622.8 109.3 1436.6 0.2455 0.7403 92.93 176.34 397.07
−15 0.2362 1.518 507.9 131.9 1443.2 0.2964 0.7490 77.69 182.16 399.16
−10 0.2908 1.534 417.7 154.5 1449.4 0.3550 0.7581 65.40 188.06 401.18
− 5 0.3548 1.549 346.2 177.2 1455.2 0.4219 0.7676 55.39 194.00 403.10
0 0.4294 1.566 289.0 200.0 1460.7 0.4980 0.7776 47.18 200.00 404.93
+ 5 0.5158 1.583 242.8 222.0 1465.9 0.5839 0.7882 40.40 206.03 406.65
+10 0.6150 1.601 205.3 245.9 1470.6 0.6803 0.7994 34.75 212.11 408.27
+15 0.7284 1.619 174.6 269.0 1474.9 0.7881 0.8112 30.03 218.21 409.77
+20 0.8573 1.639 149.4 291.4 1479.0 0.9081 0.8238 26.04 224.34 411.14
+25 1.003 1.659 128.4 314.9 1482.4 1.041 0.8373 22.66 230.50 412.38
+30 1.167 1.680 110.8 338.5 1485.3 1.188 0.8517 19.78 236.69 413.48
+35 1.350 1.702 95.96 362.3 1487.8 1.350 0.8673 17.31 242.93 414.42
+40 1.555 1.726 83.47 386.3 1489.7 1.527 0.8841 15.17 249.22 415.19
+45 1.782 1.750 72.85 410.5 1491.1 1.721 0.9024 13.32 255.57 415.76
+50 2.033 1.777 63.78 434.9 1491.9 1.933 0.9226 11.70 262.03 416.11
+55 2.310 1.805 56.07 458.6 1492.4 2.164 0.9449 10.29 268.62 416.20
+60 2.614 1.834 49.33 483.9 1491.8 2.415 0.9700 9.033 275.41 415.99
∗ p = pressure; v = specific volume of the liquid; v = specific volume of the saturated vapor; h = specific enthalpy of the
liquid; h = specific enthalpy of the saturated vapor.
Refrigeration Technology 11
λ =ηv − (1 −ηw )
compressor and that the lubricating oil will not eration systems, especially those with moderate
degrade heat transfer in the heat exchangers. and high capacity.
In special cases, e.g., at very low evaporat- Most of these devices are oil-flooded, two-
ing temperatures, oil-less compression may be shaft machines (Fig. 17). The refrigerant vapor
required. Nonlubricated compressors are used is compressed by two screw-shaped rotors (b and
widely in process engineering and are suitable c), which engage and make contact with each
for this purpose. In these crosshead machines, other. The rotors turn in opposite directions in-
either the piston does not make contact with side a closefitting case. As the rotors turn, the
the cylinder (labyrinth compressor) or the pis- spaces between teeth continuously increase and
ton rings are made of a self-lubricating mate- decrease in size because of the screw shape.
rial, usually polytetrafluoroethylene or sintered Thus, as in a reciprocating compressor, refrig-
carbon with appropriate additives (plastic-ring erant vapor is pulled in, compressed, and dis-
nonlubricated compressor). charged. The position and size of the discharge
port in the housing determine the ratio of dis-
charge to suction volume (installed volume ratio
or, because for a given refrigerant conversion to
pressure is possible, installed pressure ratio).
The screw compressor has neither clearance
volume nor working valves. Precooled oil is usu-
ally injected into the compression space bet-
ween rotors after completion of the suction pro-
cess. This procedure allows direct torque trans-
mission from the driven rotor (usually male)
to the partner rotor, seals the clearances bet-
ween rotors and housing, and removes the en-
thalpy of compression. Oil injection is driven
by a pump or by the pressure of liquefaction.
Independent of the compression ratio, pressure
differences up to 2 MPa can be attained without
the compression temperature exceeding 100 ◦ C.
Injected oil is separated from the refrigerant
stream in one or two oil separators (depending
on the degree of separation required), which are
connected in series. The oil is cooled and re-
turned to the compressor. The principal refrig-
erants used are ammonia (R 717) and chlorodi-
fluoromethane (R 22); in heat-pump service, di-
chlorodifluoromethane (R 12) and dichlorotetra-
fluoroethane (R 114) are also employed.
Capacity is controlled by altering the mass
flow rate with an axially adjustable movable slid-
ing. When the sliding is moved toward the dis-
charge port, usually by oil pressure, it creates an
Figure 17. Principle of a rotating-screw compressor opening through which the suction-side vapor
A) Cross section: a) Inlet; b) Female rotor; c) Male rotor; flows back into the inlet casing. Efficiency fac-
d) Return channel; e) Return channel; f) Movable slidingB) tors are favorable over a wide range of part-load
Top view of the rotors: a) Inlet; b) Discharge conditions.
Small screw compressors, without a mov-
Screw Compressors. Screw compressors able sliding and offering theoretical flow rates
are being used increasingly in industrial refrig- ≤100 m3 /h, are available. As with smaller recip-
rocating compressors, capacity can be divided
14 Refrigeration Technology
among several machines, which are turned on ing a sequence of continuously varying com-
and off to meet demand. pression spaces.
Besides the tooth shape and number shown Overflow losses at the vanes limit compres-
for the male and female rotors in Figure 17, sion ratios to only 1 : 5 for economic reasons.
other rotor profiles with different numbers of Therefore, multivane rotary compressors have
teeth are also available. Energetically optimal restricted applications in refrigeration. They are
rotor tip speeds are generally 25 – 35 m/s; with used as boosters in reciprocating compressor
smaller rotors, gearboxes are required between plants with theoretical flow rates up to ca.
drive motor and compressor in order to attain 1000 m3 /h. Their advantages are low mass and
these values. The drive motor speed is usually small volume (due to the high rotation speeds)
3000 min−1 . as well as vibration-free operation. Drawbacks
Semihermetic screw compressors are used, include vane wear, especially when lubrication
especially in air conditioning. In these devices, is inadequate, and the sharp drop in volumetrc
the refrigerant vapor on the suction or discharge efficiency at higher compression ratios.
side is used to cool the rotor.
The most important qualities of the screw-
type compressor are simple, compact design; 1.1.2.2. Dynamic Compressors
low vibration and noise levels; high reliability;
insensitivity to liquid refrigerant flow rates on Centrifugal Compressors. All turbine
the suction side; efficient, continuous capacity compressors (turbocompressors) for refrigera-
control; and efficiency factors similar to those tion service are radial-flow centrifugal designs;
of reciprocating compressors. they are used for refrigerating capacities from
To reduce the specific power consumption, ca. 300 to >104 kW. These machines have sig-
medium- and high-capacity screw compressors nificant advantages over reciprocating compres-
are fitted with an intermediate injection device sors: low mass per unit capacity, decreased space
(see Section 1.1). To allow further optimization requirement, vibration-free operation, oil-free
of the efficiency factor under a variety of service compression, and high reliability due to the ab-
conditions, the installed volume ratio of some sence of reciprocating machine parts and valves.
types can be varied continuously during opera- For a given design, the discharge head ∆h for
tion. one stage is set by the tip speed u of the gas:
u2
Multivane Rotary Compressors. The ∆h = ψ
2g
multi-vane rotary compressor (Fig. 18) consists
of a cylindrical housing (a) in which an eccen- where the pressure coefficient ψ depends on the
trically mounted rotor (c) with several vanes (b) vane shape (ψ = ca. 1.0 for vanes with a back-
rotates. ward curve and 1.3 for vanes with radial ends).
If the discharge head is known, then the com-
pression ratio for isentropic compression is
κ
pc x− 1 ∆h Mr κ−1
= · · +1
p0 x T0 R
where M r is the relative molecular mass and R
is the universal gas constant. Substances with
high relative molecular masses thus favor the use
of centrifugal compressors in terms of construc-
tion cost: achieving a given compression ratio
then requires a lower discharge head, and often
Figure 18. Principle of a multivane rotary compressor fewer stages, than with a low molecular mass
a) Housing; b) Vane; c) Rotor fluid. Typical refrigerants for turbocompressor
refrigeration plants are trichlorofluoromethane
The vanes, guided in the rotor, are pressed by
(R 11), dichlorodifluoromethane (R 12), and di-
centrifugal force against the housing wall, form-
chlorotetrafluoroethane (R 114); for very high
Refrigeration Technology 15
passes and the refrigerant condenses on the shell for various types of cooling water are given in
side. The end covers, containing the bends, are Table 4.
removable so that the tubes can be cleaned easily
from the water side.
Seawater 1 1
Brackish water 4 2
Figure 21. Heat-transfer coefficients for shell-and-tube am-
Water from cooling tower 2 2
monia condensers
Spring water 2 2
Ri = internal fouling resistance
Stream water 4 2
∗ Water velocity
with halocarbon refrigerants because of poorer countercurrently. Because the partial pressure of
heat transfer. The tubes are made of cop- water vapor in the air is lower than that of the
per or brass; with seawater, they are made of cooling water, a small portion of the water evap-
copper – nickel alloys. The heat-transfer coeffi- orates and thus cools itself. The cooled water is
cients for halocarbon refrigerants, referred to the collected in a catch basin and is then available
external tube area, are 600 – 1200 W m−2 K−1 to absorb heat again in the condenser.
at w = 1.5 – 3 m/s when the fouling resistance
Ri = 1 – 2×10−4 m2 K/W. Evaporative Condensers. An evaporative
If the water is very dirty or space is limited, condenser combines the actions of a cooling
vertical condensers are used (Fig. 22). These tower and a water-cooled condenser. It is used
shell-and-tube devices are open on the water for medium to large capacities when a cooling
side and easy to clean; under certain conditions, tower is not available and when cooling water is
cleaning does not require shutdown. Cooling in short supply. Freshwater consumption is the
water enters from a distribution tank at the top same as that with a tower and water cooling.
and is led down the inside of the tubes by spi- The refrigerant condenses in a system of
ral vanes. Thus, the water falls as a film, while tubes (Fig. 24), which are sprayed with water
the refrigerant condenses on the outside of the from a tank. Air flows upward through the tube
tubes. array either by free convection or, more often,
by forced draft. The air absorbs the heat of con-
densation by evaporating water from the tube
surfaces. The water level in the tank is held con-
stant by freshwater supplied under float control.
The mist collector above the array of pipes pre-
vents water droplets entrained in the airstream
from escaping.
ferred to the external tube surface area may be similar to those for vertical-tube evaporators un-
400 – 2000 W m−2 K−1 , depending on the brine der the same conditions.
being cooled and the tube design.
A vertical-type evaporator (Fig. 28) consists Evaporators for Gas Cooling. Gases, espe-
of a system of vertical, inclined, or hairpin tubes cially air for space cooling, are cooled on the
connected to one header at the top and another at outer surface of finned evaporators (Fig. 29).
the bottom, with a liquid separator in line down- The apparatus consists of a system of tubes
stream. The refrigerant stays at a constant level with bonded fins that are connected in series and
in the tubes as it evaporates, thus cooling the sec- parallel on the refrigerant side. The gas is usually
ondary refrigerant which is circulated around the drawn or forced through the system of fins by a
tubes by an agitator. This kind of apparatus was blower connected to the evaporator; natural con-
formerly employed to cool brine in open vessels; vection cooling is employed less often. When the
today, it is used mainly as an ice-bank evapo- gas is cooled, water or other constituents often
rator, where the ice frozen around the tubes is condense or freeze. If a frost coating forms on
melted off periodically by the circulating water. the tubes and fins, continuous operation is pos-
sible only if the system includes a second unit.
Defrosting is accomplished from the pressure
side of the compressor with warm compressed
gas, which gives up its heat of condensation to
the cold surfaces of the apparatus; otherwise,
electric heating rods can be built into the evap-
orator system. To eliminate frequent defrosting,
fin spacings of 8 – 20 mm are used in air coolers
with a frost deposit. In air conditioners for oper-
Figure 28. Vertical-type evaporator for ammonia ation above the freezing point of water, compact
a) Refrigerant inlet; b) Refrigerant vapor outlet; c) Oil drain; systems with close fin spacings (ca. 2 mm) are
d) Refrigerant separator; e) Agitator used.
System capacities, materials, and tube or
fin sizes vary widely. As with air-cooled con-
densers, galvanized steel is used in ammonia
systems, and copper tubes with aluminum fins
are used for halocarbon refrigerants.
With halocarbon refrigerants, as in the case
of liquid chillers, direct expansion is used. The
refrigerant is expanded into the tubes as a liq-
uid – vapor mixture; it is completely evaporated
and superheated by several degrees. Where a
network of evaporators with finned units exists
Figure 29. Finned air cooler as direct-expansion evaporator (e.g., in ammonia refrigerant plants), expanded
a) Refrigerant inlet; b) Refrigerant vapor outlet; liquid refrigerant is transported through the sys-
c) Thermostat-controlled expansion valve; d) Sensor
tem by pumps. Part of the refrigerant evaporates,
A parallel-plate evaporator consists of sev- and the resulting vapor – liquid mixture goes to
eral plates, connected in parallel, in which the a collecting tank that also serves as a refrigerant
refrigerant evaporates. The corrugated plates are separator.
welded or soldered together to form narrow Instead of the evaporating refrigerant, a sec-
channels, which may be horizontal or vertical. ondary refrigerant can be pumped through the
This kind of device can thus be employed in di- chiller. At air temperature <0 ◦ C, heat-transfer
rect expansion or flooded mode. The plates are coefficients are relatively low (ca. 7 – 17 W m−2
made of galvanized or lacquered steel or, in spe- K−1 ) because of frost formation. At tempera-
cial cases, stainless steel. These units are em- tures > 0 ◦ C, values of up to 30 W m−2 K−1 can
ployed as drinking-water and brine chillers and be achieved with some designs. At gas pres-
for ice storage. The heat-transfer coefficients are sure significantly greater than 0.1 MPa, shell-
Refrigeration Technology 21
and-tube devices are used; like similar liquid valves use electronic actuation, which offers bet-
chillers, these can be designed for flooded or ter dynamic properties; this can be an advantage
direct expansion operation. especially when the cooling loads vary rapidly.
trol unit detects a change in temperature, a com- ondary refrigerant, as well as primary refriger-
pressor capacity stage is turned on or off. If the ant. Virtually all the pumps used are centrifu-
evaporating pressure is to be held constant, a gal. Whereas open pumps are commonly em-
low-pressure pressostat is used instead of a ther- ployed for secondary refrigerants, hermetically
mostat. The high-pressure pressostat carries out sealed (canned-motor) pumps are usually found
a corresponding function on the condenser side. in primary-refrigerant service. Because of the
Oil-pressure differential cutouts are employed as low static pressure differences to be overcome
oil delivery monitors in compressors with pres- in finned air chillers or air-cooled and evap-
surized oil lubrication. orative condensers, the fans used with these
For freshwater-cooled refrigerating systems, units are generally axial-flow types. Some air-
automatic water valves reduce water consump- conditioning evaporators and evaporative con-
tion. They control the flow rate of cooling water densers also have radial-flow fans. To avoid cold
so that a constant condensing pressure is main- losses, all components that operate under evap-
tained, independent of the condensing capacity orating pressure and are located in ambient-
required. temperature areas are provided with insula-
Automatic shutoff, especially of refrigerant tion. Insulating materials include cork, cellu-
piping, is accomplished with solenoid valves. lar glass, foamed polystyrene, and polyurethane.
These devices enable, for example, the supply The most economical insulation thickness de-
of refrigerant to an evaporator to be discontin- pends strongly on refrigerant and ambient tem-
ued. If intermediate positions between open and peratures; it should always be sufficient to pre-
closed are needed, as is often the case in cooling- vent sweating. Vapor locks must be included to
water and brine loops, motor-actuated valves are prevent the diffusion of water vapor.
used.
Pressure safety relief devices are employed
to prevent excessive pressure in system com- 1.2. Absorption Refrigerating Systems
ponents. These devices include rupture disks, [3], [8], [14], [27], [30], [97–106]
pressure safety relief valves, and safety pres-
sure cutouts. Their design and use must comply Absorption refrigeration systems differ from
with applicable national safety provisions and compressor refrigerating systems in two main
standards (DIN 8975 in the Federal Republic of respects: (1) The refrigerant vapor drawn out of
Germany). the evaporator is compressed not by a mechan-
Systems using halocarbon refrigerants often ical compressor but by a thermal one, which
have heat exchangers to subcool the liquid re- consists of an absorber, a solution pump, and
frigerant flowing to the control device and su- a generator. (2) Operation of the thermal com-
perheat the refrigerant vapor flowing to the com- pressor requires a solvent (a second working
pressor. The exchangers improve the coefficient fluid) as well as a refrigerant. The most impor-
of performance and volumetric refrigerating ef- tant refrigerant – solvent pairs are:
fect with many refrigerants (R 12), (R 502) and 1) ammonia – water, used for evaporating tem-
the filling ratio in direct-expansion evaporators; peratures between +10 and −60 ◦ C, and
they also protect the compressor against intake 2) water – lithium bromide solution, used
of liquid refrigerant. As a rule, refrigerant vapor for evaporating temperatures >0 ◦ C (air-
is led through internally finned tubes, while liq- conditioning systems).
uid moves through the baffled shell-side space Although many other pairs have been sug-
of the apparatus in crosscurrent – countercurrent gested and studied, none is widely used.
flow.
Filters in the refrigerant line keep the com-
pressor and control valve free of solid con- 1.2.1. Ammonia – Water Absorption
taminants. Halocarbon refrigerant loops include Refrigerating Systems
dryers, which prevent refrigerant degradation
and icing in expansion valves on expansion be- Figure 31 is a schematic diagram of a single-
low 0 ◦ C. Refrigerating units must have pumps stage ammonia – water absorption refrigerating
to transport cooling water, brine, or other sec- system.
Refrigeration Technology 23
the evaporator; PP is the drive power of the solu- portional decrease of the consumption rates of
tion pump; and Q̇A , Q̇c , and Q̇R are the rates of heating agent and cooling water can be expected.
heat removal in the absorber, condenser, and re- The most important advantage of absorp-
flux condenser, respectively. In many cases, PP tion refrigerating systems is that they can uti-
can be neglected in comparison with the other lize waste heat. However, the following points
quantities. are also important for the use of these systems:
Instead of the coefficient of performance for safety in operation, good part-load performance,
the compression system, the heat ratio (Q̇0 /Q̇H ) adaptability to changing service conditions, and
is used here for thermodynamic assessment: low noise emission. Investment costs and en-
ergy consumption are higher than for compa-
Q̇0 Q̇0 rable compressor refrigerating systems, but the
ζ= ≈
Q̇H +PP Q̇H low price of waste heat can often be crucial in
the decision to use an absorption system.
This ratio indicates how much refrigerating ef-
fect can be accomplished by a given thermal
power supplied to the generator at the evapo-
rating temperature t 0 . The heat ratio for today’s
large-capacity ammonia – water absorption sys-
tems is ca. 0.7 when t 0 ≈ 0 ◦ C; between 0.47 and
0.40 for t 0 from −20 to −30 ◦ C; and between
0.34 and 0.25 for t 0 from −40 to −50 ◦ C.
In the case of compressor refrigerating sys-
tems, economic considerations dictate a shift to
two-stage or multistage operation above a cer-
tain compression ratio that depends on the com-
pressor design. By contrast, two-stage absorp-
tion systems are employed when the tempera-
tures of the heating medium, the cooling water,
and the evaporating temperature (which deter-
mine the concentration difference between the
weak and rich solutions) take on values so un-
favorable that this concentration difference be-
comes <5 %. In two-stage absorption systems,
the two solvent loops are connected in series;
the pressure difference between generator and
evaporator is divided into two steps. Figure 33. Steam-heated vertical sprayed generator
Changes in the process (e.g., the use of mul- a) Reflux condenser; b) Distillation section; c) Heating sys-
tistage absorption, the injection of cold rich so- tem; d) Solution vessel; e) Rich solution inlet; f) Coolant
lution into the distillation column, or multistage inlet; g) Coolant outlet, h) Ammonia vapor outlet; i) Weak
solution outlet; j) Inlet for heating steam; k) Condensate
desorption) lead to further improvement in the outlet; l) Guide inserts; m) Packed bed; n) Trays; o) Sepa-
heat ratio and to a reduction in the necessary rator
temperature of the heating agent.
Absorption refrigeration systems can be
driven by relatively low-grade heat, which is
1.2.2. Equipment for Ammonia – Water
often available from industrial processes. The
Refrigerating Systems
process can then be economically optimized for
given heating media and cooling-water temper- Absorption refrigerating systems employing
atures. water – lithium bromide solution are used pri-
Alteration of the solution flow rate and the marily in air-conditioning systems, because this
heating capacity allows infinitely variable con- combination of substances is nontoxic. These
trol down to the lowest heat-removal rate. Up systems, usually factory-assembled, with ca-
to ca. 10 % of the refrigerating capacity, a pro- pacities of 200 – 6000 kW, are distinguished by
Refrigeration Technology 25
Figure 35 shows a high-capacity solution heat The weak, high-temperature solution is recy-
exchanger, consisting of several shell-and-tube cled through the solution heat exchanger to the
units mounted one above another. absorber, where the vapor from the evaporator
is absorbed by cooling water. Steam produced
in the generator is condensed in the condenser;
1.2.3. Water – Lithium Bromide Absorption the condensate flows to the evaporator, where it
Refrigerating Systems absorbs heat from the secondary refrigerant. An-
other pump (i) circulates refrigerant to spray the
The condenser and evaporator designs used in evaporator tubes; the refrigerant vapor produced
absorption refrigeration systems are largely the is absorbed by the weak solution in the bottom
same as those employed in compression systems part of the vessel. An inhibitor (usually lithium
(Sections 1.1.3 and 1.1.4). Therefore, only the nitrate or lithium chromate) is added to the loop
generator, absorber, and solution heat exchanger to combat corrosion.
are discussed in this section. Other equipment Lower capacity water – lithium bromide ab-
worth mentioning includes extra heat exchang- sorption systems have attracted interest in con-
ers, refrigerant and solution receivers, capac- nection with solar energy utilization.
ity controls, ventilation devices, and expansion
valves.
Figure 36 is a schematic diagram of a lithium 1.3. Steam-Jet Systems [3], [5], [30], [107],
bromide absorption refrigerating system. The [108]
principal components are two vessels mounted
one above the other. The lower vessel (a) con- The steam-jet refrigeration system can be re-
tains the evaporator (c) and the absorber (d). The garded as a thermally driven compression sys-
generator (e) and the condenser (f) are located tem in which vapor is compressed in a jet ap-
inside the upper vessel (b). Because the system paratus. Its operation is illustrated in Figure 37.
operates under a high vacuum, virtually no heat-
transfer losses occur between the components in
each vessel, despite the large temperature differ-
ences. A pump (g) delivers rich solution through
the heat exchanger (h) to the generator, where
part of the water is driven out of it.
Figure 36. Water – lithium bromide absorption system Steam is generated at pressure p1 in boiler
a) Lower vessel; b) Upper vessel; c) Evaporator; d) Ab- (g); the mass flow rate of steam is ṁ1 . In the
sorber; e) Generator; f) Condenser; g) Pump; h) Heat ex-
changer; i) Pump nozzle (a), the steam is expanded to the pressure
p0 prevailing in the evaporator (e); then, in the
Refrigeration Technology 27
mixing chamber (c), it is mixed with steam (rate 1.4. Thermoelectric Refrigeration [3],
ṁ0 , pressure p0 ) from the evaporator. Next, the [28], [109–112]
pressure of the two streams ṁ1 and ṁ0 is raised
to the condensation pressure in the diffuser (b). Thermoelectric refrigeration is based on the
Virtually all the kinetic energy is transformed Peltier effect, which is the reversal of the See-
to pressure. When heat is withdrawn in the con- beck principle. In an electrical circuit consisting
denser (d), the steam condenses. The condensate of two different conductors and a d.c. voltage
is divided into two substreams ṁ1 and ṁ0 ; ṁ1 source, one of the junctions between the two
is delivered to the steam boiler (g) by a pump conductors is heated while the other is cooled.
(f), and ṁ0 is led to the evaporator through an If the direction of the current is changed, the
expansion valve (h). Here, substream ṁ0 evapo- warm and cold junctions change places. Energy
rates at pressure p0 , absorbing heat; the exiting is lost by Joule heating in the conductors, be-
expanded steam, moving at a higher velocity, cause of their resistance, and by conduction from
sucks this stream into the mixing chamber. the warm junction to the cold one; these losses
Water, employed mainly as working steam greatly reduce the coefficient of performance.
and as refrigerant in the steam-jet system, is a The maximum temperature difference that can
low-cost, hazard-free working fluid with a high be produced between the junctions and the coef-
specific enthalpy of evaporation. The pressure ficient of performance are primarily determined
p0 is usually between 0.6 and 1.2 kPa; pc de- by the properties of the two conducting mate-
pends on the cooling-water temperature and lies rials: thermoelectric force e, electrical conduc-
between 3 and 8 kPa. tivity σ, and thermal conductivity λ. These are
This system’s drawbacks are the large spe- grouped into a parameter called the figure of
cific volume in the region of the evaporating merit z:
temperatures, the high vacuum, and the limita-
e2 ·σ
tion placed on the evaporating temperature by z=
λ
the freezing point. Lower temperatures can be
reached if hydrocarbons and halocarbon refrig- The thermoelectric force and the electrical
erants are used as working fluids. conductivity should be as high as possible,
As in absorption systems, the decisive quan- while the thermal conductivity should be as
tity for assessing this process in energy terms small as possible. This requirement is best
is the heat ratio ζ, which indicates how much met by alloys of semiconducting materials,
refrigerating effect Q̇0 is gained from the heat- such as lead – tellurium, antimony – bismuth,
ing power Q̇H and the pump power Pp supplied and germanium – silicon (→ Semiconductors).
(see Section 1.2.1). The heat ratios attained in Because the capacity of a single Peltier el-
practice are much lower than those for an ab- ement is very low, a number of elements must
sorption system. With multistage jet units and be connected in a thermally parallel manner so
multistage evaporation, the energy performance that their refrigerating effects are additive. Fig-
can be improved. ures of merit z of (3.0 – 3.5)×10−3 K−1 can be
The advantages of the steam-jet system are attained with current semiconductor technology,
low plant costs due to the simple design, utiliza- so the available coefficients of performance are
tion of waste heat, small space requirement, and comparable with those of other processes only
low maintenance costs. These are partly offset by at very small refrigerating capacities.
the drawback of high operating costs, especially Thermoelectric refrigeration is used in spe-
because of the large consumption of cooling wa- cial cooling devices for laboratory purposes and
ter. These features make the steam-jet process in low-capacity air-conditioning units.
suitable for short-term refrigeration using cheap
waste heat.
2. Industrial Applications of
Refrigeration [10–13], [21], [31]
Many industrial chemical processes require low
temperature, often in conjunction with large re-
28 Refrigeration Technology
frigerating capacity. Examples of design of re- ants is suitable when cold is to be distributed to
frigerating plants for these applications are de- several consumer locations or when contact bet-
scribed in this chapter. Machines and equipment ween primary refrigerant and product resulting
for ice making, food technology, climate control, from leaks must be avoided. The selection of a
and construction are also discussed. secondary refrigerant depends on temperature,
Table 5. Important data for calcium chloride brines
heat-transfer properties, material compatibility,
toxicity, and price. Figure 38 shows the tempera-
Density Salt content, Start of Specific ture ranges for the most important secondary re-
at 15 ◦ C, kg CaCl2 / freezing, heat at 0 ◦ C, frigerants; the shaded part of each range should
kg/m3 100 kg ◦
C kJ kg−1 K−1
solution
be avoided whenever possible, because of poor
heat-transfer properties. The favorable qualities
1000 0.1 0.0 4.20
1010 1.3 − 0.6 4.13
of water mean that it is almost always preferred
1020 2.5 − 1.2 4.05 when the evaporating temperature of the refrig-
1030 3.6 − 1.8 3.98 erant is > 0 ◦ C. Down to − 40 ◦ C, calcium chlo-
1040 4.8 − 2.4 3.90 ride brines are commonly used with steel; eth-
1050 5.9 − 3.0 3.83
1060 7.1 − 3.7 3.76
ylene glycol – water mixtures are used more and
1070 8.3 − 4.4 3.69 more because of their good behavior with respect
1080 9.4 − 5.2 3.62 to ferrous and nonferrous metals.
1090 10.5 − 6.1 3.56 The concentrations of aqueous mixtures are
1100 11.5 − 7.1 3.50
1110 12.6 − 8.1 3.44 chosen so that the freezing point lies several de-
1120 13.7 − 9.1 3.38 grees below the evaporating temperature. Tables
1130 14.7 −10.2 3.33 5 and 6 list important data for calcium chloride
1140 15.8 −11.4 3.27
1150 16.8 −12.7 3.22
brines and ethylene glycol – water mixtures.
1160 17.8 −14.2 3.17
Table 6. Important data for ethylene glycol – water mixtures
1170 18.9 −15.7 3.13
1180 19.9 −17.4 3.08
Density Glycol con- Start of Specific
1190 20.9 −19.2 3.04
at 15 ◦ C, tent, kg freezing, heat at 0 ◦ C,
1200 21.9 −21.2 3.00
kg/m3 glycol/100 kg ◦
C kJ kg−1 K−1
1210 22.8 −23.3 2.96
solution
1220 23.8 −25.7 2.93
1230 24.7 −28.3 2.90 1005 4.6 − 2 4.10
1240 25.7 −31.2 2.87 1010 8.4 − 4 4.06
1250 26.6 −34.6 2.84 1015 12.2 − 5 3.98
1260 27.5 −38.6 2.81 1020 16.0 − 7 3.89
1270 28.4 −43.6 2.78 1025 19.8 −10 3.85
1280 29.4 −50.1 2.75 1030 23.6 −13 3.77
1286 ∗ 29.9 −55.0 2.74 1035 27.4 −15 3.73
1290 30.3 −50.6 2.72 1040 31.2 −17 3.64
1300 31.2 −41.6 2.70 1045 35.0 −21 3.56
1310 32.1 −33.9 2.67 1050 38.8 −26 3.52
1320 33.0 −27.1 2.65 1055 42.6 −29 3.43
1330 33.9 −21.2 2.62 1060 46.4 −33 3.35
1340 34.7 −15.6 2.60
1350 35.6 −10.2 2.58
1360 36.4 − 5.1 2.55
1370 37.3 0.0 2.53
Equipment. With few exceptions, chilling of
∗ Eutectic the secondary refrigerant or other liquid takes
place in shell-and-tube heat exchangers. Direct-
expansion-type evaporators are employed with
halocarbon refrigerants at capacities of up to ca.
2.1. Chilling of Liquids [18], [24], [26], 1000 kW. At higher capacities and with ammo-
[28], [30], [33], [113–117] nia as refrigerant, flooded shell-and-tube evap-
orators are used.
Liquid chilling usually refers to the cooling of Liquid-chilling machines for temperatures
secondary refrigerants in order to transfer cold > 0 ◦ C, with treated water as secondary refrig-
to other products. The use of secondary refriger- erant, are widely used, especially for air condi-
Refrigeration Technology 29
tioning, but also for manufacturing processes, high reliability. Like reciprocating plants, they
food technology, cooling plastics machinery, can be adapted to varying discharge pres-
etc. Nearly all of these units operate with halo- sures; this is important for air-cooled chillers.
carbon refrigerants. The compressors are driven by bipolar three-
Plants with reciprocating compressors are phase motors. In hermetic or semihermetic
in service at refrigerating capacities up to ca. motor – compressors, the oil stream separation
1000 kW; above this range, centrifugal compres- required on the discharge side of screw com-
sors are used most widely. Compact systems pressors can take place inside the motor space,
of this type are made for capacities up to ca. so that compact construction is possible. In sys-
5000 kW. These water chillers have compres- tems with a single compressor, capacity control
sor, evaporator, condenser, control, safety de- is exerted with a slide valve; with several com-
vices, and electrical switching; they are factory- pressors, individual machines are turned on and
assembled on a single frame, so that setup and off as in the case of reciprocating compressors.
commissioning are simple. Water- or air-cooled Most centrifugal units use R 11 or R 12. The
condensers are employed; in large air-cooled rotational speeds required are greater than bipo-
plants, the air-cooled condensers may be very lar three-phase motors can supply, so builtin
large and, so separate placement of the water- gearing or frequency converters are employed.
chilling unit and the condenser (erected out- Even in large-capacity systems, semihermetic
doors) is common. Virtually all water chillers mounting of the drive motor and compressor is
with reciprocating compressors use R 22 as re- common. Both single-stage and two-stage units
frigerant. are built; the two-stage design with intermediate
Hermetic compressors are mainly employed expansion offers somewhat better energy econ-
at low refrigerating capacities up to ca. 50 kW, omy. Water chillers with centrifugal compres-
whereas semihermetic motor-driven compres- sors usually feature water cooling, because of
sors are used at higher capacities. Because air- their high capacity and the inflexibility of cen-
conditioning service means frequent part-load trifugal compressors with respect to varying dis-
operation, the refrigerating capacity is usually charge pressures. Whereas evaporators in sys-
distributed between several smaller compres- tems with reciprocating and screw compressors
sors, which can be turned on or off as needed. operate in direct-expansion mode, centrifugal
Larger units are also made with two separate re- systems employ flooded evaporators. Usually a
frigerant loops to enhance reliability. unit has just one compressor; part-load control is
Water chillers with screw compressors also exerted by inlet guide vanes, the less economical
use R 22 as their principal refrigerant. These bypass control being used only at cooling loads
units are distinguished by quiet operation and much lower than half the maximum capacity.
30 Refrigeration Technology
Units for chilling brine and other secondary 2.3. Cooling and Liquefaction of Gases
refrigerant liquids are essentially similar in de- [13], [21], [124–130]
sign to water chillers.
Very viscous or pasty liquids are chilled in Except in room air-conditioning systems (see
screw or scraped-pipe coolers, whose walls are Section 2.5), where air is used as secondary re-
held at the required low temperature by evap- frigerant, the purpose of cooling gases and gas
orating primary refrigerant or by a secondary mixtures is nearly always to bring about total
refrigerant. Such devices are frequently used in or fractional condensation. The fractional con-
the food and chemical industries. densation of gas mixtures effects separation; the
desired product may be either the residual gas
or the condensate.
2.2. Separation of Liquids by A number of industrially important gases are
Crystallization [13], [21], [118–123] produced by condensation from crude gases.
The condensation temperature depends on the
Recovering some products and separating ma- concentration of the gas in the mixture or on
terials from mixtures may require low process its partial pressure. The partial pressure can be
temperature, because of either the position of the raised by compressing the crude gas. The recov-
thermodynamic equilibrium (solubility curves) ery (the ratio of gas condensed to gas in the feed
or the temperature sensitivity of some sub- stream) and the concentration of the gas in the
stances. feed are the chief factors dictating the tempera-
For example, p-xylene is recovered from ture to which the crude gas must be cooled. Sub-
the mixture of ortho, meta, and para isomers sequent storage or transport of the condensed
by crystallization in a scraped-pipe heat ex- gas also determines the condensation temper-
changer (→ Xylenes); the process temperature ature. Chlorine, ammonia, sulfur dioxide, and
is ca. − 70 ◦ C. The xylene mixture flows inside carbon dioxide are examples of important prod-
a cylinder, while a stream of secondary refriger- ucts recovered by condensation at subambient
ant flows through the jacket. Scraper blades ro- temperatures.
tating inside the cylinder continuously remove Chlorine is recovered between + 20 and
the crystals precipitated on the wall and thus en- − 50 ◦ C, depending on the production pro-
sure constant heat-transfer conditions. Cold is cess. Chlorine gas from electrolysis of sodium
produced in cascade-type refrigerating systems. or potassium chloride contains, after prelimi-
Figure 39 is a flow sheet of a cascade unit nary treatment, 2 – 8 vol % air, hydrogen, car-
for chilling methane (secondary refrigerant) to bon dioxide, and carbon monoxide (→ Chlorine,
− 77 ◦ C. Both loops use three-stage centrifugal Chap. 11.). The choice for chlorine separation
compressors; the high-temperature loop oper- among the following three candidate processes
ates with R 12 and the low-temperature loop with depends on the chlorine content in the feed
R 13. stream and the desired recovery:
Another example is the dewaxing of crude
1) The crude gas inlet at 0.1 MPa is condensed
oils. Alkanes left in the crude oil after distilla-
at this pressure. Multistage refrigerating sys-
tion are crystallized by cooling to ca. −30 ◦ C.
tems may be needed (depending on the re-
The crystallizers, operating in several tempera-
covery) for evaporating temperatures at or
ture stages, are similar in design to those used
below −45 ◦ C.
for xylene separation. The refrigerating sys-
tems are usually multistage ammonia compres- 2) The crude gas is compressed to ca. 0.3 MPa
sor refrigerating systems or ammonia – water in nonlubricated reciprocating compressors
absorption refrigerating systems. Low-tempera- (or centrifugal compressors when the quan-
ture fractional crystallization is also used to sep- tity of gas is large). The increased partial
arate undesirable byproducts, especially when pressure enables condensation to be carried
an impurity has a boiling point close to that of out at evaporating temperatures of ca. − 15
the desired product. to − 20 ◦ C in the refrigerant loop.
Refrigeration Technology 31
Figure 39. Flow sheet of cascade centrifugal refrigerating system for xylene separation
a) Centrifugal compressor; b) Drive motor; c) Water – cooled condenser; d) Receiving vessel; e) Expansion vessel; f) R 12
evaporator – R 13 condenser; g) Methanol cooler; h) Vessel for thermal expansion of R 13; i) Expansion valve
– – – R 12 Loop; −→ R 13 loop
3) The crude gas is compressed to 1.0 – 1.5 MPa These processes are often linked. For example,
in several stages and can then be con- part of the chlorine gas from the compressed
densed with water; no refrigerating machine crude gas can be condensed with water; the re-
is needed. maining gas is then cooled to ca. −40 ◦ C and
another fraction condenses. The recovery, de-
pending on feed-gas composition, is >99 vol %.
Figure 40 is a flow sheet of a chlorine liq-
uefaction system. The crude gas is first treated
to remove water vapor and other gases, then led
through a precooler (b). Here, evaporating chlo-
rine cools the gas to ca. − 30 ◦ C so that, on sub-
sequent compression to ca. 0.4 MPa (c), the final
temperature does not exceed 80 ◦ C, the allowed
maximum on safety grounds. The compressed
gas is first cooled against water in a heat ex-
changer (d). It then goes to the first chlorine con-
denser (e), which is cooled by evaporating pri-
mary refrigerant. The condensed fraction flows
to a receiving vessel (g). The uncondensed frac-
tion continues to a second chlorine condenser
(f), where it is collected at a lower temperature
and led to the vessel.
Ammonia can be condensed from converter
gas in low-temperature refrigerating systems
(→ Ammonia). Evaporating temperatures of the
two-stage refrigeration process are between −50
Figure 40. Flow sheet of a chlorine liquefaction system
a) Crude gas inlet; b) Precooler; c) Chlorine gas compressor; and − 60 ◦ C.
d) Water-cooled chlorine gas cooler; e) First-stage chlorine In the separation of sulfur dioxide, the feed
condenser; f) Second-stage chlorine condenser; g) Vessel for gas is first compressed to ca. 0.5 MPa; up to
liquid chlorine; h) Expansion valve; i) Residual gas outlet; one half of the initial sulfur dioxide content is
j) Liquid chlorine outlet; k) High-stage compressor; l) Con-
denser; m) Medium-pressure vessel; n) Low-stage compres- recovered by condensation at − 40 ◦ C (→ Sulfur
sor; o) Expansion valve; p) Drive motor Dioxide). The gas is then expanded to ca.
−→ Chlorine loop; - - - - Refrigerant loop 0.1 MPa, the gas temperature drops to − 50 ◦ C,
and the remaining sulfur dioxide condenses.
32 Refrigeration Technology
Carbon dioxide for the beverage industry ing is ruled out for economic reasons. To min-
and for dry-ice production is purified by scrub- imize energy consumption, the dry cold gas
bing and adsorption, then condensed at low tem- can be used to precool the moist gas stream.
peratures and stored (→ Carbon Dioxide). Evap- Smaller units generally employ R 12 and R 22
orating temperatures are ca. − 30 to − 35 ◦ C. and thermostatically controlled expansion; for
For tank storage and transport, gases are liq- high capacities, ammonia and flooded operation
uefied and recondensed with cold-vapor refrig- are preferred. Finned cooling systems are used
eration processes, provided their standard boil- at standard pressure, whereas shell-and-tube ex-
ing points are not much lower than − 100 ◦ C. changers with smooth or shallow finned tubes
This group includes ethane, ethylene, propane, come into play at higher pressures. If dew points
propene, butane, butadiene, ammonia, and oth- < + 5 ◦ C are required, the water vapor collects
ers. Gases such as ethane and ethylene, which as frost on the heat-exchange surfaces. It must be
have critical pressures near or below ambient melted periodically by using electrical heating or
temperature, are liquefied in the evaporator of pressurized refrigerant vapor. This arrangement
a closed refrigerating system resembling a cas- calls for two evaporators connected in parallel
cade system. The process takes place at elevated and operated alternately. To avoid short cycle
pressure between − 50 and − 30 ◦ C. Figure 41 times, the greatest possible areas are provided
is a flow sheet of a plant that recondenses ethyl- on the gas side, so that the frost layer grows
ene for storage at atmospheric pressure. Higher slowly. Finned coolers best meet this require-
boiling substances are condensed either by com- ment; in shell-and-tube devices, the air is on the
pression and cooling against water or air, or in a shell side to prevent the tubes from becoming
closed refrigerating system at storage pressure. plugged with ice.
Recondensing units with gas compression re- In refrigeration systems, the use of conden-
present a possible application for nonlubricated sation to recover valuable feedstock and solvent
reciprocating compressors, because the product and to return them to the production process
must not be contaminated with lubricating oil. contributes to saving raw materials. To reduce
water and air pollution, increasingly lower tem-
peratures (down to − 70 ◦ C) are employed for
off-gas treatment and other purposes, in order
to remove even slight traces of foreign and haz-
ardous substances by recondensation.
2) A decentralized system, in which each cham- is generally lowered (storage under controlled
ber has its own refrigerating unit that may atmosphere).
have one or several compressors In cold-storage plants, flat construction is
favored because of better transport conditions,
In large cold-storage plants, slaughterhouses, even though it involves greater cold consump-
and breweries, the usual refrigerant is ammo- tion and higher land costs. Cold room chamber
nia. In mobile refrigerating systems and in food loading, depending on product and room height,
stores, R 22 or R 502 is preferred. Plants using is between 2 and 4 t/m2 of floor area. Proper in-
ammonia are centralized; the liquid refrigerant sulation of cold-storage rooms is important; the
flows by gravity or is pumped from a receiv- thickness of insulation is matched to the cham-
ing and separating tank on the low-pressure side ber temperature. The insulation must also incor-
to the individual chamber coolers. The air cool- porate a vapor barrier. The costs of insulating a
ers must be defrosted from time to time; this is cold-storage plant are often of the same order as
usually done by passing hot gas through the re- those for the entire refrigerating system.
frigerant piping (Fig. 43).
Refrigeration plants for cold rooms operating Freezing Processes. Freezing in liquid
on R 22 or R 502 can be centralized or decentral- brine (immersion freezing) is appropriate only
ized. The air cooler in such a unit is generally for foods in liquid-tight packages, such as
a thermostatically controlled direct-expansion canned frozen juices and shrink-wrapped poul-
evaporator. Decentralized machines are simpler try. Heat transfer is equally good everywhere on
in design, but require a much greater number the surface, especially for products with uneven
of refrigerant compressors than centralized sys- surfaces, so that freezing times are short. The
tems and also consume more energy in most product, such as packaged poultry, is moved by
cases. Whereas hot-gas defrosting is common conveyors through a tank containing the brine,
in centralized plants, electrical defrosting is of- a mixture of propylene glycol and water. After
ten used in decentralized systems with direct- leaving the tank, the product must be rinsed with
expansion evaporators. water to remove residual brine.
The products to be stored may be cooled or In contact freezing, small unit packages of
frozen in the chambers themselves, but special uniform thickness are frozen in plate-type equip-
equipment is usually employed for this purpose. ment. The plates are sometimes vertical but most
Such equipment lowers the product temperature often horizontal. A unit has up to 20 aluminum
much more rapidly (see following discussion of plates with integrally cast channels for refrig-
“ Freezing Processes”). erant or brine. The packages are laid on sheets
The coolers in a chamber are mounted either between the plates, and the plates are pressed
along the walls or below the ceiling. Air is of- against the fixed lowermost plate to produce
ten distributed by a system of ducts below the good contact between the cooled plates and the
ceiling, whereas it is commonly exhausted from product. After freezing is completed, the plates
the chamber without any special ductwork. The must be warmed briefly with a defrosting circuit
rate of air circulation depends on the size of the so that they can be separated.
room and the products stored there; an air speed Liquid, pulpy, or pasty material can be frozen
in the chamber of ca. of 0.5 m/s is often selected. at high rates in a scraped-surface freezer. The
Maintenance of a given humidity level in the air, product is fed onto a slowly rotating horizon-
usually between 85 and 95 % R.H., is very im- tal cylindrical surface cooled by primary refrig-
portant. If the humidity is too high, product shelf erant. The devices used for application and re-
life is shortened; if it is too low, the product will moval depend on the product. The form of the
dry out. Adequate sizing of the air-cooler sur- frozen product (powdered or flaked) depends on
faces keeps the humidity from dropping too low. the scraping apparatus and the starting material.
The accuracy of temperature and humidity con- The process is continuous and can be adapted
trol can be improved by using additional heating to prevailing requirements by varying the roller
and humidifying equipment. Other measures can speed, the evaporating temperature, and the coat-
extend the shelf life of foodstuffs. In fruit stor- ing thickness.
age, for example, the oxygen content of the air
Refrigeration Technology 35
Figure 43. Flow sheet of a refrigerating plant for cold rooms with pumped circulation of refrigerant and hot-gas defrosting ∗
a) Compressor; b) Condenser; c) Receiver; d) Separator; e) Refrigerant circulation pump; f) Air coolers; g) Expansion valve;
h) Switchover valve; i) Nonreturn valve
∗ The upper switchover valves are closed and the lower ones opened for cooling; the opposite is true for defrosting.
Cold-Blast Freezing. Freezing in air is suit- ing times, so that equipment can be made com-
able for products of any type, size, or form, pact and space requirements minimized. The air,
whether in the loose or packaged state; all frozen which must be cooled to ca. −30 ◦ C usually is
products are processed in this way. Many unit de- generally blown by fans through several finned-
signs and ratings are available. Achieving eco- tube evaporators. Pressure drops in the evapora-
nomical freezing rates with air requires greater tors and the fluidized bed must be considered.
temperature differences than with contact or im- The optimal bed depth is determined by the type
mersion freezing. Air temperatures of −30 to of product being frozen and is controlled through
− 50 ◦ C are used. air velocity and particle size. The evaporators
The product is conveyed through the freez- are defrosted automatically at intervals, without
ing tunnel on wheeled racks, belts, carousels, interrupting the overall process; the refrigerant,
or slide ways. In this continuous process, the usually R 22, is conveyed through the loop by
material enters the freezing unit through locks. pumping.
Multiple fans blow cold air countercurrently or
crosscurrently over the product at up to 7 m/s. Freezing with Boiling Liquids. Two freez-
The air is cooled against refrigerant evaporating ing processes involving boiling liquids have
at roughly −40 to − 55 ◦ C in finned-pipe heat found limited application. One employs liquid
exchangers. Freezing rates of ca. 1 – 3 cm/h can nitrogen; in the other, boiling R 12 is placed in
be attained. The residence or freezing time can direct contact with the product.
be controlled continuously by varying the belt Liquid nitrogen is sprayed onto the product
or chain speed or the feed rate. in a tunnel (Fig. 44). The product is precooled
The refrigerating equipment, usually two- by the cold gas produced by evaporation. Fans
stage, employs ammonia or R 22 as refrigerant. (h) circulate the gas around the product to pre-
Reciprocating and screw compressors are used. vent surface cracking, which would otherwise
A special form of cold-blast freezing is the occur if the uncooled product suddenly came in
fluidized-bed process; this is particularly suit- contact with liquid nitrogen (d), which boils at
able for free-flowing materials in the form of ca. − 190 ◦ C. To avoid excessive residence times
small lumps or fine grains, which are often en- and thus overlong tunnels, the large temperature
countered in food technology and the chemical difference between the surface and the interior
industry. of the product is not equalized in the tunnel. The
Cold air, blown upward through a metal pan product only remains in the tunnel as long as is
with a perforated bottom, suspends the product necessary to remove the heat needed to bring its
and flows around it. The good heat transfer (coef- average temperature down to its desired storage
ficients of 90 – 300 W m−2 K−1 for specific sur- temperature. Final temperature equalization bet-
faces of 0.25 – 1 m2 /kg) results in short freez- ween the core and the surface occurs later dur-
36 Refrigeration Technology
ing frozen storage. With 1 kg of liquid nitrogen suitable than coarse ones, because both the freez-
(1.245 L), some 330 kJ of heat can be removed ing time and, more important, the drying time are
from the product. The large temperature differ- shorter. The main difficulty is to remove water
ence and good heat transfer allow quick freez- vapor quickly from the interior of the product
ing and thus good product quality. Liquid carbon without causing local overheating of the exte-
dioxide can be used instead of liquid nitrogen. rior. To prevent oxidation during storage, freeze-
With R 12, the liquefied refrigerant is brought dried products are packaged under vacuum or in
into contact with the product, again in a tunnel. a nitrogen atmosphere.
The refrigerant evaporates at a temperature of ca. Cold is produced with multistage compres-
−30 ◦ C. In contrast to nitrogen, R 12 can easily sion and absorption machines. The energy con-
be recondensed with a condenser mounted in the sumption is high (10 to 15 times that required for
tunnel. The condenser is held at about −45 ◦ C by frozen-food production) because the required re-
a two-stage R 22 refrigerating unit. Withdraw- frigerating capacity is about eightfold and the
ing a given amount of heat requires much less evaporating temperatures are 10 – 20 K lower.
energy than with liquid nitrogen, because of the However, energy costs for three months’ storage
higher evaporating temperature. For economical of frozen food are roughly the same as for freeze
operation, refrigerant losses resulting from leaks drying. Nevertheless, the process is much more
in the tunnel and entrainment with product must expensive than frozen storage, so freeze drying
not exceed 1 – 2 wt % of product. of foods is not very important; it is used increas-
ingly for high-quality food and pharmaceutical
Freeze Drying (see also → Drying of Solid products.
Materials, Chap. 2.5.). Frozen-dried products
are of better quality than conventionally dried Ice Making. Ice, especially in finely divided
products because of reduced cell damage. form such as “tube” or “snow” ice, is used for
Freeze drying consists of the following steps: cooling products during transport (factory ships,
(1) freezing and cooling of the product to ca. refrigerator railroad cars, etc.). It also helps
−20 ◦ C, (2) evacuation to 50 – 100 Pa, (3) addi- avoid drying. In the chemical industry, finely di-
tion of heat of sublimation through heated plates, vided ice is used to absorb the heat of reaction.
and (4) condensation of water vapor on cold sur- Ice plays an important part in concrete construc-
faces (−40 to −60 ◦ C). The residual water con- tion work, where it removes the heat of setting.
tent is <2 %. Finely divided products are more
A further application is in cold storage. Large freezes; the rest goes to a receiver, where a float
amounts of ice are often stored in nuclear reac- controller admits fresh water to make up for the
tor buildings, so that radioactive steam can be amount frozen. About twice an hour, a timer cuts
completely condensed on the stored ice if the off the water flow and admits pressurized gas
steam pipes rupture. The storage of cold also al- from the condenser to start the defrosting pro-
lows better use of refrigerating capacity when cess. The ice released from the tubes is broken,
cold demand is variable. Ice is frozen on a re- then passes over a draining screen and through
frigerant evaporator (coiled-pipe or plate evap- a chute to a belt conveyor, which carries it to an
orator) located in an open, water-filled vessel. ice hopper or directly to the consumer. For a tube
The water, which is close to 0 ◦ C, serves mainly ice maker operating with ammonia (evaporating
as a secondary refrigerant in food production, temperature ca. − 12 ◦ C) and having a capacity
especially in dairies. When the demand for cold of ca. 400 kg/h, the specific cold consumption is
rises, the ice layer frozen on the evaporator coils ca. 780 kJ/kg of ice.
is melted, providing additional cooling capac- Flaked Ice. Ice in the form of thin flakes is
ity. Ice-storage units are used in air condition- made continuously in machines where freezing
ing, where ice produced with cheap nighttime takes place on the inside or outside surface of a
power is used to meet peak daytime loads. In this cylinder. Water is sprayed onto the inner surface
way, refrigerating systems can be made smaller, of the cylinder from a revolving distributor; the
power-connected load can be reduced, and en- cylinder is cooled from the outside by refrigerant
ergy costs can be lowered. evaporating in a jacket. The ice is removed by a
revolving scraper. In another design, the cylinder
is cooled from the inside by brine or evaporat-
ing refrigerant and rotates; the water feed and
scraping devices are stationary. Capacities for
this type of icemaking equipment are between 5
and 30 t/d.
Block Ice. Ice blocks are generally 1 m long
and weigh 12.5 or 25 kg each. Water is charged
into a large number of conical ice cells situated
in an open brine tank. Because the brine used as
secondary refrigerant is corrosive, the ice cells
are made of lead-coated sheet steel or stainless
steel. An agitator moves the brine to a vertical-
tube evaporator in the brine tank, where it is
chilled and then circulated around the ice cells.
At a brine temperature of ca. − 7 ◦ C, the freez-
ing time is ca. 8 h for a 12.5-kg block or 19 h for
a 25-kg block. After freezing, the ice cells are
hoisted out of the brine tank and briefly dipped
in warm water to release the ice blocks, which
Figure 45. Schematic of a tube ice maker are then easily displaced by tipping.
a) Shell-and-tube heat exchanger; b) Freezing tubes; c) Up- To shorten the freezing time, double-walled
per water tank; d) Tube-side space of exchanger; e) Lower
water tank; f) Water pump; g) Ice breaker; h) Ice chute;
ice cells are used in the “Rapid-Eis” freez-
i) Draining screen; j) Belt conveyor ing process. The refrigerant is evaporated in
the jacket space and freezing is accelerated by
Tube Ice. Ice in short tubular pieces (diame- means of an evaporator tube located inside the
ter ca. 40 mm, wall thickness 8 mm) is produced ice cell. To melt the ice and free it from the cell,
in tube ice makers. Figure 45 shows such a ma- the jacket and evaporator tube are connected to
chine. In a vertical shell-and-tube device, refrig- the condenser side of the refrigerating system.
erant evaporates in the shell-side space, while Drawbacks of this process are the high manu-
water from a tank flows through distributors and facturing costs and high mass of the ice cells,
down the inside of the tubes. Some of the water which must be designed for the refrigerant pres-
38 Refrigeration Technology
sure. The process can also operate with brine; units with reciprocating or screw compressors,
cell costs are then lower. Refrigerating systems using ammonia as primary refrigerant, are em-
for this process are single-stage ammonia ma- ployed.
chines with reciprocating compressors.
Dry Ice. The method most commonly em-
ployed for producing dry ice (solid carbon diox- 2.8. Air Refrigeration in Mining [13],
ide) consists of expanding pressurized liquid [163–165]
carbon dioxide to ambient pressure; the temper-
ature falls below the triple point and snowlike The temperature and humidity in mines often
carbon dioxide is obtained (→ Carbon Dioxide, become so high that ordinary ventilation with
Chap. 9.). Roughly a third of the liquid is trans- outside air is inadequate. Refrigeration equip-
formed to the solid state; the remaining gas is ment can be set up below ground in the shaft,
recycled. The carbon dioxide “snow” is molded or central cooling plants can be erected at the
into 12 – 100-kg blocks in hydraulic presses. surface to produce cold water, which is then led
Dry ice sublimes at − 78.9 ◦ C and has a heat to air coolers near the working face.
of sublimation of 573 kJ/kg. It is used chiefly in Refrigerating systems for underground in-
the transport of deep-frozen products and, to a stallation are compact, transportable, explosion-
minor extent, in laboratory chilling apparatus. proof units that cool air to ca. 18 – 20 ◦ C and de-
humidify it. The air is introduced into the venti-
lation tubing ca. 50 – 100 m before the road end-
2.7. Use of Cold in Construction [13], ing. The plants usually have watercooled con-
[21], [31], [159–162] densers and employ R 22 or R 12 as refrigerant.
Such machines can be driven by a compressed-
The heat of setting in concrete gravity dams
air motor instead of an electric motor.
ranges from 250 to 500 kJ/kg, depending on
the aggregate used and the cement : sand ra-
tio. This heat must be removed, especially in
thick dams, so that it does not buildup and 2.9. Artificially Cooled Skating Rinks
cause cracking. In postcooling, chilled water is [13], [21], [31], [166]
pumped through pipes inside the structure; com-
pact water-chilling plants are used for this pur- An artificially cooled skating rink consists of
pose. About 75 000 kJ of cold is required per cu- tubes embedded in a concrete slab that rests on
bic meter of concrete. In precooling, excessive a frost-proof base. The pipes are parallel, spaced
temperatures are prevented either by cooling the some distance apart, and ca. 25 – 30 mm below
aggregate and water before mixing or by adding the surface. A secondary refrigerant (usually
finely divided (flaked or tube-frozen) ice during brine), evaporating ammonia, or R 22 is pumped
mixing. Aggregate cooling is usually performed through the pipes. The surface temperature of the
with chilled water, but other methods employing ice over the entire rink surface must stay within
air chilled to − 20 ◦ C also offer some operational narrow limits; stringent requirements thus ap-
advantages. ply to both the supply of secondary or primary
When tunneling or similar construction work refrigerant and the control system.
requires shaft sinking in water-bearing ground,
the ground around the planned excavation is
stabilized by freezing. Double-walled pipes are 3. Heat Pumps [167–172]
driven into the soil. A secondary refrigerant
(usually brine) at − 20 to − 40 ◦ C flows down Heat pumps operate on the refrigeration prin-
the inner pipe and returns through the outer ciples described in Sections 1.1 and 1.2. The
space. The time required for freezing with these process is shifted toward higher temperatures,
parallel pipes depends on the type and size of the and the temperature of the rejected heat allows
excavation, the spacing of the pipes, and the tem- a medium to be heated for a given application.
perature of the secondary refrigerant; months
are often necessary. Transportable brine-cooling
Refrigeration Technology 39
11. Die Anwendung der Kälte in der 35. R. Plank: “Über den Idealprozeß von
Lebensmittelindustrie, vol. 10, 1960 in [1] Kältemaschinen bei Verbund-Kompression,”
12. Der gekühlte Raum, der Transport gekühlter Z. Gesamte Kälte Ind. 35 (1928) 17 – 24.
Lebensmittel und die Eiserzeugung, vol. 11, 36. K. Linge: “Der Einfluß des Ansaugzustands
1962 in [1] auf die volumetrische und die spezifische
13. Die Anwendung der Kälte in der Verfahrens- Kälteleistung,” Kältetechnik 8 (1956) 75 – 79.
und Klimatechnik, Biologie und Medizin, 37. K. Linge: “Eine vereinfachte Berechnung
Sicherheitsvorschriften, vol. 12, 1967 in [1] zweistufiger Kältemaschinen,” Z. Gesamte
14. Kältemaschinenregeln, 7th ed., C. F. Müller, Kälte Ind. 44 (1937) 181 – 185.
Karlsruhe 1981. 38. A. Rasi: “Der günstigste Zwischendruck für
15. W. Pohlmann, W. Maake, H. J. Eckert: zweistufige Kälteprozesse,” Ber. d. IX.
Taschenbuch für Kältetechniker, 17th ed., C. F. Internat. Kältekongr. 1 (Paris 1955)
Müller, Karlsruhe 1988. 3032 – 3039.
16. M. Bäckström, E. Emblik: Kältetechnik, 3rd 39. H. Lotz: “Fragen der Bemessung zweistufiger
ed., G. Braun, Karlsruhe 1965. Kälteanlagen mit Kolbenkompressoren,”
17. H. L. v. Cube (ed.): Lehrbuch der Kältetechnik, Kältetech. Klim. 20 (1968) 38 – 46.
vol. 1, Physik, Chemie, Kälteerzeugung, 40. K. Baumann, E. Blass: “Beitrag zur Ermittlung
Montage, C. F. Müller, Karlsruhe 1975. des optimalen Mitteldruckes bei zweistufigen
18. Regelung, Elektrotechnik, Kälteschutz, Kaltdampf-Verdichter-Kältemaschinen,”
Kälteanwendung, Lebensmitteltechnik, Kältetechnik 13 (1961) 210 – 216.
Schallschutz, Neue Einheiten,vol. 2 in [17] 41. H. Thumm: “Systemanalyse von
19. H. Jungnickel, R. Agsten, W. E. Kraus: Tieftemperatur-Kälteanlagen,” Kältetech.
Grundlagen der Kältetechnik, 2nd ed., Klim. 19 (1967) 36 – 43.
Technik, Berlin 1985. 42. D. J. Missinur, W. L. Holladay: “Cascade
20. International Institute of Refrigeration: Saving Refrigeration Systems,” ASHRAE J. 9 (1967)
of Energy in Refrigeration, Paris 1980. 70 – 73.
21. E. Emblik: Kälteanwendung, G. Braun, 43. G. Ahnefeld, M. Giebe, Chr. Kluge:
Karlsruhe 1971. “Erzeugung tiefer Temperaturen mit
22. H. G. Hirschberg: Kältemittel, C. F. Müller, Kaskadenkälteanlagen,” Luft Kältetech. 12
Karlsruhe 1966. (1976) 198 – 205.
23. M. Mörsel: Taschenbuch Kälteanlagen, 3rd 44. W. Gosney: “A Survey of the newer
ed., VEB Technik, 1970. Refrigerants,” Aust. Refrig. Air Cond. Heat 5
24. H. Löwer: Kältetechnik in Klimaanlagen, (1962) 113 – 117.
C. F. Müller, Karlsruhe 1980. 45. J. H. Anderson: Refrigerants for Centrifugal
25. H. Löwer: Klimatechnik, Springer, Berlin Water Cooling Systems, Aust. Refrig. Air
1968. Cond. Heat 10 (1967) 100 – 104.
26. L. Piatti: Kühlflüssigkeiten und Kälteträger, 46. H. O. Spauchus: “Development in
Sauerländer, Aarau, Frankfurt/M. 1968. refrigeration: technical advances and
27. H. Titze: Elemente des Apparatebaus, opportunities for the 1990 s,” Int. J. Refrig. 10
Grundlagen, Bauelemente, Apparate, 2nd ed., (1987) 263 – 270.
47. W. Frie: “Übersicht über die Berechnung der
Springer Berlin 1967.
Zustandsgrößen von Kältemitteln,” Brennst.
28. ASHRAE (Amer. Soc. of Heating, Refrig. and
Wärme Kraft 33 (1981) 320 – 324.
Air Cond. Eng.) Handb., Fundamentals, New
48. V. Chlumský: “Reciprocating and Rotary
York 1981.
Compressors,” Public of Tech. Lit., SNTL,
29. ASHRAE Handb., Systems, New York, 1980.
Prague 1965.
30. ASHRAE Handb., Equipment, New York,
49. K. Linge: “Der Liefergrad und der indizierte
1979.
Wirkungsgrad von Kältemaschinen,” Kälte
31. ASHRAE Handb., Applications, New York,
(Hamburg) 3 (1948) 116 – 123.
1982.
50. H. J. Müller: “Moderne Kälteverdichter der
32. Bull de l’Inst. Int. Froid, Paris.
Hubkolbenbauart,” Linde Ber. Tech. Wiss. 21
33. VDI-Wärmeatlas, 4th ed., Düsseldorf 1984.
(1966) 25 – 37.
34. K. Nesselmann: “Verfahren zur
51. H. Najork: “Entwicklungstendenzen auf dem
Kälteerzeugung unter −100 ◦ C,” Chem. Ing.
Gebiet der Kältemittelkompressoren,” Luft
Tech. 29 (1957) 198 – 200.
Kältetech. 1 (1965) 2 – 9.
Refrigeration Technology 41