Internal

Panel CPT-ID Non compliant depth


23 CPT-BPJV-PRE-VC-Int-P23-1 -12.4 mCD to -15.0 mCD
24 CPT-BPJV-Int-DC-MC-17
24 CPT-BPJV-PRE-VC-Int-P24-1
25 CPT-BPJV-Int-DC-MC-16
25 CPT-BPJV-PRE-VC-Int-P25-1
26 CPT-BPJV-Int-DC-MC-15
26 CPT-BPJV-PRE-VC-Int-P26-1
27 CPT-BPJV-PRE-VC-Int-P27-1 -13.2 mCD to -13.8 mCD
28 CPT-BPJV-Int-DC-MC-13B 3.9 mCD to 2.5 mCD and -4.2 mCD to -4.8 mCD
28 CPT-BPJV-PRE-VC-Int-P28-C -4.0 mCD to -4.5 mCD
29 CPT-BPJV-PRE-VC-Int-P29-1 -4.5 mCD to -5.2 mCD and -11.5 mCD to -14 mCD

30 CPT-BPJV-Int-DC-MC-11A -4.2 mCD to -6.0 mCD and -11 mCD to -11.6 mCD
30 CPT-BPJV-PRE-VC-Int-P30-1 -4.8 mCD to -6.0 mCD and -10.2 mCD to -10.8 mCD
31 CPT-BPJV-Int-DC-MC-10 -4.5 mCD to -5.1 mCD
31 CPT-BPJV-PRE-VC-Int-P31-1A -5.1 mCD to -6.0 mCD
32 CPT-BPJV-Int-DC-MC-9 -4.8 mCD to -5.9 mCD
32 CPT-BPJV-PRE-VC-Int-P32-1 -5.8 mCD to -8.2 mCD
33 CPT-BPJV-Int-DC-MC-8
33 CPT-BPJV-PRE-VC-Int-P33-1 -3.5 mCD to -5.5 mCD
34 CPT-BPJV-Int-DC-MC-7
34 CPT-BPJV-PRE-VC-Int-P34-1
35 CPT-BPJV-Int-DC-MC-6
35 CPT-BPJV-PRE-VC-Int-P35-1
36 CPT-BPJV-Int-DC-MC-5
36 CPT-BPJV-PRE-VC-Int-P36-1
38 CPT-BPJV-Int-DC-MC-3
39 CPT-BPJV-Int-DC-MC-2 -2.5 mCD to 1.9 mCD
40 CPT-BPJV-Int-DC-MC-1
Remark
Soft layer immediately above and below dredging line
No siltation issue
No siltation issue
No siltation issue
No siltation issue
No siltation issue
No siltation issue
Minimimal, do not expect negative response from SJC

Soft layer immediately above and below dredging line

Soft layer immediately below dredging line


Soft layer immediately below dredging line

Siltation in the middle of sandbody


Soft layer immediately above dredging line
Soft layer immediately above and below dredging line
No siltation issue
Minimimal, do not expect negative response from SJC
No siltation issue
No siltation issue
No siltation issue
No siltation issue
No siltation issue
No siltation issue
No siltation issue
No siltation issue
No siltation issue
Official
Panel
CPT-PRE-VC-DC-P23-1

CPT-PRE-VC-DC-P24-1

CPT-PRE-VC-DC-P25-1

CPT-PRE-VC-DC-P26-1
CPT-PRE-VC-DC-P27-1

CPT-PRE-VC-DC-P28-1
CPT-PRE-VC-DC-P29-1
Official
Non compliant depth

-11.5 mCD to -13.2 mCD


Documents
Remark AECOM Endorsement SJ Approval
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Soft layer immediately above and below dredging line Yes
Yes
Yes Yes
Yes Yes
No No

No No
No No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Action to note

Post CPT location shall be carefully chosen - internal test first

Post CPT location shall be carefully chosen - internal test first

If approval is obtained from SJC, post CPT location shall be carefully


chosen - internal test first

Additional internal CPT to be done before official one

Additional internal CPT to be done before official one

Additional internal CPT to be done before official one