Professional Documents
Culture Documents
548
STANDARD RECOMMENDED GUIDE FOR THE
SELECTION OF A LEAK TESTING METHOD
SE-432
549
SE-432 2001SECTIONV
550
ARTICLE 27 - LEAK TESTlNG STANDAKIIS SE-432
sensitive procedure involving fewer steps. As in the 4.1.1 Testing of Evacuated Systems (Tracer Probe
case with the other methods, a final inspection must Mode)-In the location of leaks in evacuated systems,
be conducted by means of a bubble test procedure to first determine if there is an inherent detector within
locate exceptionally large leaks. the system. This may be a pressure gage; preferably
a gage that is specific for some tracer gas which may
be used. If such a gage does not exist, the methods
to use in the order of increasing sensitivity are: sonic,
pressure change, gage response, high-voltage discharge,
alkali-ion diode leak halogen detector, infrared detector,
4. Leak Location and mass spectrometer.
4.1 Leak location can be subdivided into a tracer 4.1.2 Testing at Atmospheric Pressure (Detector
probe mode and a detector probe mode. The tracer Probe Mode)-In testing a system that is leaking into
probe procedure is used when the system is evacuated, atmosphere, the first consideration is whether or not
and the tracer gas comes from a probe located outside the leaking fluid may be used as a tracer. This will
the system. The detector probe mode is used when the always be the case when using either the sonic method
system is pressurized with tracer gas and testing is or the bubble-testing method. However, the tracer might
done at atmospheric pressure. Usually the tracer probe be of a composition that will also prove satisfactory
technique is more rapid because the gas reaches the for use with the other testing methods. In order of
detector at a higher concentration, despite any streaming increasing sensitivity these methods for leak location
effects, than it does with a detector probe which detects are: chemical testing, gage response, infrared gas ana-
tracer gas which is highly diluted by atmospheric gases. lyzer, mass spectrometer, and alkali-ion diode halogen
In the detector probe mode, a higher pressure differential detector.
across the system may be used, and therefore leaks of 4.1.2.1 When using liquid pen&rants, the pres-
a smaller conductance can be found. In using either sure may be atmospheric both inside and outside. Both
mode it is important that leak location be attempted surfaces must be accessible. Leaks are detected visually
only after the presence of a leak has been verified. by fluorescence or coloration.
551
SE-432 2001 SECTION V
552
STANDARD GUIDE FOR PREPARATION
OF A LEAK TESTING SPECIFICATION
SE-479
1. SWlpe 3. Terminology
1.1 This standard is intended as a guide. It enumerates 3.1 DeJnitions:
factors to be considered in preparing a definitive speci-
3.1.1 operational specijcation (OS) - a specifica-
fication for maximum permissible gas leakage of a
tion from which the others are derived. The specification
component, device, or system. The guide relates and
specifies and states the limits of the leakage rate of
provides examples of data for the preparation of leak
the fluid to be used for the product using criteria such
testing specifications. It is primarily applicable for use
as failure to operate, safety, or appearance.
in specifying halogen leak testing methods.
3.1.2 testing specification (TS) - a specification
1.2 Two types of specifications are described: for the detection, location, or measurement, or a combi-
nation thereof, of leakage. The operational fluid usually
1.2.1 Operational specifications (OS), and is not detectable with commercially available leak detec-
tors. The leak test must be performed with a suitable
1.2.2 Testing specifications (TS): test gas containing a tracer to which the detector is
sensitive. The pressure magnitude and pressure direction
may vary greatly from operational conditions. These
1.2.2.1 Total, and
and other factors are to he considered and evaluated
when the leak testing performed to the requirements
1.2.2.2 Each leak. of the TS is to result in a product that meets most of
the OS requirements. In addition, should a product be
1.3 This standard does not purport to address all tested with a detector or tracer probe from point to
of the safetyconcerns, if any, associated with its use. point, allowance should be made for the possibility of
It is the responsibility of the uw of this standard to two or more leaks, each causing less leakage than the
establish appropriate safetyand health practices and total leakage maximum, but adding up to an amount
determine the applicabiliry of regulatory limitations greater than allowed.
prior to use.
4.1.3 Any special restrictions or statement of facts vacuum-operated hot gas bypass capacity control valve,
that might prohibit the use of a particular type of leak and a sealed temperature control thermostat.
testing method.
6.2 OS, ReJrigerum Circuil - It is &&able that
4.1.4 The methods of the leakage specification the rechargeable portions of the system operate three
shall not be limited to any one particular method unless years before requiring additional refrigerant: for the
it is the only one suitable. Specific leak testing methods sealed parts, five years. Tests show that 6 oz of the
can be selected when careful consideration of the facts normal charge can be lost before serious operational
is outlined (refer to Guide E 432 or the other applicable inefficiency begins, and the neoprene connecting hoses
documents of Section 2). have a basic permeation rate of 1 oz/year. Inspection
of the system shows that the vacuum operator of the
capacity valve and the thermostat are not directly
connected to the refrigerant circuit, and can thus be
5. Significance and Use
considered separately.
5.1 For any product to be tested the geometrical 6.2.1 Calculations:
complexity will vary widely. However, the basic concept
Leakage to be detected = 6 oz (total loss) - 1 oz
of determining an operative leakage specification regard- x 3 years = 3 oz
less of geometries is much the same for all, whether Period = 3 years
it be simple, ordinary, or complex.
Rate = 3 oz/3 years = 1 oz/year. Rate (standard
5.2 The data required for writing the OS, which is units) = 1 oz/year x 1.8 x 10m4 (or 0.00018 = R-
total leakage (moles), time (s), and pressure difference 12 conversion factor) = 7.308 x low9 moles/s. See 6.6.3.
across the leak, are either available or can be determined Pressure - The maximum operating temperature of
by tests or measurements. the system will be 77°C at which temperature the
pressure of the refrigerant will be about 2.07 MPa.
5.3 A user who selects values to be used in a leakage Pressure difference = 2.07 MPa (internal) - 0.10 MPa
specification as a result of someone else having used (atmosphere) = 1.97 MPa.
the value or simply because of prestige reasons, may
find the value or values unsatisfactory for the product. 6.2.2 Therefore, the following would appear on
the appropriate documents: Leakage Specification (Oper-
5.4 A specification that is too restrictive may result ational): 3.6 x 10m5 MPa max at 1.97 MPa pressure
in excessive leak testing costs. A specification that is difference (7.308 x 10e9 moles/s excluding hose perme-
not restrictive enough may result in premature product ation).
failure, or increased warranty costs, or both.
6.3 T’S, Refrigerant Circuif:
5.5 A typical illustration for determining a leakage
6.3.1 For a unit to be tested at the OS level,
specification, using the complex geometry of a refriger-
any inaccuracies in the test could cause possible unit
ant system for an example, will be used throughout
acceptance when in fact the unit may leak in excess
this recommended guide. It is well to point out that
of the amount allowed. Most testing conditions cannot
the user should real& that the values and test methods
duplicate operating conditions. Should a point-by-point
selected do not necessarily represent the best or typical
probing technique be used, a number of smaller leaks
ones for this application.
may allow a total leakage in excess of the value
specified.
6.3.2 In addition, some portions of the system
6. Procedure
may be purchased as a completed operative component.
6.1 The example that follows is to be construed as Their potential contribution to the total system leakage
applicable to the equipment and testing method cited, must be limited. It is because of the requirements of
and is not to be construed as setting up mandatory the testing specification that these and other factors are
leakage rates for any other equipment or method of considered, and that required leak testing at levels to
testing. The example used to illustrate the use of this ensure acceptable quality levels in the final product is
guide is as follows: An automotive air-conditioning made with the consideration for a lesser testing cost.
system using Refrigerant-12 (R-12, dichlorodifluoro- Often it is necessiuy to divide the leakage allowance
methane) and consisting of a compressor, condensing equitably among various components, taking into ac-
coil, thermostatic expansion valve, evaporating coil, count the statistical probability of the largest allowable
554
ARTICLE 27 .-~-LEAK TESTING STANDARDS SE-479
leakage occurring in a number of a given set of which has a strong tendency to have porosities that
components. leak in the range of 4.06 x 10.” moles/s. For this
reason, the TS total will be divided by five for this
6.3.2.1 Division of Leakage Allowance Among
item, and by three for the others, that is, a factor of
System Components - Assume in the previous example
0.2 and 0.3 respectively.
that the compressor, condensing and evaporating coils,
the expansion valve, capacity control valve, and sealed 6.6 Factor of Safety for Test verw~ Operating Condi-
thermostat all have to be considered. Also assume that tions:
the compressor and evaporating coil will both be tested
6.6.1 Pressure - As a recommendation, the leak-
separately before assembly into the system, as each
age is assumed to be proportional to the difference of
has a number of fabricated joints more prone to leakage
the squares of the pressures on each side of the leak.
than the condensing coil. The condensing coil, consid-
However, for this example, it is assumed that a 2.76
ered a continuous length of tubing, can be tested at
MPa pressure difference, high pressure internal, is
the final system test. All components except the themm-
needed. This would allow combining the leak test with
stat make up some portion of the refrigerant circuit.
the burst test which is fixed at 2.86 MPa, absolute
How then should the leakage allowance be divided
internal - 0.10 MPa, absolute external = 2.76 MPa.
among them? The usually equitable way is to make
This pressure will possibly reveal leaks that can only
the division on the basis of the number of joints in
develop with higher stress. With the operating condition
each, considering 25 mm of seam as one ‘tjoint.” A
at 2.07 MPa, gage max, greater leakage can be expected
tabulation example on this basis follows:
at the higher test pressure. Calculate the Factor of
No. of % of Safety as follows:
Joints TOtal
Compressor 36 28 Factor of Safety = (Pz2- P,2)l(P~2- PI’)
Condensing coil 78 60 = (2.762 - 0.12)/(2.072 - 0.12) = 1.8
Expansion 7 5
Capacity control valve 9 - 7 where:
Tatal 13” 100
P, = pressure, atmospheric,
6.4 Factor of Safety for Leak Testing Accuracy - P2 = high pressure (internal), and
When establishing the data for the factor of safety for P3 = pressure, operating.
leak testing accuracy and when performed by various Therefore, a factor of 1.8 can be applied to the opera-
people “sing different equipment, facilities, or operating tional specification.
standards, the resulting data usually will vary tremen-
dously. Results of a round-robin test conducted by 6.6.2 Test Gas -Except at high ambient tempera-
ASTM resulted in a spread of the test data of about tures, most refrigerant gases normally used in a system
one decade. This value is considered valid for leak will liquefy before the test pressure is reached. Nonethe-
tests “sing procedures and equipment described in less, other gases or a mixture of gases will be required
Section 2. Therefore any operational specification may for leak testing. The more suitable gases, such as
apply a factor of ‘/3 or 0.3. helium, nitrogen, air, etc., have a viscosity of about 1.9
x 10e4 P, compared to 1.2 x 10e4 for most halogenated
6.5 Factor of S&y for Number of Leaks per Sys-
refrigerants, compared to 1 x 10’ for water and 1 x
tem - When a “nit or device has a number of points IO’ for lubricating oils. The leakage of a fluid is
that may leak, the leak test is to be performed by
inversely proportional to its viscosity. Therefore, the
point-to-point probing. There is a possibility that the
correction for test fluid is extremely important, particu-
sum of all leaks smaller than the specification total
larly when liquids are involved. In this example a
may add up to a” amount in excess of it. However, factor of 1.2 x 10e4 divided by 1.9 x 10e4 = 0.6 will
this is dependent upon the number of leak possibilities be used.
or on whether there is any distortion of the normal
leak distribution curve, which covers many decades of 6.6.3 Test Spec@~rions - From an operational
sizes. The factor assigned here may depend upon a specification of 7.308 x low9 moles/s (excluding hoses)
judgment of the probability of such an event occurring, the testing specification for the completed system is
the degree of confidence needed in the leak test, and derived (Note Appendix Table Xl, Nos. 14). Test
the safety factor that can be afforded. In this example, specification, total = 1.8 x 10.’ x 0.3 (equipment
assume that the condensing coil is of welded aluminum accuracy) x 1.8 (gas pressure) x 0.6 (gas viscosity) =
555
SE-479 2001 SECTION V
1.8 x 10.’ x 0.32 = 5.8 x 10m6.Round the coeflicient Using factors previously discussed, the specifications
to the nearest whole number. The total for all leaks may be tabulated as follows:
will be: “Leakage specification, testing, total: 24.36 x
IO-‘” moles/s max at 2.76 MPa pressure differential, Maximum Lenkage at 0.48 MPa Differential, Pressure tnternat
(Note Appendix Table Xl, Nos. 9-13)
pressure internal.” Therefore, each leak = 24.36 x
10.” x 0.3 (selected by consideration of factors outlined Maximum
in 6.5) = 7.308 x 10.” moles/s. Rounded, each leak Type of Leakage,
will be: “Leakage specification, testing, each leak: 8.12 Specification -Seller USeI moles/s
x IO-” moles/s at 2.76 MPa pressure differential, Operational x 5.3 x IO@’
pressure internal.” Testing, tot*, x 16.24 x 1O-‘4
Testing, total X 4.06 x IO-”
6.6.4 Testing Spec@ation, Purchased Compo- Testing, each leak X 12.18 Y 10-14
Testing, each leak 4.06 x IO-”
nents - When purchased components will be subject
to receiving inspection for compliance with the leakage Note that the factors used are larger than normal, as
specification supplied to the vendor, these two specifica- the sensitivity limit for the detection of halogen has
tions should not he the same: otherwise, parts tested been approached. (See Practice E 427.)
at normal accuracies by the vendor may he rejected
by the customer. Therefore, a typical factor of about 6.6.4.2 Control Valve - There are two separate
‘/o (0.1) should be applied to the vendor’s specification. leakages to consider for this component: the refrigerant
side and the operational side. Applying appropriate
6.6.4.1 Expansion Valve - This component has factors, the specifications may be tabulated as follows:
two leakage requirements. The part common with the Refrigerant Circuit Side Specijications:
refrigerant system must meet its requirements; the sealed
operator assembly, a diaphragm, capillary tube, and bulb Maximum Leakage at 2.76 MPa Differential, Pressure Internal
filled with R-12 gas has its own oper&ion specification. (Note Appendix Table XI, Nos. 14-17)
(1J Refrigerant System Side Spec@cations: Test Speci-
Maximum
fication, Total - In the tabulation example in 6.3.2.1 Type of Leakage.
an allowance of 5% for the expansion valve cornpart- Specification Seller “SU moles/s
ment was established. Applying this to the similar Testing, total 8.12 Y lo-‘0
system specification: 7.308 x 10m9 x 0.05 = 36.54 x Testing. total X 8.12 x lo-”
lo-” moles/s. (This allowance might be increased on Testing. each leak x 24.36 x IO-”
Testing, each leak X 24.36 x IO-”
a statistical basis if desired.) Thus the specification for
this component can be tabulated as follows: Calculation, testing, total: 7.308 x 10m9x 0.09 (see the
tabulation example in 6.3.2.1) = 6.5 x 10“’ moles/s.
Maximum Leakage at 2.76 MPa Differential, Pressure Internal Operator Specijications:
(Note Appendix Table Xl, Nos. 5-8)
Maximum Leakage at 0.10 MPa Differential, Pressure External
Maximum (Note Appendix Table Xl, Nos. 18-20)
Type of Leakage,
Specification Maximum
-Seller -User moles/s
Type of Leakage,
Testing, total x 36.54 x IO-” Specification Seller user moles/s
Testing, total x 36.54 x IO-”
Testing, each leak X 12.18 x lo-” Testing, total X 4.06 x W5
Testing, each teats x 12.18 Y lo-‘? Testing, total X 4.06 x IO-’
Observe that a factor of ‘/3 has been applied for probe As this component is nonrepairable, and because the
testing versus total leakage testing. diaphragm is accessible only through parts on each
(2) Operator Assembly Specifications - This is an side of its enclosure, probe testing to locate points of
independent system, and the operational specification leakage is neither possible nor desirable.
must be established as before. Make the following
6.6.4.3 Thermostat - No parts are in contact
calculations:
Maximum loss of R-12 before malfunction: with the refrigerant circuit. The unit components usually
2 standard cm’
Time limif: 5 years arc sealed in an inert atmosphere at one atmosphere
Pressure (internal): 0.6 MPa pressure, to prevent contaminants and oxidation. It is
preferred to specify the tracer gas to be used, in order
Operational specification = Z/(5 x 3.15 x 10’) = 5.3 x IO-” moles/s to control the electrical characteristics and contact life.
556
ARTICLE 27 - I,EAK TESTING STANDARDS SE-479
As a rule, probing tests are difficult and not necessa~, 7. Summary of Requirements
as defective units will be scrapped. Test data have 7.1 A leakage specification should contain all the
revealed that a seal that leaks no more than 4.06 x requirements for the qualifying procedure. It shall
lo-” moles/s at 0.10 MPa differential will give adequate specify:
protection at the normally small operating differentials.
7.1.1 Mass flow, preferably in mol/s,
7.1.2 Time, preferably in seconds,
Maximum Leakage at 0.10 MPa Differential, Pressure Internal 7.1.3 Pressure differential, preferably in malls,
(Note Appendix Table Xl, Nos. 21-23)
7.1.4 Direction of pressure differential,
7.1.5 Other restrictions only when necessary, and
Maximum
Type of Leakage, 7.1.6 Intended use of specifications:
Specification setter user ITlOldS
7.1.6.1 Operational.
Operational 4.06 x IO-”
Testing, total x 12.18 x d3” 7.1.6.2 Testing, total.
Testing. total X 12.18 x 10-14”
7.1.6.3 Testing, each leak (optional).
7.1.6.4 Testing, total, seller (optional).
“Pill to be 10% helium in dry nitrogen. This value pertains to
helium leakage only. 7.1.6.5 Testing, each leak, seller (optional).
APPENDIX
(Nonmandatory Information)
X1.1 It should be noted that furnished specifications spectrometer with 100% helium external test gas. He
in no way prevent the manufacturer or seller from computes the expected difference in leak rate:
making his own interim leak tests. It should be deter-
mined, however, that such tests do not prejudice the Factor of Safety = (P; - P2)/(P4’ - I’:)
required tests. For example, a preliminary bubble test = (0.P - 02)/(0.57* - 0.12) = 0.03
underwater might temporarily plug small leaks. As an
example, consider line 11, Table Xl, “Expansion valve Therefore he will get a value of 1 x 10.‘” x 0.03 =
operator assembly, seller, max leakage 1 x 10e9 standard 12.18 x lo-l6 moles/s. However, in leaks of this size,
cm3/s at 70 psi (0.48 MPa) differential, pressure inter- helium leaks about 7 times faster than R-12. Therefore,
nal.” The seller wishes to test the assembly before he may desire to use the specification value of 3 x
fitting and sealing. He elects to use the helium mass 1OV’2x 7 = 8.12 x lo-l5 moles/s as a preliminary test.
557