You are on page 1of 1

USE PROSET FIRESTOP PENETRATORS, OR EQUAL FOR ALL PIPE PENETRATIONS

AND FIXTURE OPENINGS THROUGH FIRE RATED FLOORS AND WALLS.


BUILDING CODE REQUIRED SYSTEM NUMBERS ARE LISTED & DETAILED BELOW.
NOTE: PLUMBING CONTRACTOR SHALL COORDINATE WITH STRUCTURAL SYSTEM
PLUMBING - PLASTIC DWV PLUMBING - CAST IRON DWV FOR ALL HOLES THROUGH SLABS. THIS INCLUDES LEAVE OUT FOR BATHTUBS.
PVC - ABS CPVC - CONDENSATE CAST IRON NO-HUB - WASTE - VENT - CONDENSATE

TYPE OF FIRE RATED CONSTRUCTION TYPE OF FIRE RATED CONSTRUCTION


TYPE OF PLASTIC TYPE OF CAST IRON
PENETRATION PENETRATION

"A-4" "B-4" "B-4" "C-4" "C-1" "B-1"


U.L. NO. U.L. NO.
F-A-1003 F-B-2002 MASONRY
WALL

"A-1"
CORRUGATED
POURED
METAL INPLACE U.L. NO.
DECK CONCRETE W-L-1038

"B-1"

U.L. NO.
C-AJ-1146
U.L. NO. U.L. NO. U.L. NO. U.L. NO.
C-AJ-1106 C-AJ-1146 F-A-2006 C-AJ-1146
"C-1"

U.L. NO.
"A-1" "A-2" "B-1" "B-2" "B-1" "CA-1" "C-2" "C-1" W-J-2010

U.L. NO. U.L. NO. U.L. NO. U.L. NO. U.L. NO. U.L. NO. "A-2"
C-AJ-1106 C-AJ-2039 C-AJ-1146 C-AJ-1146 F-B-1003 F-A-2009

U.L. NO.
W-L-1038

POURED "A-3"
INPLACE
CONCRETE
U.L. NO.
W-L-1038

U.L. NO. U.L. NO.


SLEEVES AND FIRESTOPPING "CA"
F-A-2007 F-A-2006

USE PROSET "FIRESTOP PENETRATORS". U.L. CLASSIFIED IN THE BUILDING MATERIALS DIRECTORY, TESTED BY ASTM E-814.
USE FOR ALL APPLICABLE PIPE PENETRATIONS THROUGH FIRE RATED FLOORS, WALLS OR FLOOR/CEILING ASSEMBLIES U.L. NO.
IN ACCORDANCE WITH THE MANUF. INSTRUCTIONS. W-J-2010
GYPSUM
A. SYSTEM "A" PENETRATORS FOR WATER LINES, HEATING AND COOLING LINES, FIRE STANDPIPE AND SPRINKLER LINES, TEMPERATURE
WALL
CONTROL, ACID WASTE GLASS PIPE AND ELECTRIC AND COMMUNICATION CONDUIT PENETRATING FLOORS OR WALLS.
B. SYSTEM "B" PENETRATORS FOR CAST IRON DWV PIPES FOR STACKS AND DRAINS PENETRATING FLOORS OR WALLS.
C. SYSTEM "C" PENETRATORS FOR PLASTIC DWV PIPES FOR STACKS AND DRAINS PENETRATING FLOORS OR WALLS.
PLUMBING - WATER & GAS CA. SYSTEM "CA" PENETRATORS FOR POLYPROPYLENE ACID WASTE PIPE PENETRATING FLOORS OR WALLS.

COPPER - STEEL - CPVC - POLYBUTYLENE 1. CAST-IN-COUPLING PENETRATORS FOR POURED-IN-PLACE CONCRETE ON STEEL OR WOOD FORMS IN FLOORS OR WALLS.
2. CORED HOLE COUPLING PENETRATORS FOR CORED HOLES THROUGH PRECAST OR EXISTING CONCRETE IN FLOORS OR WALLS.
3. SPLIT WALL SLEEVE PENETRATORS FOR PIPES PASSING THROUGH GYPSUM WALLS OR FLOOR / CEILING ASSEMBLIES.
TYPE OF FIRE RATED CONSTRUCTION 4. SLIP FLANGE CM COUPLING FOR POURED-IN-PLACE CONCRETE ON CORRUGATED METAL DECK.
TYPE OF WATER & GAS
PENETRATION

FIRESTOP CONCRETE PENETRATOR DETAILS