Lightning Protection Calculation
Lightning Protection Calculation
Width of Building L = 36 m
Depth of building W = 28 m
Height of building H = 23 m
23.00
(L X W) + 2 x (L x H) +
= 2 sqm
Collection Area Ac 2 x (W+H) + pH
= 5613.90 sqm
ELEVATION
Probable Number of strikes to -6
P = Ac x Ng x 10
the structure per year
Annual
Isokeronic Level = 73
thunderstorm days
Lightning flash density (Clause Lightning flashes /
Ng = 6.9
8.1.2 and fig1 IS: 2309 sqkm / year
Lightning flashes /
P = 0.038735927
36.00
year
Weighting Factors
Use of Structure A = 1 Table 1, 1A 28.00
Type of Construction B = 1 Table 1, B
Consequential Effects C = 1 Table 1, 1C PLAN
Degree of Isolation D = 1 Table 1, 1D
Type of Country E = 0.3 Table 1, 1E
= AxBxCxDxE
Overall weightage
= 0.3
= PxAxBxCxDxE
Overall Risk Factor
= 1.162E-02
Perimeter = 128 m
No of Down Conductors = 5 Nos
No of down conductors to be
considered (minimum of the above = 5 Nos
two)
Width of Building L = 40 m
Depth of building W = 15 m
Height of building H = 12 m
12.00
(L X W) + 2 x (L x H) +
= 2 sqm
Collection Area Ac 2 x (W+H) + pH
= 2372.39 sqm
ELEVATION
Probable Number of strikes to -6
P = Ac x Ng x 10
the structure per year
Annual
Isokeronic Level = 73
thunderstorm days
Lightning flash density (Clause Lightning flashes /
Ng = 6.9
8.1.2 and fig1 IS: 2309 sqkm / year
Lightning flashes /
P = 0.016369486
40.00
year
Weighting Factors
Use of Structure A = 1 Table 1, 1A 15.00
Type of Construction B = 1 Table 1, B
Consequential Effects C = 1 Table 1, 1C PLAN
Degree of Isolation D = 1 Table 1, 1D
Type of Country E = 0.3 Table 1, 1E
= AxBxCxDxE
Overall weightage
= 0.3
= PxAxBxCxDxE
Overall Risk Factor
= 4.911E-03
Perimeter = 110 m
No of Down Conductors = 4 Nos
No of down conductors to be
considered (minimum of the above = 3 Nos
two)
Width of Building L = 33 m
Depth of building W = 20 m
Height of building H = 50 m
50.00
(L X W) + 2 x (L x H) +
= 2 sqm
Collection Area Ac 2 x (W+H) + pH
= 13813.98 sqm
ELEVATION
Probable Number of strikes to -6
P = Ac x Ng x 10
the structure per year
Annual
Isokeronic Level = 73
thunderstorm days
Lightning flash density (Clause Lightning flashes /
Ng = 6.9
8.1.2 and fig1 IS: 2309 sqkm / year
Lightning flashes /
P = 0.095316473
33.00
year
Weighting Factors
Use of Structure A = 1 Table 1, 1A 20.00
Type of Construction B = 0.2 Table 1, B
Consequential Effects C = 1 Table 1, 1C PLAN
Degree of Isolation D = 1 Table 1, 1D
Type of Country E = 0.3 Table 1, 1E
= AxBxCxDxE
Overall weightage
= 0.06
= PxAxBxCxDxE
Overall Risk Factor
= 5.719E-03
Perimeter = 106 m
No of Down Conductors = 4 Nos
No of down conductors to be
considered (minimum of the above = 4 Nos
two)