You are on page 1of 17

Release Control Fire Alarm Systems

UL, ULC, CSFM Listed; FM Approved; 4004R Suppression Releasing Panel for Automatic
MEA (NYC) Acceptance* Extinguishing, Deluge and Preaction Sprinkler Control

Features Agent discharge path

Fire alarm control panel designed specifically for


suppression release operation with: Actuator
Agent
Actuator
source
 Four initiating device circuits (IDCs) circuit

 Two notification appliance circuits (NACs) Coil


 Two releasing appliance circuits (RACs)
COIL SUPERVISION MODULE (2 AMP) 2081-9046
RED YEL

supervisory
INSTALLATION INSTRUCTIONS 574-437 REV
NAC+ MAINTAIN 1/4" SEPARATION
BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER S
LIMITED (YEL/BLK) WIRING
DATE CODE: 519-958
BLK
NAC-
BLK SIMPLEX T IME RECORDER CO. GARDNER MA. USA

module
 Two special purpose monitor inputs (SPMs) that accept
manual release request and manual abort request for
Agent Release systems, and waterflow and supervisory NORMAL

Maintenance Switch
0

for Preaction or Deluge systems


1
DISC./
DISABLE

FIRE SUPPRESSION
DISCONNECT / DISABLE

 Three auxiliary relays with selectable functions


 Easily selected activity timing options SPM 1
FIRE SUPPRESSION
RAC 1 RAC 2

Suppression release operation includes:


SYSTEM ABORT

PUSH AND HOLD


NAC 1
 Automatic extinguishing release
SPM 2
 Deluge and preaction sprinkler system release Alarm

Trouble
Zone 1
Manual Release

Zone 5 Trouble

IDC 1
Alarm Manual Release

 Dual or single hazard area protection


Trouble
Zone 2 Zone 6 Trouble
CAUTION
Alarm NAC 1 Trouble DISCONNECT

Trouble
Zone 3 NAC 2 Trouble

Alarm RAC 1 Trouble

Trouble
Zone 4 RAC 2 Trouble
BATTERY AND
A. C. POWER
Alarm Silenced Agent Released BEFORE
SERVICING

 Combined agent release and preaction operation**


Supervisory Earth Fault

System Trouble Abort Active

AC Power Relay Disconnect

 IDCs are selectable for cross-zoning or for activation


IDCs 2, 3, and 4 NAC 2
from a single detection input
 Short circuit RAC supervision 4004R Suppression Release Panel
 Compatible with Listed/Approved 24 VDC or
4004R Suppression Release Panel
2, 12 VDC series connected actuators One-Line System Reference Drawing
Audible Escalation of Events:
 Single Audible Appliance Tone: Stage 1 activates Introduction (Continued)
Temporal or 20 bpm March Time pattern; Stage 2 Flexible I/O Capabilities. Four IDCs allow for either
activates 120 bpm March Time pattern to indicate four separately monitored zones or two, cross-zoned
release timer active; Release activates On Steady to connections. Two SPMs allow dedicated manual inputs for
indicate release timer expired and actuator is activated release or abort; for waterflow and supervisory, or
 Dual Audible Appliance Control** (Single Hazard): release/abort and pressure, depending on system type. Two
RAC 2 provides a third NAC for dedicated Stage 1 Bell releasing appliance circuits (RACs) supervise to the
control; NACs 1 & 2 indicate release as On Steady actuator coils and activate the actuators when required. The
Operator interface provides: two NACs and the three panel auxiliary relays provide
 Status LEDs per circuit for Alarm, Trouble, and status condition information.
Supervisory (where appropriate) Easy Program Selections. The operator panel has a
 Acknowledge, Alarm Silence, and System Reset program mode that allows selection of panel operation
 Operating mode selection and timer selections when in type and detailed operating selections using an easily
programming mode selected sequential programming operation.
Related system components: History Log. The last 50 events are stored in
 Coil supervision module 2081-9046, one per RAC non-volatile memory. This information is accessed by
 Maintenance Switch, one per RAC connecting a technician’s computer to the service port
 Abort Switch which is also used to set the date and time.
Listed to Panel Feature Description
 UL Standard 864 and ULC Standard S527
Operator Panel. The operator panel has alarm and
Introduction trouble status indicating LEDs for each input and output,
visible through the locking cabinet door (refer to diagram
Dedicated for Suppression Release. 4004R on page 4). Unlocking the door provides access to the
Suppression Release Panels provide conventional fire alarm Acknowledge, Alarm Silence, and System Reset
control circuits and are equipped with the features required pushbutton switches.
for a wide variety of single or dual hazard suppression release
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
applications. Capabilities include automatic extinguishing Section 13144.1 of the California Health and Safety Code. See CSFM Listing
agent release and deluge and preaction sprinkler control. 7165-0026:314 for allowable values and/or conditions concerning material presented in
this document. Additional listings may be applicable; contact your local Simplex® product
** Requires Software Revision 4.01 or higher. supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are
the property of Tyco Fire Protection Products Westminster.

S4004-0002-6 12/2015
Panel Feature Description (Continued) Two Class B Releasing Appliance Circuits (RACs). Rated
2 A each, these circuits are dedicated to operating release
(Refer to specifications on page 6 for more information.) control actuators. RAC cutout timing is selectable as no
Four Class B IDCs provide coverage for either two cutout, 45 seconds, or 1, 3, 3.5, 4, 5, 6, 7, 21, 25, 34, 44,
cross-zoned areas or four separately zoned areas. IDCs are or 64 minutes. For bell/horn/strobe single hazard
capable of supporting up to 30 Simplex current-limited applications, RAC 2 functions as a third NAC (NAC 3).
smoke detectors or electronic heat detectors (see list on Auxiliary Power Output. Two sets of output terminals are
page 2) as well as manual stations and other compatible provided, one for continuous operation and the other for
contact closure initiating devices. IDCs are capable of resettable operation, rated for 750 mA combined.
Class A operation with an optional adapter module and can Resettable terminals are provided for 4-wire smoke
be programmed as Style C (short or open initiates a trouble) detector power.
for use with current limited devices only. Single hazard agent Standard Panel Auxiliary Relay Outputs. Three relay
release applications monitor pressure switches with IDC 3 outputs are available, selectable as normally open or
and tamper switches with IDC 4. normally closed, rated 2 A @ 30 VDC, 0.35 p.f. inductive:
Two Class B Special Purpose Monitoring Circuits (SPMs)
Aux Relay 1 (Trouble) is energized when Normal and is
are dedicated for manual release or abort, waterflow and de-energized with a common Trouble condition.
supervisory, or release/abort and pressure, depending on
system type. Inputs are normally open switches. An abort Aux Relays 2 and 3 respond differently depending on the
switch stops release while activated and upon deactivation, system type and whether single or dual hazard. Typical
the release operation occurs after a selectable time delay. functions are:
Manual release inputs override abort switches and activate For Single Hazard Operation, Aux Relay 2 is the
the release after selectable delays of from 0 to 30 seconds in common Alarm relay. Aux Relay 3 can be selected to
5 second increments. For Dual Hazard applications, current indicate pre-discharge (release time delay started),
limited abort operation is required. SPMs are programmable common supervisory, waterflow, or pressure switch relay,
as Style C and capable of Class A operation with the optional depending on the system type.
adapter module. For Dual Hazard Operation, Aux Relay 2 is for Hazard
Two Class B NACs are provided for reverse polarity, Area 1 common Alarm; Aux Relay 3 is for Hazard Area 2
notification appliance operation, each rated 2 A. Class A common Alarm.
operation is available with the optional adapter module. Power Supply and Battery Charger. During alarm, the
NAC operation is selectable per application. Synchronized power supply provides 3 A at 25.5 VDC, filtered and
strobe operation requires a separate 4905 Series Strobe regulated. The temperature compensated battery charger
Synchronization Module (see product selection below), and provides 27.5 VDC for charging batteries up to 12.7 Ah,
a continuous, steady-on (non-coded) input from the NAC. suitable for up to 90 hour standby and 10 minutes of alarm.
A 4081 Series external battery cabinet with charger can be
used for more battery backup (see battery selection below).
Product Selection
Release Control Panels
Model Color Listings Description
4004-9301 Beige UL, ULC, CSFM, & FM Basic Releasing Panel; operates with AC input of: 120/220/230/240 VAC,
50/60 Hz (auto-select); includes: four IDCs, two NACs, two SPMs, two RACs,
UL, ULC, CSFM, FM, & 3 auxiliary relays, 3 A power supply with battery charger, and NEMA 1/IP30 rated
4004-9302 Red
MEA (NYC) cabinet and door
Expansion Modules
Model Description Reference
Auxiliary Relay Module; four dual contact relays selectable as N.O. or N.C.; rated 7 A Select
4004-9860 Two maximum
@ 120 VAC resistive, 5 A @ 30 VDC, 0.35 p.f. inductive; unsupervised contacts as
4004-9864 Two Circuit Class A Adapter Module for IDCs, SPMs, or NACs Four maximum required

System Batteries
Model Description Reference
2081-9272 6.2 Ah battery, 12 V These batteries can be mounted in the 4004R cabinet; select one battery model
2081-9274 10 Ah battery, 12 V per system standby requirements; two batteries are required; for more capacity
2081-9288 12.7 Ah battery, 12 V see data sheet S4081-0001 for a compatible external battery cabinet with charger

Release Control Systems Accessories (refer to additional information listed on page 3)


Model Description
2081-9046 Coil Supervision Module, one required per RAC; refer to pages 6 and 7 for detail
Abort Supervision Module; encapsulated 560, 1/2 W resistor; for Dual Hazard SPM; allows non-current limited
2081-9048
Abort and Manual Release stations to be on same circuit; refer to pages 6 and 7 for detail
4081 Series End-of-Line Resistor Harnesses; refer to data sheet S4081-0003
2099 Series Manual Stations for Releasing Applications; refer to data sheet S2099-0010
Strobe synchronization modules; 4905-9914 for Class B, 4905-9922 for Class A; see data sheet S4905-0003 for
4905-Series
details

2 S4004-0002-6 12/2015
Release Control System Reference Release Control System Requirements
Automatic Extinguishing Release Systems 1. Actuators are connected as two-wire, Class B
automatically activate actuators for the release of a fire notification/releasing circuits with only one 24 VDC
extinguishing agent (dry chemical, water spray, foam, actuator per circuit to ensure supervision. Where
CO2, Clean Agent, etc.) in response to fire detection applicable, two, 12 VDC actuators in series, or one
device input. 12 VDC actuator and a manufacturer supplied series
Automatic Extinguishing Release Systems with resistor may be used.
Separate Bell Control (single hazard) (SW rev. 4.01 2. Coil Supervision Module, model 2081-9046, must be
or higher). RAC 2 operates as a bell control NAC. When wired electrically before the actuator and located in the
cross-zoned, stage 1 alarm activates the bell until the actuator wiring junction box. (See diagram on page 7.)
release timer starts. When not cross-zoned, stage 1 alarm 3. For UL Listed Automatic Extinguishing Release valves
activates the bell until expiration of the release timer. In and actuators, refer to list on page 7.
both cross-zoned and non cross-zoned applications, 4. For FM Approved Automatic Extinguishing Release,
NAC2 may be programmed to indicate either a tamper secondary standby must be a minimum of 24 hours with
switch supervisory condition or the start of the release 5 minutes of alarm. Actuators must be electrically
timer using a cadence pattern operation. compatible.
UL and FM Extinguishing Release System Panels 5. For FM Approved Deluge and Preaction Sprinkler
must have a minimum of 24 hours of standby power. operation: IDCs must be Class A, wired to
Initiating devices must be Listed/Approved for the Listed/Approved devices; secondary standby capacity
application, and may be wired either Class A or B. must be a minimum of 90 hours with 10 minutes of
Actuators must be electrically compatible with the control alarm; and the specified compatible Automatic Water
panel circuits and power supplies, and are wired Class B to Control Valves/Actuator must be used. (See list on
provide coil supervision. (See details in next section.) page 8.)
Deluge and Preaction Sprinkler Systems 6. Power supply loading and wiring distances must be per
automatically activate water control valves in response to Installation Instructions 579-354.
fire detection device input. 7. Battery standby must be selected for proper actuator
Deluge Sprinkler Systems employ open sprinkler heads operation and may require a minimum voltage of
and provide water flow when the fire detection system 23 VDC depending on the actuator. Detailed battery
activates a common automatic water control valve. They are calculation reference information is contained in
used to deliver water simultaneously through all of the open Installation Instructions 579-354.
sprinkler heads. This type of system is applicable where the 8. Maintenance Switches, one per RAC, are required per
immediate application of large quantities of water over large NFPA 72, the National Fire Alarm and Signaling Code,
areas is the proper fire response. to allow the system to be tested or serviced without
Preaction Sprinkler Systems are similar to deluge actuating the fire suppression systems. Their use may not
systems except that normally closed sprinkler heads are used be allowed in some jurisdictions, always confirm local
and supervisory air pressure is maintained in the pipe. requirements. When used, Simplex Maintenance
Operation requires both an activated sprinkler head and an Switches are required to ensure that operation initiates a
activated fire alarm initiating device. supervisory condition.
Combined Agent Release and Preaction Systems Additional System Device Information
provides agent release and preaction control. (Available
1. Simplex Abort Switches are available when abort
with software revision 4.01 or higher.) For applications
operation is required. When used, wire on Special
where agent release may not be sufficient for fire control,
Purpose Monitoring Circuits (SPMs) as Class A or
sprinklers are put in preaction mode to allow waterflow to
Class B; Simplex model Abort Switches are required.
continue the fire response. (Preaction is assumed, selected
deluge could be provided, determined by the sprinkler 2. Manual Release Stations are used for direct activation of
installation, panel operation is the same.) the release actuators with the appropriate time delay
implemented by the fire alarm control panel.
UL requirements for Fire Alarm Systems Listed for
Automatic Release or Deluge and Preaction Sprinkler 3. See pages 2 and 3 for additional reference information.
Systems are the same as described above for Automatic Additional Information
Extinguishing Release Systems.
This data sheet is a summary of the extensive operating
FM Approved requirements for Fire Alarm Systems for features and options available with the 4004R Release
Automatic Release of Deluge and Preaction Sprinkler Control Panel. Complete details are covered in the 4004R
Systems require operation of specific compatible FM Installation, Programming, and Operating Instructions
Approved Automatic Water Control Valves, a minimum manual (publication 579-354) shipped with each 4004R.
secondary power capacity of 90 hours, and all circuits for Compatible system devices are listed on page 3. For general
the automatic release initiating devices must be capable of information, refer to Factory Mutual Research Corporation
operation during a single open circuit fault condition (FMRC) “FMRC Approval Guide,” FM Approval standard
(Class A). “Deluge Systems and Preaction Systems.”
PLEASE NOTE: Proper operation of release control systems requires that the system design, installation, and maintenance be
performed correctly and in accordance with all applicable local and national codes, and equipment manufacturer’s
instructions. No liability for total system operation is assumed or implied.
5 S4004-0002-6 12/2015
Specifications (Refer to diagram on page 7 and Instructions 579-354 for additional information)
Power Ratings
Voltage Ratings 120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select
AC Input
Current Ratings 2 A maximum @ 120 VAC input; 1 A maximum @ 240 VAC input
Power Supply Output 3 A maximum available for external loads
Temperature compensated, capable of recharging batteries required for 90 hour
Battery Charger
standby and 10 minute alarm (contingent on auxiliary power load)
Standby Current 100 mA; with IDCs fully loaded, tone-alert silenced, trouble LED on, charger off
Alarm Current 264 mA + external loads; (2 zones in alarm & 2 internal relays, NACs and RACs on)
Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum; see NAC ratings for details)
Supervisory 3 mA maximum; 3.3 k end-of-line resistor per circuit
Alarm Current 75 mA maximum
Initiating Device
Circuits (IDCs) Output Voltage 28 VDC maximum
Each IDC supports up to 30 detectors (smoke or electronic heat) and manual
Capacity
stations as required; wiring distance is limited to 50 Ω maximum
For Manual Release, Abort Switches, or Supervisory functions only; not for
Application
detectors; wiring distance is limited to 50 Ω maximum
Special Purpose For Dual Hazard Dual Hazard Application Abort Switches require a current limiting resistor of 1.2 kΩ,
Monitoring Circuits Applications 1 W, or an external Abort Supervision Module per SPM
(SPMs) Supervisory 6 mA; 3.3 k end-of-line resistor per circuit
Activated 75 mA maximum
Output Voltage 28 VDC maximum
Special Application appliance rating = 2 A maximum on a NAC
NOTE: Special Application appliance rating = full 3 A power supply rating
Alarm Current
Regulated 24 DC appliance power = 1.5 A maximum on a circuit
Notification
Appliance Circuits NOTE: Regulated 24 DC strobe load = 1.35 A maximum total for power supply
(NACs) Output Voltage Alarm = 26 VDC max.; supervisory = 29 VDC maximum; 10 k end-of-line resistor
Requires NAC dedicated to strobe control with non-coded output; use an external
Synchronized
Synch Module (4905-9914, Class A, or 4905-9922, Class B, see data sheet
Strobe Operation
S4905-0003 for details); up to 33 strobes can be synchronized per 4004R
Special Application Simplex 4901 Series horns, 4904 and 4906 Series strobes, 4903 Series 4-wire
Notification Appliances horn/strobes; refer to Installation Instructions 579-354 for additional details
Appliance
Reference Regulated 24 DC Power for other appliances listed to UL Standard 1971 or UL Standard 464; use
Appliances associated external synchronization modules where required
Output Current 2 A maximum per circuit
Release Appliance
Circuits (RACs) Activated = 26 VDC maximum; non-alarm = 29 VDC maximum;
Output Voltage
10 k end-of-line resistor
Auxiliary Power Output; for Special Two outputs are available, continuous operation or resettable operation; combined
Application loads only output is 750 mA maximum; output voltage = 19.25 to 27 VDC
Auxiliary Relay Outputs Contacts rated 2 A @ 30 VDC, 0.35 p.f., inductive, selectable as N.O. or N.C. by
(Trouble, Aux Relay 2, Aux Relay 3) jumper
Wiring Connections for Above and AC Input Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2 )
Auxiliary Module Ratings
Two circuits per module, rated same as circuits; not applicable to RACs (no
Class A Adapter Module 4004-9684
additional current required)
Relay Type Four relays with two outputs per relay; individually selectable as N.O. or N.C.
AC Ratings 7 A @ 120 VAC, resistive
Auxiliary Relay Module
DC Ratings 5 A @ 30 VDC, 0.35 power factor, inductive
4004-9860
Module Current 12 mA standby; 70 mA with all four relays energized; @ 24 VDC
Wiring Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2 )
2081-9046 Coil Supervision Module and 2081-9048 Abort Supervision Module (see page 7 for additional details)
Construction Epoxy encapsulated
Dimensions 1-3/8” W x 2-7/16” L x 1-1/16” H (34 mm x 62 mm x 27 mm)
Wiring 18 AWG (0.82 mm2) wire leads, color coded
Coil Supervision Module Current Rating 2 A maximum; internally fused at 3 A, non-replaceable
Abort Supervision Module Resistance 560 , 1/2 W
Environmental Ratings
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range up to 93% RH, non-condensing @ 100.4° F (38° C) maximum

6 S4004-0002-6 12/2015
Series 600 Smoke Detectors
UL Listed* Series 600 Optical Smoke Detectors
for Two-Wire Bases

Features

Series 600 Optical Smoke Detector details:


• Superior performance and reliability
• Attractive new design
• Designed for fast and easy installation
• Unique ‘park’ position for commissioning and service
procedures
• Interfaces seamlessly with a wide range of panels
• Compatible with Tyco® 600 Series for easy upgrade
• Low operating current, up to 32 detectors per zone 601P-UL Optical Smoke Detector Mounted
• Optional remote alarm indicating LED in 5B Base with 6A-5B-UL Adapter
• Low profile, discrete and unobtrusive
• Designed for EMI compatibility Series 600 Detector Features
• UL listed to Standard 268
The optical system consists of an infrared emitter and
Models available in two sensitivity settings: receiver arranged such that their optical axes cross in the
• 601P-UL Standard Sensitivity, nominal 2.11 to 3.8%/ft sampling volume. The emitter produces a narrow beam of
obscuration light which is prevented from reaching the receiver by the
baffles. When smoke is present in the sampling volume a
• 601P-UL-L Special Application Sensitivity, nominal
proportion of the light is scattered, some of which reaches
3.0 to 3.8%/ft obscuration
the receiver. For a given type of smoke, the light reaching
Functional chamber enclosure: the photodetector is proportional to the smoke density.
• Concentric baffle design enhances smoke capture by The emitter is a GaAlAs solid state type operating in the
directing air flow to the smoke chamber near infrared at 880 nm, while the sensor is a matched
silicon photodiode. These devices are held in place by the
Description labyrinth mouldings. The design of the labyrinth is such
that the presence of small insects should not cause false
Optical Detection. The optical detector uses a unique alarms.
measuring system. Unlike most other optical scatter
detectors the optical design does not use vertical chevrons Application Reference
to exclude ambient light, but uses concentric baffles. This
Detector Locations (see table on page 4). Locations
approach gives a better signal to noise ratio.
should be determined only after careful consideration of
This type of detector is very effective in detecting very the physical layout and contents of the area to be
low levels of visible smoke particulates (often at levels protected. Refer to NFPA 72, the National Fire Alarm
where they are not visible to the naked eye). Invisible Code. On smooth ceilings, smoke detector spacing of
smoke aerosol products, cannot however, be detected 30 ft (9.1 m) may be used as a guide.
using current optical smoke detectors as these aerosols do
Sensitivity Selection. The 601P-UL standard
not scatter or obscure light. This means that optical
sensitivity detector is recommended for most applications.
detectors favor the type of fire that we have described as
When a special application for reduced sensitivity
slow burning.
detector is required, the 601-P-UL-L should be
Although this is true, some smoldering materials such as considered. Consult your local Simplex product supplier
rubber will produce a predominantly black smoke, which for assistance in determining the proper selection.
has less scattering properties than white smoke and will
be detected later than an equivalent density of white
smoke. * Refer to page 2 for additional listing information. This product was not ULC or CSFM
listed, or approved by FM or MEA (NYC) as of document revision date. Additional listings
may be applicable; contact your local Simplex product supplier for the latest status. Listings
and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products
Westminster.

A0001-0004-1 3/2009
Product Selection

Nominal
Model Description Compatibility
Sensitivity
601P-UL 2.11 to 3.8%/ft
Optical Smoke Detector Compatible with 5B base; 5” (127 mm) diameter
601P-UL-L 3.0 to 3.8%/ft

Compatible Bases
Model Description Details Listing Reference
2-Wire Base with connections IDC and LED connections are screw
5B for Remote Alarm LED terminals for input/output wiring; 18 to UL listed under Thorn Security LTD
Indicator 14 AWG (1 mm2 to 1.5 mm2)

Detector Accessories
Model Description Details Listing Reference
6A-5B-UL 6” (152 mm) Base Adapter Increases the 5B surface area UL listed under Thorn Security LTD
Robust protective cage for Series 600
CW-5B Detector Protective Cage Not listed
detectors using the 5B base
Commissioning tool, shorts out base
SA600 Line Shorting Adapter contacts to enable cable resistance Listing not applicable, service tool only
checks to be carried out

Detector Status LED Indicators

LED Indication Status


Pulses approximately every 10 seconds Normal
Steady On Alarm

Dimensions and Reference Information

C5-B Detector Cage

2 A0001-0004-1 3/2009
Series 600 Heat Detectors
UL Listed* Series 600 Heat Detectors
for Two-Wire Bases

Features

Series 600 Heat Detector details:


• Superior performance and reliability
• Attractive new design
• Designed for fast and easy installation
• Unique ‘park’ position for commissioning and service
procedures
• Interfaces seamlessly with a wide range of panels
• Compatible with Tyco® 600 Series for easy upgrade
• Low operating current, up to 32 detectors per zone
• Optional remote alarm indicating LED 601H-F-UL Heat Detector Mounted
• Low profile, discrete and unobtrusive in 5B Base with 6A-5B-UL Adapter
• Designed for EMI compatibility
• UL listed to Standard 521 Series 600 Detector Features
• Base and adaptor are UL listed to Standard 268
Rate-of-Rise. Two negative temperature coefficient
Available models: thermistors, Rsens and Rref are used in a bridge
• 601H-RF-UL; rate-of-rise plus fixed temperature 135° F configuration. One thermistor, Rsens, is exposed to the air
(57° C), spacing distance is 70 ft (21.3 m) while the other, Rref, is thermally lagged inside the
• 601H-F-UL; fixed temperature 135° F, spacing distance detector body.
is 60 ft (18.3 m) If the temperature of the air around the detector rises
• 631H-F-UL; fixed temperature 200° F (93° C), spacing quickly, a temperature difference will be established
distance is 60 ft (18.3 m) between Rsens and Rref. The values of the bridge
components are chosen such that, if a particular rate of
Description change of temperature is sustained for sufficient time, the
comparator will change state and the detector will signal
Heat Detector Categories. Heat detectors fall into two an alarm condition. If the rate of temperature increase is
main categories; those that go into alarm once a certain very slow, then the temperatures of the sensing and
sensor temperature has been reached (fixed) and those reference thermistors will be more nearly equal. Under
that go into alarm if the rate of temperature increase is these conditions the bridge components ensure that the
above a certain level (rate-of-rise). comparator changes state when the predetermined fixed
temperature is reached.
The combination of rate-of-rise and fixed temperature
sensing elements allows fire detection from low The Rate-of-Rise detector has a rate sensitivity and fixed
temperatures, where rate-of-rise sensing would give an (static) temperature setting to suit a particular type of
earlier alarm than a fixed temperature, with the fixed application.
temperature element available for fires where temperature
builds up gradually. Fixed Temperature. The Fixed Temperature detector is
similar to the rate-of-rise detector except that the
Heat Detector Considerations. Heat detection is not reference thermistor is replaced by a fixed resistor. The
as fast as smoke detection in most fires as early stages of detector, therefore, responds more slowly to Rate-of-Rise
a fire tend to burn less hot than the later stages. However, of temperature. The bridge components are chosen instead
hostile environments where aerosols, dust, smoke or even to cause a comparator to change state when the sensing
extremes of temperature are normally present, preclude thermistor reaches a predetermined temperature
the use of smoke detectors as a fire indicator. In these irrespective of the rate of change.
cases a heat detector may provide an acceptable, though
less sensitive alternative. Heat detection is also often used
where the risk of fires or the consequences of fire are * Refer to page 2 for additional listing information. This product was not ULC or CSFM
listed, or approved by FM or MEA (NYC) as of document revision date. Additional listings
considered low, as heat detection is generally less may be applicable; contact your local Simplex product supplier for the latest status. Listings
expensive than smoke detection. and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products
Westminster.

A0001-0001-4 3/2009
Application Reference Fixed Temperature Guidelines
Detector Locations (see table on page 4). Heat 135° F (57° C) fixed temperature detectors are for normal
detectors are used where property protection is desired temperatures that do not exceed 100° F (38° C).
and where life safety protection is not required or is
200° F (93° C) fixed temperature detectors are for normal
performed by other equipment. Typical heat detector
temperatures that exceed 100°F (38° C) but are less than
applications are satisfied by the use of fixed temperature
150° F (66° C).
detectors.
The addition of rate-of-rise operation provides two forms WARNING:
of heat detection for use where temperature fluctuations In most fires, hazardous levels of smoke and
are controlled and are less than 6° F/min (3.33° C/min). toxic gas can build up before a heat detection
Where temperature may fluctuate more quickly, use fixed device would initiate an alarm. In cases where
temperature detectors. Life Safety is a factor, the use of a smoke
detector is highly recommended.

Product Selection
Model Description Compatibility
601H-RF-UL Heat Detector Fixed 135° F + Rate-of-Rise
601H-F-UL Heat Detector Fixed 135° F Compatible with 5B base; 5” (127 mm) diameter
631H-F-UL Heat Detector Fixed 200° F
Compatible Bases
Model Description Details Listing Reference
2-Wire Base with connections IDC and LED connections are screw
5B for Remote Alarm LED terminals for input/output wiring; 18 to UL listed under Thorn Security LTD
Indicator 14 AWG (1 mm2 to 1.5 mm2)
Detector Accessories
Model Description Details Listing Reference
6A-5B-UL 6” (152 mm) Base Adapter Increases the 5B surface area UL listed under Thorn Security LTD
Robust protective cage for Series 600
CW-5B Detector Protective Cage Not listed
detectors using the 5B base
Commissioning tool, shorts out base
SA600 Line Shorting Adapter contacts to enable cable resistance Listing not applicable, service tool only
checks to be carried out

Detector Status LED Indicators


LED Indication Status
Pulses approximately every 10 seconds Normal
Steady On Alarm

Dimensions and Reference Information

C5-B Detector Cage

2 A0001-0001-4 3/2009
Releasing System Peripherals
UL, ULC, CSFM Listed; FM Approved; Non-Coded Manual Stations
MEA (NYC) Acceptance* for Releasing Applications

Features
Manual fire alarm stations for releasing
applications:
 Double action push and pull operation with a
normally open (N.O.) contact
 Current limited model is available with series PUSH
connected 560  resistor for Style C operation
(current limited = alarm; open or short = trouble)
 Operation complies with ADA requirements
 Pull lever protrudes when alarmed
 Break-rod is supplied (use is optional)
 Label kit provides six varieties of releasing
applications (ordered separately) EXTINGUISHING
 Screw terminals for wiring connections RELEASE

Tamper resistant reset key lock (keyed same as


Simplex® fire alarm cabinets) Double Action Push Type Manual Release
Station (shown with sample release label)
Multiple mounting options:
 Surface or semi-flush with standard boxes or
matching Simplex boxes
CLEAN AGENT
 Flush mount adapter kit RELEASE
 Adapters are available for retrofitting to commonly EXTINGUISHING
RELEASE
available existing boxes
CARBON DIOXIDE
UL listed to Standard 38 RELEASE

FOAM SYSTEM
Operation RELEASE

SPRINKLER
Double Action Push Type Manual Release RELEASE
Stations require that a spring loaded interference plate MANUAL
(marked PUSH) be pushed back to access the pull lever of RELEASE
the single action station, reducing the possibility of an
accidental activation. A firm downward pull of the lever Label Kit 4099-9802
then activates the alarm switch, breaking an internal
plastic break-rod, visible below the pull lever.
Break-rod use is optional. Use of a break-rod can provide
an additional reduction of the possibility of an accidental Label Selection
activation without interfering with the minimum pull
requirements needed for easy activation. A blank area on the front of the station allows the
selection of a label to match the specific release
When activated, the pull lever latches into the alarm application (label kit is ordered separately).
position and remains extended out of the housing to
provide a visible indication. (Refer to data sheet S2099-0007 for standard Simplex
manual stations.)
Station reset requires the use of a key to reset the
manual station lever and deactivate the alarm switch. (If
the break-rod is used, it must be replaced.) * This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7150-0026:175 for allowable values and/or conditions concerning material presented in
Station testing is performed by physical activation of this document. Accepted for use – City of New York Department of Buildings –
the pull lever. Electrical testing can be also performed by MEA35-93E. Additional listings may be applicable; contact your local Simplex product
unlocking the station housing to activate the alarm switch. supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
are the property of Tyco Fire Protection Products Westminster.

S2099-0010-3 6/2013
Product Selection

Double Action, Push Operation, Manual Release Stations


Model Description
2099-9149 Standard operation, N.O. contact
Manual release station, red housing with white letters and white
For Style C operation, N.O. contact pull lever; requires label kit 4099-9802
2099-9152
with series connected 560 Ω resistor
Label kit; select the label required for the specific release application; types include: Clean Agent,
4099-9802
Extinguishing, Carbon Dioxide, Foam System, Sprinkler, and Manual
Accessories
Model Description Reference
2975-9178 Surface mount Steel
Refer to page 3 for dimensions
2975-9022 red box Cast aluminum
2099-9813 Semi-flush trim plate for double gang switch box, red Typically for retrofit, refer to
2099-9814 Surface trim plate for Wiremold box V5744-2, red page 4 for details

2099-9819 Flush mount Black


Refer to page 4 for details
2099-9820 adapter kit Beige
2099-9804 Replacement break-rod

Specifications

Wire Connections Screw terminal for in/out wiring, for 18 to 14 AWG wire (0.82 mm2 to 2.08 mm2)
Temperature Range 32° to 140° F (0° to 60° C) intended for indoor operation
Humidity Range Up to 90% RH at 90° F (38° F)
Housing Color Red with white raised lettering
Material Housing and pull lever are Lexan polycarbonate or equal
Pull Lever Color White with red raised lettering
Housing Dimensions 5” H x 3-3/4” W x 1” D (127 mm x 95 mm x 25 mm)
Installation Instructions 574-686

Semi-Flush Mounting Reference

Single Gang Box Mount 4" Square Box Mount


Single gang box, 2-1/2" deep 4" (102 mm) square box, 2-1/8" (54 mm) minimum
(64 mm), RACO #500 or equal depth, RACO #231 or equal (supplied by others)
(supplied by others)

Mount flush or with


1/16" (2 mm)
maximum extension
4" Square box
DO NOT RECESS
with cover plate

Station
FIRE ALARM side view

Single gang cover plate, 3/4"


PUSH (19 mm) extension, RACO #773
or equal (supplied by others)
PULL DOWN
Single gang
box outline
Wall surface

Semi-Flush Mount Side View


MANUAL
RELEASE

2 S2099-0010-3 6/2013
Releasing System Peripherals
UL, ULC, CSFM Listed; Fire Suppression System Abort Switches and Releasing
MEA (NYC) Acceptance* Appliance Circuit (RAC) Maintenance Switches

Features Description
Abort switches provide a manual Fire Suppression Releasing systems require maintenance disconnect switches
System release abort request: and often require abort switches. These abort and
 Pushbutton momentary switch is mounted on a maintenance switches are clearly labeled and combine easy
stainless steel single-gang plate operation with rugged construction for high integrity
operation.
 A protruding collar protects the switch from
accidental contact (collar is removable if required)
 Available flush or surface mount
 Flush mounting requires standard single-gang box
 Surface mounting includes a red mounting box
 Models are available with internal 1.2 k resistor for NORMAL

current limited operation 0

DISC./
1
Maintenance switches provide a secure and visible DISABLE
disconnect means for servicing Fire Suppression
System Releasing Appliance Circuits (RACs): FIRE SUPPRESSION
 Maintained position keyswitch with key removable DISCONNECT / DISABLE
only in the normal position
 Disabled position opens connection to output circuit
and places a 16.2 k resistor across the input circuit Maintenance Switches, with and without Disconnect
to initiate a supervisory condition at the host panel Indicator Lamp
 Models with indicator lamp use a bright incandescent
bulb with red lens, powered from separate 24 VDC
 Available for flush or surface mount
 Flush mounting requires a standard double-gang box FIRE SUPPRESSION
for models with lamp or a standard single gang box SYSTEM ABORT
for models without lamp.
 Surface mount models includes a red mounting box
 Models with lamp provided with a double gang
stainless steel plate. Models without lamp provided
with a single gang stainless steel plate.
PUSH AND HOLD
UL listed to Standard 864

Abort Switch

* Refer to page 2 for specific product listings. NOTE: MEA is not applicable to
Maintenance Switches. FM is not applicable to Abort Switches.
As indicated on page 2, these products have been approved by the California State Fire
Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See
CSFM Listing 7300-0026:313 for allowable values and/or conditions concerning material
presented in this document. Abort switches are accepted for use – City of New York
Department of Buildings – MEA35-93E. Maintenance switches were not approved by FM as
of document revision date. Additional listings may be applicable, contact your local Simplex®
product supplier for the latest status. Listings and approvals under Simplex Time Recorder
Co. are the property of Tyco Fire Protection Products.
S2080-0010-5 3/2017
Product Selection (see page 3 for specifications)
Abort Switches
Model Description Listing Status Details
2080-9056 Flush mount UL & CSFM listed;
Single-gang size; includes 3 position contact block housing
Surface mount; includes MEA (NYC)
2080-9057 with one contact block installed
red mounting box Acceptance
Abort Switches for 4004R Series Suppression Release Panel Current Limited Operation
Model Description Listing Status Details
2080-9067 Flush mount UL & CSFM listed; Single-gang size; includes 1.2 k, 1W resistor for current
Surface mount; includes MEA (NYC) limited operation and 3 position contact block housing with
2080-9068 Acceptance one contact block installed.
red mounting box

Note: For ULC listed abort switches, refer to datasheet S2080-0011.

Maintenance Switches with Disconnect Indicator Lamp


Model Description Listing Status Details
2080-9059 Flush mount Double-gang size; includes 3 position contact block housing
UL, ULC, & CSFM with 2 contact blocks installed; disabled position opens
Surface mount; includes listed connection to output and places a 16.2 k resistor across the
2080-9060
red mounting box input circuit; resistor is removable if required for retrofit
Maintenance Switches without Disconnect Indicator Lamp
Model Description Listing Status Details
2080-9069 Flush mount Single-gang size; includes 3 position contact block housing
UL, ULC, CSFM with 1 contact block installed; disabled position opens
Surface mount; includes listed; connection to output and places a 16.2 k resistor across the
2080-9070
red mounting box input circuit; resistor is removable if required for retrofit
Accessories for Field Installation
Model Description
Additional Contact Block for Abort or Maintenance Switch; 1 Form C contact; UL recognized component for use
2080-9061
with these switches; listings and approvals are not applicable

Abort Switch Installation Reference

2 S2080-0010-5 3/2017
TrueAlert Notification Appliances
UL, CSFM Listed; FM, and Non-Addressable Audible/Visible Notification
MEA (NYC) Approved* Appliances for 4-Wire Operation (Horn/Strobe)

Features
Wall mount audible/visible notification appliances
with efficient piezoelectric horn and high output
xenon strobe for 4-wire control applications
Xenon strobe visible notification appliance:
 24 VDC operation with switch selection for free-run or
synchronized flash rate
 Models available with 15, 75, or 110 candela
 UL listed to Standard 1971
 Compatible with ADA requirements (refer to important
installation information on page 4)
 Strobe candela rating is clearly indicated on reflector
Electronic horn audible notification appliance:
 Low current operation (25 mA @ 24 VDC)
 Harmonically rich output sound suitable for either
coded or steady operation
 UL listed to Standard 464
Available housing colors:
 Red cover with white "FIRE" lettering
 White cover with red "FIRE" lettering
Flexible, easy, and convenient semi-flush or
surface wall mounting:
TrueAlert Non-Addressable A/V Notification Appliances
 Easily mounts to single gang, double gang, or 4-inch are available in Red with White Lettering and White with
square outlet box Red Lettering
 Optional mounting adapters are available to cover
surface mounted electrical boxes and to adapt to Description
Simplex® 2975-9145 boxes
TrueAlert non-addressable audible and visible
 Diode polarized inputs for connection to reverse
notification. For applications requiring audible/visible
polarity, supervised notification appliance circuit (NAC)
(A/V) notification with horn tones, these Simplex 4903
 In/out wiring terminals for 18 AWG to 12 AWG, series appliances combine a high intensity strobe with a
accessible from front of housing, providing easy access low current electronic horn in a compact package that is
for installation, inspection and testing easy and quick to install. Each appliance can be controlled
 Rear of housing assembly does not extend into box independently from each other using conventional reverse
 Rugged, high impact, flame retardant thermoplastic polarity NACs.
housing with optional covers available to convert Multiple models with flexible mounting choices.
housing color These 4-wire operation A/V appliances are available with
 Optional UL listed red wire guard is available for semi- three strobe intensity levels (15, 75, or 110 cd) and with
flush or surface mounting red or off-white housings. Mounting can be semi-flush or
surface mount on a standard single or double gang, or 4”
square (102 mm) electrical box. Optional accessories are
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to available to increase mounting and application flexibility.
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7125-0026:239 for allowable values and/or conditions concerning material presented in this Strobe Selection
document. Accepted for use – City of New York Department of Buildings – MEA35-93E.
This product was not ULC listed as of document revision date. Additional listings may be Proper selection of visible notification is dependent on
applicable; contact your local Simplex product supplier for the latest status. Listings and
approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection occupancy, location, local codes, and proper applications
Products. of: the National Fire Alarm Code (NFPA 72); ANSI
A117.1; the appropriate model building code, BOCA,
ICBO, or SBCCI, and the application guidelines of the
Americans with Disabilities Act (ADA).
S4903-0011-6 11/2014
Strobe Operation Horn Operation
TrueAlert non-addressable A/V strobes can be set TrueAlert non-addressable A/V horns provide an
for free-run operation or synchronized operation using an audible notification output that is a loud and penetrating,
on-board selection switch. When selected for harmonically rich sound capable of a continuous or coded
synchronized operation, flash operation is controlled output per the controlling NAC’s capabilities.
from:
 Synchronized Flash Modules, 4905-9914 (Class B)
or 4905-9922 (Class A)
 4006, 4007ES Hybrid, 4008, 4010, 4010ES, 4100ES,
and 4100U Fire Alarm Control Panels (refer to
individual product data sheets for details)
 4009 IDNet NAC Extender, models 4009-9201 and
4009-9301 (refer to data sheet S4009-0002)

Product Selection

Audible/Visible Notification Appliances (Horn/Strobe)


Visible Notification Appliance Output
Model Housing Color
15 cd 75 cd 110 cd
4903-9425
Red with white
4903-9426
“FIRE” lettering
4903-9427
4903-9431
White with red
4903-9432
“FIRE” lettering
4903-9433

Adapters
Model Description Dimensions
4905-9937 Surface mount red adapter skirt Use to cover 1-1/2” 5-3/8” H x 5-1/4” W x 1-5/8” D
deep surface (136 mm x 133 mm x 41 mm)
4905-9940 Surface mount white adapter skirt mounted boxes Total depth with strobe = 4-3/8” (111 mm)
Red adapter plate, for mounting to Simplex 2975-9145 box 8-5/16” x 5-3/4” x 0.060” Thick
4905-9931
(typically for retrofit, may be mounted vertical or horizontal) (211 mm x 146 mm x 1.5 mm)
7-7/8" x 5-1/8" x 2-3/4" Deep
2975-9145 Red mounting box, requires 4905-9931 adapter plate
(130 mm x 200 mm x 70 mm)
Synchronized Flash Control Modules
Model Description Dimensions
Synchronized Flash Module, Epoxy encapsulated with
4905-9914
Class B operation in/out 18 AWG wire 1-3/8” W x 2-7/16” L x 13/16” H
Synchronized Flash Module, leads, rated for 2 A NAC, (35 mm x 62 mm x 20 mm)
4905-9922 requires 10 mA for power
Class A operation
Optional Covers and Guard
Model Description Dimensions
4905-9994 Red cover with white “FIRE” lettering 5-1/8” H x 5” W x 1-1/2” D
4905-9995 White cover with red “FIRE” lettering (130 mm x 127 mm x 38 mm)

Wire guard with mounting plate, red, compatible with surface 6-1/16” H x 6-1/16” W x 3-1/8” D
4905-9961*
or semi-flush mounted boxes (154 mm x 154 mm x 79 mm)
* UL listed by Space Age Electronics Inc.

2 S4903-0011-6 11/2014
Specifications

General Specifications

Housing Dimensions (including lens) 5-1/8” H x 5” W x 2-3/4” D (130 mm x 127 mm x 70 mm)


Temperature Range 32° to 122° F (0° to 50° C)
Humidity Range 10% to 93%, non-condensing at 100° F (38° C)
2 2
Terminal blocks for 18 AWG to 12 AWG (0.82 mm to 3.31 mm ); two
Connections
wires per terminal for in/out wiring

Strobe Specifications

Rated Voltage Range UL Listed Range Regulated 24 VDC; see Note 1 below
Flash Rate and Synchronized NAC Loading 1 Hz; with up to 35 synchronized strobes maximum per NAC

Maximum RMS Current Rating per Strobe Output 15 cd 75 cd 110 cd


(see Note 2 below) 76 mA 192 mA 227 mA

Reference Currents 18 VDC 68 mA 171 mA 202 mA


at other voltages 24 VDC 51 mA 128 mA 151 mA

Horn Specifications

Rated Voltage Range UL Listed Range 16 VDC to 33 VDC, see Notes 3 and 4 below
Sound Output Characteristics 2400 to 3700 Hz sweep, modulated at 120 Hz rate
Voltage 16 VDC 24 VDC 33 VDC

Sound Type (see Note 5) Steady Coded Steady Coded Steady Coded
Sound Output and
Current Ratings Current 15 mA 10 mA 25 mA 15 mA 28 mA 20 mA
@ 10 ft (3 m) Reverberant Chamber,
85 dBA 82 dBA 88 dBA 84 dBA 91 dBA 87 dBA
UL 464 Test
Anechoic Chamber 90 dBA 86 dBA 91 dBA 86 dBA 91 dBA 87 dBA

NOTES:
1. “Regulated 24 VDC” refers to the voltage range of 16 to 33 VDC per UL Standard 1971, Signaling Devices for the
Hearing Impaired. This voltage range is the absolute operating range. Operation outside of this range may cause
permanent damage to the appliance. Please note that 16 VDC is the lowest operating voltage that is allowed at the last
appliance on the NAC under worst case conditions. The strobe of this A/V is field selectable for free-run or synchronized
operation.
2. The maximum RMS current listed is the device nameplate rating. Strobe designs are constant wattage and the maximum
RMS current rating occurs at the lowest allowable operating voltage. (RMS is root mean square and refers to the
effective value of a varying current waveform.)
3. Terminals are provided for wiring the horn and strobe of these A/Vs to separate NACs. Operation of the horn and strobe
is not separately controlled when they are both wired to the same NAC.
4. The rated voltage range listed is the absolute operating range. Operation outside of this range may cause permanent
damage to the appliance. Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on
the notification appliance circuit under worst case conditions.
5. Coded values are typical of the output measured with a Temporal coded or a March Time coded pulse and with a sound
level meter reading on a “fast” setting. Under the same test conditions, coded horn output “peak” sound level readings
are typically 4 dBA higher.

3 S4903-0011-6 11/2014
Fire Alarm Bell GB
Applications
The GB Series provide durable and dependable operation S E R I E S
required for life safety alarm systems.

Alarm bells are low current, high decibel notification


appliances for use in fire and burglary systems or other
signaling applications. The GB Series is available in
24VDC or 120VAC.
The GB Series is available in 6" or 10" housing and listed
for indoor and outdoor applications. Bells must be used
with the GBBB box for outdoor use.

The GB Series is UL 464 listed and the units are


warrented for 3 years from the date of purchase.

Standard Features GB10 GB6 GBBB

• Available in 24VDC or 120VAC


• Available in 6” or 10” housing Product Listings
• Four wire 24VDC or 120VAC operation
• High dbA output
• Mounts to a standard 4" square electrical box
• UL listed for outdoor use when used with the GBBB
back box • UL 464
• 18 AWG wire leads • CSFM: 7135-0569:139
• BS+A/MEA #285-91-E
• Available in red metal finish • BFP (City of Chicago)
• Meets UL464 requirements
Product Compliance
• NFPA 72

GB Series Alarm Bells 24VDC or 120VAC


Model Number Part Number Voltage Current Draw dBA @ 10ft.
GB6-24 904-1278-002 24VDC 100mA 95
GB10-24 904-1279-002 24VDC 100mA 96
GB6-120 904-1280-002 120VAC 25mA 95
GB10-120 904-1281-002 120VAC 25mA 98
GB
S E R I E S
Dimensions Mounting

GBBB Box

Wiring Diagrams

24 units per carton


44 pounds per carton GB6
50 pounds per carton GB10

Architect & Engineering Specifications


The audible signal shall be Gentex GB Series or approved equal and shall be listed by Underwriters Laboratories, Inc. per
UL 464. The notification appliance shall also be listed with the California State Fire Marshal (CSFM) and the Bureau of
Standards and Appeals (NYC).
The notification appliance shall produce a peak sound output of 95dBA or greater as measured in an anechoic chamber. The
appliance shall be polarized to allow for electrical supervision of the system wiring. The unit will mount to a double gang box or
double workbox without the use of an adapter plate. The GB unit must be used with the GBBB outdoor box for outdoor
applications to meet UL listing requirements.

Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes
only, are necessarily summary, and are not purported to serve as legal advice and should not be used
551-0042-02
as such. Gentex makes no representations and warranties, express or implied, that these materials
are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws,
regulations and rules. The materials do not address all legal considerations as there is inevitable
uncertainty regarding interpretation of laws, regulations and rules and the application of such laws,
regulations and rules to particular fact patterns. Each person's activities can differently affect the
obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be
used only for informational purposes and should not be used as a substitute for seeking professional
legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the
information contained in this material.

You might also like