The RV-K cable is for power distribution and can be used for IEC 60502-1, UNE 21123-2
all types of low voltage industrial-type connections, building
installations, in urban grids, etc. This cable is particularly Flame retardant according to IEC/EN 60332-1-2
suitable for use in challenging layouts because of its high
flexibility, also making the installation process substantially
easier. It can be buried or installed in a tube as well as ISO/IEC 17025 LABORATORY TESTED
outdoors without requiring additional protection. The RV-K This product is subject to the Quality Assurance protocols of The Cable Lab®,
an ISO/IEC 17025 accredited cable testing laboratory. Testing includes vertical
cable withstands damp conditions.
flame, conductor resistance, tensile & elongation, and dimensional consistency,
verified to published standards and approved product drawings.
CHARACTERISTICS ISO/IEC
17025
Accredited
Voltage Rating (Uo/U) Testing
Laboratory
0.6/1kV
8578
Temperature Rating
-15ºC to +90ºC REGULATORY COMPLIANCE
This cable is compliant with European Regulation EN 50575, the Construction
Minimum Bending Radius Products Regulation.
Fixed: 5 x overall diameter
CONSTRUCTION
This cable meets the requirements of the Low Voltage Directive 2014/35/EU
Conductor and the RoHS Directive 2011/65/EU. RoHS compliance has been tested and
Class 5 flexible copper conductor confirmed by The Cable Lab® as meeting the requirements of the BSI RoHS
Trusted KitemarkTM.
Insulation
XLPE (Cross-Linked Polyethylene) RoHS Trusted
KITEMARK™
Sheath KM 634267
Core Identification
3 core: Green/Yellow Blue Brown
4 core: Green/Yellow Brown Black Grey
5 core: Green/Yellow Blue Brown Black Grey
7 core and above: Black with White numbers
Sheath Colour
Black
DIMENSIONS
ELAND PART NO. NO. OF NOMINAL CROSS NOMINAL THICKNESS NOMINAL OVERALL NOMINAL
CORES SECTIONAL AREA OF INSULATION DIAMETER WEIGHT
mm2 mm mm kg/km
ELAND PART NO. NO. OF NOMINAL CROSS NOMINAL THICKNESS NOMINAL OVERALL NOMINAL
CORES SECTIONAL AREA OF INSULATION DIAMETER WEIGHT
mm2 mm mm kg/km
CONDUCTORS
NOMINAL CROSS MAXIMUM DIAMETER MAXIMUM RESISTANCE OF CONDUCTOR AT 20°C
SECTIONAL AREA OF WIRES IN CONDUCTOR ohms/km
mm2 mm
Plain Wires
2.5 0.26 7.98
4 0.31 4.95
6 0.31 3.3
10 0.41 1.91
16 0.41 1.21
25 0.41 0.78
35 0.41 0.554
50 0.41 0.386
70 0.51 0.272
95 0.51 0.206
120 0.51 0.161
150 0.51 0.129
185 0.51 0.106
240 0.51 0.0801
ELECTRICAL CHARACTERISTICS
NO. OF NOMINAL CROSS CURRENT CARRYING CAPACITY VOLTAGE VOLTAGE
CORES SECTIONAL AREA Amps DROP
mm2 mV/A/m
In Air at 40ºC In Earth at 20ºC
TIME S 0.1 0.2 0.3 0.5 1.0 1.5 2.0 2.5 3.0
DE-RATING FACTORS
For air temperature other than 30°C
AIR TEMPERATURE 20°C 25°C 30°C 35°C 40°C 45°C 50°C 55°C 60°C
DE-RATING FACTOR 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.71
AIR TEMPERATURE 10°C 15°C 20°C 25°C 30°C 35°C 40°C 45°C 50°C
DE-RATING FACTOR 1.07 1.04 1.00 0.96 0.93 0.89 0.85 0.80 0.76
For soil thermal resistivity, which depends on damp other than 2.5°K.m/W
MOISTURE DEGREE OF SOIL Very Damp Slightly Damp Slightly Dry Dry Very Dry
THERMAL RESISTIVITY
(°K.m/W)
1.0 1.5 2.0 2.5 3.0
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is
believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.