Project Job ref.

(Name Of Project)
WS Atkins & Partners Overseas Calculation Title Fire Protection System Calculations (Project No)
P.0.Box 24656 Date Of Issue
Doha, Qatar

Sr. No Rev. Calculation Description No of Pages Calcs By Date Checked By Date Remarks

F001 Fire Water Storage

F002 Fire Protection Pump Sizing

NOTE
1) The calculations are based on the relevant sections of NFPA 13 - 2010 Standard for the installation of Sprinkler Systems & NFPA 14 - 2010 Standard for the Installation of
standpipe and hose systems.

2) The design values in the yellow fields are indicative only (i.e prepared as a sample calculation) .The actual values to be used, in particular for the project as per selected fire
hazard classification.In addition to that, the designer shall ensure the correctness of the values in the yellow fields as per the latest edition of the relevant NFPA Standards.
Project Job ref.:
NAFFCO QATAR (Name Of Project)
Calculation Title
Fire Water Storage (Project No)
P.0.Box 24656 Calc. by Date Checked by Date Calc sheet no.: Rev. no.
Doha, Qatar F001

A FIRE WATER DEMAND


A1 Sprinkler System
A1.1 Operating area
System Protection Area Limitations ft2 m2

Light Hazard 52000 4831


Ordinary Hazard 52000 4831
Pipe schedule 25000 2323
Extra hazard
Hydraulic calc 40000 3716
Storage 40000 3716
Ref. NFPA 13, Chapter 8.8.2 (Edition 2007)

A1.2 Occupancy hazard


light hazard Selection of hazard classification for different building
application. Ref. NFPA 13 , Annex A.5.2, A.5.3, A.5.4
(Edition 2010) or Local Authority requirements.

A1.3 Minimum flow density Density L/min gpm/ft2


LIGHT Hazard 4.1 L/min Light Hazard 3 0.10
Ordinary Hazard (Group 1) 4.1 0.15
Ordinary Hazard (Group 2) 6.1 0.20
Extra hazard (Group 1) 8.1 0.30
Extra hazard (Group 2) Extra hazard (Group 2) 12.2 0.40
Ref. NFPA 13, Chapter 11.2.3 (Edition 2010)

A1.4 Design area of water application Min.area of Sprinkler operati m2 ft2


light hazard 139 m2 Light Hazard 139 1500
Ordinary Hazard (Group 1) 139 1500
Ordinary Hazard (Group 2) 139 1500
Extra hazard (Group 1) 232 2500
Extra hazard (Group 2) 232 2500
Ref. NFPA 13, Chapter 11.2.3 (Edition 2010)

A1.5 Number of active sprinklers 12 Nos


Maximum allowable protection area of coverage for a
sprinkler and maximum spacing between sprinklers for
A1.6 Max area / sprinkler 11.583 m2 different hazard calassification shall be as per
(=A1.4 / A1.5) NFPA 13, Chapter 8, Table 8.6.2.2.1 (a,b,c,d) (Edition
2010)

A1.7 Flow through sprinkler 47.49 L/min/m2


(=A1.6 * A1.3)

A1.8 Calculation Sprinkler Water Flow rate


(=A1.7 * A1.5) 569.9 L/min
150.55 US gpm
Selected fire water demand 250 US gpm

208.2 IMP gal


Project Job ref.:
NAFFCO QATAR (Name Of Project)
Calculation Title
Fire Water Storage (Project No)
P.0.Box 24656 Calc. by Date Checked by Date Calc sheet no.: Rev. no.
Doha, Qatar F001
Hose Stream Demand
A2 Standpipe system Inside Total Combined inside
Occupancy Hose and outside Hose

A2.1 Selected fire water demand 100 US gpm gpm gpm


Light Hazard 0,50,100 100

Selected Class II standpipe system 83.3 IMP gal Ordinary Hazard (Group 1) 0,50,100 250
with Ordinary Hazard (Group 2) 0,50,100 250
hose station of 40mm (1 1/2") Extra hazard (Group 1) 0,50,100 500
Extra hazard (Group 2) 0,50,100 500
Ref. NFPA 13, Chapter 11.2.3 (Edition 2010)

Minimum Flow Rate


gpm
Class I 500
& Class II 100
& Class III 500
Ref. NFPA 14, Chapter 7.10 (Edition 2010)

A3 Duration of Water Supply Duration min


A3.1 light hazard 30 min Light Hazard 30
Ordinary Hazard (Group 1) 60-90
Ordinary Hazard (Group 2) 60-90
Extra hazard (Group 1) 90-120
Extra hazard (Group 1) 90-120
Ref. NFPA 13, Chapter 11.2.3 (Edition 2010)

A4 TOTAL FIRE WATER DEMAND


(=A1.8 + A2.1) 250.55 US gpm
A4.1 Selected fire water demand 500 US gpm

416.3 IMP gal

The minimum flow rate for additional standpipes


Class I shall be 250 gpm per standpipe, with the total not exceed
and Class III 1250 gpm for buildings that are not sprinklered throughout
or 1000 gpm for buildings sprinklered througout

The maximum flow required from 40 mm hose connection


Class II
shall be 100 gpm.

Ref. NFPA 14, Chapter 7.10 (Edition 2010)

B FIRE WATER STORAGE


(=(A4.1' * 3.785*A3.1) / 1000) 56.775 m3
B.1 Selected fire water storage 115 m3
Project Job ref.:
(Name Of Project)
Calculation Title
Fire Protection Pump Sizing (Project No)
WS Atkins & Partners Overseas
P.0.Box 24656 Calc. by Date Checked by Date Calc sheet no. Rev. no.
Doha, Qatar F002

A4.1 Flow Rate for Fire Protection pumpset 500.0 USgpm


31.5 L/s
Say 32.0 L/s
B Head Of the Pump

B.1 Static Head = 15.00 m


(Calculated as per current project)

B.2 Residual Pres. Required = 45.00 m

Min pressure at Hose Connection bar psi


Ø65 (2 1/2") hose connection 6.9 100
Ø40 (1 1/2") hose connection 4.5 65
Ref. NFPA 14, Chapter 7.8 (Edition 2010)
Max pressure at Hose Connection bar psi
Ø65 (2 1/2") hose connection 12.1 175
Ø40 (1 1/2") hose connection 6.9 100
Ref. NFPA 14, Chapter 7.8 (Edition 2010)

B.3 Pr. Drop through Pipe (estimated) 150.0 @300mm/m 4.50 m


(estimated)

B.4 Pr. Drop through Valves & Fittings 10.00 m


(estimated)

B.5 Calculated Head of the pump 74.50 m


(B.1+B.2+B.3+B.4)

B.6 Safety Factor 10 % 7.45 m


(estimated)

B.7 Total Head of the pump 81.95 m


Say 8.20 bar 120.0 psi

C Select The Pump set:

C.1 Electrical Pump (duty) 500 USgpm @ 120psi


32 L/s @ 8.2 bar

C.2 Diesel Pump (standby) 500 USgpm @ 120psi


32 L/s @ 8.2 bar

C.3 Jockey Pump 50 USgpm @ 120psi


3.2 L/s @ 8.2 bar

D Power Required

D.1 Power Required for Electrical Pump (calculated) = 52.48 kW


(Estimeted total pump efficiency) = 50.0%

D.2 Power Required for Jockey Pump(calculated) = 5.25 kW


(Estimeted 10% of power of Elec. pump)

D.3 Power Required for Electrical Pump


(from manufacturer catalogue) = 56 kW
D.4 Power Required for Jockey Pump
as suggested by the manufacturer
(enclosed sheet)
(from manufacturer catalogue) 5.6 kW
Project: Job ref.:
Project Name
Calculation Title: Calc. Sheet no.: Rev. no.:
Fire Protection System Calculations
WS Atkins & Partners Overseas
P.0.Box 24656 Drawing ref.: Calc by: Date: Checked by: Date:
Doha, Qatar

Calculations