PLOT LIMIT

40
30354

40
00
12065
6863

UP
46614

PLOT LIMIT UP SLOP 1:9


N

+0.00 m F.F.L SLOP 1:9


GENERAL NOTES:
UNDERGROUND WATER TANK MECHANICAL PUMP ROOM 1. THIS DRAWING & DESIGN ARE THE PROPERTY OF DAT ENGINEERING CONSULTANCY ,
=6 X 4.5 X 2.5 M =6 X 5 X 2.5 M
DUBAI, U.A.E. AND SHOULD NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY
+2.50 m +2.50 m IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM DAT ENGINEERING
CONSULTANCY.
2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED
BY THE CONTRACTOR AND APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR
UNDER GROUND WATER TANK TO COMMENCEMENT OF PHYSICAL WORKS.
FIRE RESERVE =12,252.28 GAL = 56.77 M3
3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY

∅100 U/G PIPE


WATER RESERV =1018.2 GAL = 4.56 M3
TOTAL REQUIRED =13270.48 GAL = 62 M3 ARCHITECT-ENGINEER OF RECORDS BEFORE USAGE OR INSTALLATION. ALL
TANK SIZE = 6 X 4.5 X 2.5 M DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
TANK CAPACITY = 13270.3 = 67 M3
BEFORE WORKS ARE COMMENCED.
+2.50 m 4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT
ENTRANCE ARCHITECTURAL, STRUCTURAL, MEP, SE DETAIL AND ALL RELEVANT SECTIONS OF
THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL COORDINATE
+0.00 m F.F.L THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE
PROCEEDING WITH THEIR WORKS.
5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

4500
30506

+0.18 m F.F.L 00
27 00 ISSUED FOR APPROVAL S.S.
ISSUE NO. PURPOSE OF ISSUE APPVD. BY.

STAGE LOUNGE SEATING


+0.18 m F.F.L CONTRACTOR:

55
00
+0.18 m F.F.L

ETISALAT TOWER
ZERO LEVEL LANDLORD / DEVELOPER:
+0.00 m

+0.18 m F.F.L REEM DEVELOPERS

∅100 U/G PIPE


SWINGS
UNDER GROUND WATER TANK
(FREE STANDING WALL) FIRE RESERVE =12,252.28 GAL = 56.77 M3 MECHANICAL PUMP ROOM

+0.18 m F.F.L SEATING ELEMENT WATER RESERV =1018.2 GAL


TOTAL REQUIRED =13270.48 GAL
= 4.56 M3
= 62 M3
=6 X 5 X 2.5 M

TANK SIZE = 6 X 4.5 X 2.5 M


TANK CAPACITY =14737.9 = 67 M3 INVESTOR:
+3.85 m F.F.L
CAFE/LOUNGE
ORANGE PADEL SPORTS
+4.65 m F.F.L
BOTTOM OF TANK
-2.50 m
BOTTOM OF TANK
-2.50 m LLC
CONSULTANT:

91017
∅80 U/G PIPE ∅80 U/G PIPE ∅100 U/G PIPE

ZERO LEVEL
14000 2000 14000 +0.00 m F.F.L +0.00 m
+0.00 m F.F.L
MECHANICAL PUMP ROOM TEL: 04-242 7700
=6 X 5 X 2.5 M
DESIGNER:
+0.18 m F.F.L +0.18 m F.F.L

∅80 U/G PIPE


DN +0.18 m F.F.L DN
+3.88 m F.F.L

BOTTOM OF ROOM
-2.50 m
PROJECT TITLE:

1500
280 2520

+0.00 m F.F.L +0.00 m F.F.L


KAKTUS SPORTS CLUB
6520

3720

∅80 U/G PIPE


54211

LOCATION:
DN
2000
+3.88 m F.F.L
REEM ISLAND - ABU DHABI
SECTION NO: PLOT NO:
+0.00 m F.F.L +0.00 m F.F.L +0.00 m F.F.L
19800

RR6 TMP1
PADDLE COURTS (VIP)
PROJECT DESCRIPTION:
FIRE FIGHTING LEGEND
1500 9800 2300 1800 9800 1500 TYPE DESCRIPTION
PROPOSED PADEL SPORTS
PENDANT SPRINKLER
BUILDING AND COURTS
WITH CAFE / LOUNGE
FM200 sprinkler
+3.88 m F.F.L

+3.88 m F.F.L UPRIGHT SPRINKLER SHEET TITLE:


1730

5KG CO2 EXTINGUISHER


PROPOSED PUDDLE BUILDING
SETTING OUT PLAN
6KG DRY POWDER EXTINGUISHER FIRE FIGHTING LAYOUT
+0.00 m F.F.L PLOT LIMIT FIRE HOSE CABINET SURFACE MOUNTED
CONSISTING OF:

PADDLE COURTS
1 NO. 25Øx30 MTR. LONG AUTOMATIC HOSE
REEL W/ NOZZLE. DRAWING NO: REVISION NO:

+0.00 m F.F.L +0.00 m F.F.L


1 NO. Ø25 LOCK SHIELD VALVE
1 NO. Ø25 PRESSURE GUAGE
F-001 00
1 NO. 5KG CO2 FIRE EXTINGUISHER SUBMISSION DATE: SCALE:
1 NO. 6 KG DCP FIRE EXTINGUISHER 1 : 200
PROJECT ID: SHEET SIZE:
BIN-2021-007713 A1

DRAWN BY MEP M.H.


PLOT LIMIT
CHECKED BY MEP K.M.

APPROVED BY S.S.

OFFICIAL USE ONLY: