You are on page 1of 8

PRCM Series

Cylindrical Connector Type Proximity Sensor


Features
● Improved the noise immunity with dedicated IC
● Built-in reverse polarity protection circuit
(DC 3-wire type)
● Built-in surge protection circuit
● Built-in over-current protection circuit (DC type)
● IP67 protection structure (IEC standard) for
connector part
● Replaceable for micro switches and limit switches
Please read “Safety Considerations” in operation
manual before using.

Specifications
● DC 2-wire type
PRCMT12-2DO PRCMT12-4DO PRCMT18-5DO PRCMT18-8DO PRCMT30-10DO PRCMT30-15DO
PRCMT12-2DC PRCMT12-4DC PRCMT18-5DC PRCMT18-8DC PRCMT30-10DC PRCMT30-15DC
Model
PRCMT12-2DO-I PRCMT12-4DO-I PRCMT18-5DO-I PRCMT18-8DO-I PRCMT30-10DO-I PRCMT30-15DO-I
PRCMT12-2DC-I PRCMT12-4DC-I PRCMT18-5DC-I PRCMT18-8DC-I PRCMT30-10DC-I PRCMT30-15DC-I
Sensing distance 2mm 4mm 5mm 8mm 10mm 15mm
Hysteresis Max. 10% of sensing distance
Standard sensing
12×12×1mm (iron) 18×18×1mm (iron) 25×25×1mm (iron) 30×30×1mm (iron) 45×45×1mm (iron)
target
Setting distance 0 to 1.4mm 0 to 2.8mm 0 to 3.5mm 0 to 5.6mm 0 to 7mm 0 to 10.5mm
Power supply 12-24VDCᜡ
(operating voltage) (10-30VDCᜡ)
Leakage current Max. 0.6mA
Response
1.5kHz 500Hz 350Hz 400Hz 200Hz
frequency※1
Residual voltage Max. 3.5V
Affection by Temp. Max. ±10% for sensing distance at ambient temperature 20℃
Control output 2 to 100mA
Insulation resistance Over 50MΩ (at 500VDC megger)
Dielectric strength 1,500VAC 50/60Hz for 1minute
Vibration 1mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z directions for 2 hours
Shock 500m/s² (approx. 50G) in each X, Y, Z directions for 3 times
Indicator Operation indicator: Red LED
Ambient
-25 to 70℃, storage: -30 to 80℃
Environ- temperature
ment Ambient
35 to 95%RH, storage: 35 to 95%RH
humidity
Protection circuit Surge protection circuit, Over-current protection
Protection structure IP67 (IEC standard)
Material Case/Nut: Nickel plated brass, Washer: Nickel plated iron, Sensing surface: Polybutylene terephthalate
Approval ᜢ
Weight※2 Approx. 38g (approx. 26g) Approx. 60g (approx. 48g) Approx. 154g (approx. 142g)
※1: The response frequency is the average value. The standard sensing target is used and the width is set as 2 times of the standard
sensing target, 1/2 of the sensing distance for the distance.
※2: The weight includes packaging. The weight in parenthesis in for unit only.
※There is IEC standard connector cable. Refer to the G-6 about IEC standard connector wires and specifications.
※Environment resistance is rated at no freezing or condensation.

D-28
Cylindrical Connector type
Specifications (A)
Photoelectric
● DC 3-wire type Sensors

PRCM18-5DN PRCM18-8DN PRCM30-10DN PRCM30-15DN (B)


Fiber
PRCM18-5DP PRCM18-8DP PRCM30-10DP PRCM30-15DP Optic
PRCM12-2DN PRCM12-4DN PRCM18-5DN2 PRCM18-8DN2 PRCM30-10DN2 PRCM30-15DN2 Sensors
PRCM12-2DP PRCM12-4DP PRCM18-5DP2 PRCM18-8DP2 PRCM30-10DP2 PRCM30-15DP2
Model PRCM12-4DN2 PRCML18-5DN PRCML18-8DN PRCML30-10DN PRCML30-15DN
PRCM12-2DN2 (C)
PRCM12-4DP2 PRCML18-5DP PRCML18-8DP PRCML30-10DP PRCML30-15DP Door/Area
PRCM12-2DP2 Sensors
PRCML18-5DN2 PRCML18-8DN2 PRCML30-10DN2 PRCML30-15DN2
PRCML18-5DP2 PRCML18-8DP2 PRCML30-10DP2 PRCML30-15DP2
(D)
Sensing distance 2mm 4mm 5mm 8mm 10mm 15mm Proximity
Sensors
Hysteresis Max. 10% of sensing distance
Standard sensing target 12×12×1mm (iron) 18×18×1mm (iron) 25×25×1mm (iron) 30×30×1mm (iron) 45×45×1mm (iron)
(E)
Sensing distance 0 to 1.4mm 0 to 2.8mm 0 to 3.5mm 0 to 5.6mm 0 to 7mm 0 to 10.5mm Pressure
Sensors
Power supply 12-24VDCᜡ
(operating voltage) (10-30VDCᜡ)
(F)
Current consumption Max. 10mA Rotary
Response frequency※1 1.5kHz 500Hz 500Hz 350Hz 400Hz 200Hz Encoders

Residual voltage Max. 1.5V (G)


Connectors/
Affection by Temp. Max. ±10% for sensing distance at ambient temperature 20℃ Connector Cables/
Sensor Distribution
Control output Max. 200mA Boxes/Sockets
Insulation resistance Over 50MΩ (at 500VDC megger)
(H)
Dielectric strength 1,500VAC 50/60Hz for 1minute Temperature
Controllers
Vibration 1mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z directions for 2 hours
Shock 500m/s² (approx. 50G) in each X, Y, Z directions for 3 times
(I)
Indicator Operation indicator: Red LED SSRs / Power
Controllers
Environ- Ambient temperature -25 to 70℃, storage: -30 to 80℃
ment Ambient humidity 35 to 95%RH, storage: 35 to 95%RH
(J)
Protection circuit Surge protection circuit, Reverse polarity protection circuit, Over-current protection Counters
Protection structure IP67 (IEC standard)
Material Case/Nut: Nickel plated brass, Washer: Nickel plated iron, Sensing surface: Polybutylene terephthalate
(K)
Approval ᜢ Timers
※2 PRCM: Approx. 61g (approx. 49g) PRCM: Approx. 146g (approx. 134g)
Weight Approx. 38g (approx. 26g)
PRCML: Approx. 85g (approx. 73g) PRCML: Approx. 181g (approx. 169g)
(L)

● AC 2-wire type Panel


Meters

PRCM18-5AO PRCM18-8AO PRCM30-10AO PRCM30-15AO


(M)
PRCM12-2AO PRCM12-4AO PRCM18-5AC PRCM18-8AC PRCM30-10AC PRCM30-15AC Tacho /
Model PRCM12-4AC PRCML18-5AO PRCML18-8AO PRCML30-10AO PRCML30-15AO
PRCM12-2AC Speed / Pulse
Meters
PRCML18-5AC PRCML18-8AC PRCML30-10AC PRCML30-15AC
Sensing distance 2mm 4mm 5mm 8mm 10mm 15mm (N)
Display
Hysteresis Max. 10% of sensing distance Units
Standard sensing target 12×12×1mm (iron) 18×18×1mm (iron) 25×25×1mm (iron) 30×30×1mm (iron) 45×45×1mm (iron)
Sensing distance 0 to 1.4mm 0 to 2.8mm 0 to 3.5mm 0 to 5.6mm 0 to 7mm 0 to 10.5mm (O)
Sensor
Power supply 100-240VACᜠ Controllers
(operating voltage) (85-264VACᜠ)
Leakage current Max. 2.5mA (P)
Switching
Response frequency※1 20Hz Mode Power
Residual voltage Max. 10V Supplies

Affection by Temp. Max. ±10% for sensing distance at ambient temperature 20℃ (Q)
Stepper Motors
Control output 5 to 150mA 5 to 200mA & Drivers
Insulation resistance Over 50MΩ (at 500VDC megger) & Controllers

Dielectric strength 2,500VAC 50/60Hz for 1minute (R)


Vibration 1mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z directions for 2 hours Graphic/
Logic
Shock 500m/s² (approx. 50G) in each X, Y, Z directions for 3 times Panels

Indicator Operation indicator: Red LED (S)


Environ- Ambient temperature -25 to 70℃, storage: -30 to 80℃ Field
Network
ment Ambient humidity 35 to 95%RH, storage: 35 to 95%RH Devices

Protection circuit Surge protection circuit


Protection structure IP67 (IEC standard) (T)
Software
Double insulation or reinforced insulation
Insulation type
(Mark: , dielectric strength between the measuring input part and the power part: 1kV)
Material Case/Nut: Nickel plated brass, Washer: Nickel plated iron, Sensing surface: Polybutylene terephthalate
Approval ᜢ
PRCM: Approx. 66g (approx. 54g) PRCM: Approx. 154g (approx. 142g)
Weight※2 Approx. 42g (approx. 30g)
PRCML: Approx. 78g (approx. 66g) PRCML: Approx. 194g (approx. 182g)

※1: The response frequency is the average value. The standard sensing target is used and the width is set as 2 times of the standard
sensing target, 1/2 of the sensing distance for the distance.
※2: The weight includes packaging. The weight in parenthesis in for unit only.
※Environment resistance is rated at no freezing or condensation.

D-29
PRCM Series
Dimensions (unit: mm)
● PRCM12-2D / PRCMT12-2D (-I) ● PRCM12-4D / PRCMT12-4D (-I)
Ø21 55.8 Ø21 55.8
17 31.5 Operation
17 7 24.5 Operation
indicator
indicator

4 M12×1 M12 4 M12×1 M12

● PRCM18-5D / PRCMT18-5D (-I) ● PRCM18-8D / PRCMT18-8D (-I)


Ø29 54.3 Ø29 53.8
24 29.5 Operation 24 10 19 Operation
indicator indicator

4 M18×1 M12
4 M18×1 M12

● PRCM30-10D / PRCMT30-10D (-I) ● PRCM30-15D / PRCMT30-15D (-I)


Ø42 63.8 Ø42 63.8
35 38 35 10 28
Operation Operation
indicator indicator

M12 M30×1.5 M12


5 M30×1.5 5
● PRCM12-2A ● PRCM12-4A
Ø21 72.8 Ø21 72.8
7 Operation
17 48.5 Operation 17 41.5
indicator
indicator

4 M12×1 M12 4 M12×1 M12

● PRCM18-5A ● PRCM18-8A
Ø29 60.6 Ø29 60.1
24 35.8 Operation 24 10 25.3 Operation
indicator indicator

4 M12×1 M12 M12×1 M12


4

● PRCM30-10A ● PRCM30-15A
Ø42 63.8 Ø42 63.8
35 38 35 10 28
Operation Operation
indicator indicator

M12 M30×1.5 M12


5 M30×1.5 5

● PRCML18-5D / PRCML18-5A ● PRCML18-8D / PRCML18-8A


Ø29 87.3 Ø29 86.8
24 62.5 Operation 24 10 52 Operation
indicator indicator

4 M18×1 M12 4 M12


M30×1.5
● PRCML30-10D / PRCML30-10A ● PRCML30-15D / PRCML30-15A
Ø42 85.8 Ø42 85.8
35 60 Operation 35 10 50
Operation
indicator indicator

M12 M12
5 M30×1.5 5 M30×1.5

D-30
Cylindrical Connector type
Control Output Diagram and Load Operation (A)
Photoelectric

DC 2-wire type DC 3-wire type Sensors

Brown NPN output type (B)


Fiber
N.O. N.C. Optic
4 Load +V Presence Brown N.O. N.C.
Sensing 1 +V
Sensors
target Nothing Sensing Presence
target None (C)
Main circuit

Load

Main circuit
10kΩ Load Operation Door/Area
Operation Sensors
Load (brown-black) Return
Return Black
4
Output voltage H (D)
Operating ON (black-blue) L Proximity
Blue Indicator Operating
Sensors
3 0V (red LED) OFF Blue ON
3 0V Indicator
(red LED) OFF
(E)
Pressure

AC 2-wire type
Sensors

Brown N.O. N.C. PNP output type (F)


Rotary
4 Load Sensing Presence Brown N.O. N.C.
Encoders
target None 1 +V
Sensing Presence
(G)
target None Connectors/
Main circuit

100- 240VAC

Main circuit
Load Operation Connector Cables/
Operation Black Sensor Distribution
50/60Hz Load 4 (black-blue) Return Boxes/Sockets
Return
Load Output voltage H
10kΩ (black-blue) L (H)
Blue Temperature
3 Operating ON Controllers
Indicator Operating ON
Blue
(red LED) OFF 3 0V Indicator
OFF
(red LED) (I)
SSRs / Power
※The number in a circle is pin no. of connector. Controllers

(J)

Wiring Diagram Counters

DC 2-wire type (standard type) DC 2-wire type (IEC standard type) (K)
Timers
Normally Open (N.O.) / Normally Closed (N.C.) Normally Open (N.O.) Normally Closed (N.C.)
(L)
Brown Brown Panel
2 1 Brown 2 1 2 1 Load +V 2 1 Load +V Meters
Brown
3 4 Load +V 3 4 +V 3 4 3 4 (M)
Tacho /
Blue Blue Blue Blue Speed / Pulse
0V Load 0V 0V 0V Meters

※Pin ①, ② are not used terminals. ※②,③ of N.O. type and ③,④ of N.C. type are not used (N)
Display
※For DC 3-wire type connector cable, it is available to use terminals. Units

with black wire (12-24V DC) and blue wire (0V). ※The pin arrangement of connector applying IEC standard is
being developed. (O)
Sensor
※Please attach "I" at the end of the name of standard type Controllers

for purchasing the IEC standard product. (P)


E.g.) PRCMT12-4DO-I Switching
Mode Power
※The connector cable for IEC standard is being developed. Supplies

Please attach "I' at the end of the name of standard type. (Q)
Stepper Motors
E.g.) CID2-2-I, CLD2-5-I & Drivers
& Controllers

(R)
DC 3-wire type AC 2-wire type Graphic/
Logic
Panels
NPN output type PNP output type Normally Open (N.O.) / Normally Closed (N.C.)
(S)
Field
Brown Brown Network
2 1 +V 2 1 +V Devices
2 1 2 1
Black Brown Brown
3 4 Load 3 4 3 4 3 4
Load
Black Load ~
(T)
~ Blue Software
Blue Blue Blue Load
0V 0V

※Please fasten the cleat of connector not to shown the ※In AC inductive type, ② and ③, ① and ④ are connected
thread. (0.39 to 0.49N.m) inside of the connector cable.

※Please fasten the vibration part with PTFE tape.


※Refer to the G-6 about IEC standard connector wires and specifications.

D-31
PRCM Series
Sensing Distance Feature Data by Target Material and Size

One side
Sensing

length
target
d
Detecting
Method
Sensing
distance (X)

PRCMT12-2D , PRCM12-2A PRCMT12-4D , PRCM12-4A


2.50 4.50

4.00 Iron(SS401)

2.00 Iron(SS401) 3.50


Sensing distance X (mm)

Sensing distance X (mm)


3.00
Stainless steel 364
1.50 (SUS364)
Stainless steel 364 2.50
(SUS364)
2.00 Brass(C3601)
1.00 Aluminum(ALS052)
1.50 Copper(C1100)
Brass(C3601)
Aluminum(ALS052) 1.00
0.50 Copper(C1100)
0.50

0.00 0.00
4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100 4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100
One side length of sensing target d (mm) One side length of sensing target d (mm)

PRCMT18-5D , PRCM(L)18-5A PRCMT18-8D , PRCM(L)18-8A


6.00 9.00
Iron(SS401)
8.00
5.00 Iron(SS401)
7.00
Sensing distance X (mm)

Sensing distance X (mm)

4.00 6.00
Stainless steel 364
Stainless steel 364 (SUS364)
5.00
(SUS364)
3.00
4.00
Brass(C3601)
2.00 3.00 Aluminum(ALS052)
Brass(C3601) Copper(C1100)
Aluminum(ALS052)
Copper(C1100) 2.00
1.00
1.00

0.00 0.00
4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100 4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100
One side length of sensing target d (mm) One side length of sensing target d (mm)

PRCMT30-10D , PRCM(L)30-10A PRCMT30-15D , PRCM(L)30-15A


12.00 16.00
Iron(SS401)
Iron(SS401) 14.00
10.00
12.00
Sensing distance X (mm)

8.00 Stainless steel 364


Sensing distance X (mm)

Stainless steel 364 10.00 (SUS364)


(SUS364)
6.00 8.00
Brass(C3601)
6.00 Aluminum(ALS052)
Brass(C3601) Copper(C1100)
4.00
Aluminum(ALS052)
Copper(C1100) 4.00

2.00
2.00

0.00 0.00
4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100 4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100
One side length of sensing target d (mm) One side length of sensing target d (mm)

D-32
Cylindrical Connector type
Sensing Distance Feature Data by Target Material and Size (A)
Photoelectric
Sensors

One side
Sensing

length
target
d
Detecting
(B)
Method Fiber
Sensing
Optic
distance (X)
Sensors

PRCM(L)12-2D PRCM12-4D (C)


Door/Area
Sensors
2.50 5.00

4.50
Iron(SS401) (D)
Iron(SS401) Proximity
2.00 4.00 Sensors
Sensing distance X (mm)

Sensing distance X (mm)


3.50
Stainless steel 364
Stainless steel 364 (SUS364) (E)
1.50 3.00 Pressure
(SUS364)
Sensors
2.50
Brass(C3601)
1.00 Brass(C3601) 2.00 Aluminum(ALS052)
Copper(C1100) (F)
Rotary
Aluminum(ALS052) 1.50 Encoders
Copper(C1100)
0.50 1.00 (G)
Connectors/
0.50 Connector Cables/
Sensor Distribution
0.00 0.00 Boxes/Sockets
4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100 4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100
One side length of sensing target d (mm) One side length of sensing target d (mm) (H)
Temperature
Controllers

PRCM(L)18-5D PRCM(L)18-8D (I)


SSRs / Power
Controllers

6.00 9.00
Iron(SS401) (J)
8.00 Counters
Iron(SS401)
5.00
7.00
Sensing distance X (mm)

Sensing distance X (mm)

4.00 6.00 Stainless steel 364 (K)


Timers
Stainless steel 364 (SUS364)
(SUS364) 5.00
3.00
4.00 Brass(C3601) (L)
Panel
Brass(C3601) Aluminum(ALS052)
Copper(C1100) Meters
2.00 3.00
Aluminum(ALS052)
Copper(C1100)
2.00 (M)
1.00 Tacho /
Speed / Pulse
1.00
Meters

0.00 0.00
4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100 4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100 (N)
One side length of sensing target d (mm) One side length of sensing target d (mm) Display
Units

(O)
Sensor
PRCM(L)30-10D PRCM(L)30-15D Controllers

12.00 18.00 (P)


Switching
Mode Power
16.00 Iron(SS401)
Supplies
10.00 Iron(SS401)
14.00
(Q)
Sensing distance X (mm)
Sensing distance X (mm)

Stepper Motors
8.00 12.00 Stainless steel 364 & Drivers
Stainless steel 364 (SUS364) & Controllers
(SUS364) 10.00
6.00 (R)
8.00 Brass(C3601) Graphic/
Logic
Aluminum(ALS052)
Brass(C3601) Copper(C1100) Panels
4.00 6.00
Aluminum(ALS052)
Copper(C1100) (S)
4.00 Field
2.00 Network
2.00 Devices

0.00 0.00
4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100 4 8 10 12 15 18 20 25 30 35 40 45 50 60 70 75 80 90 100 (T)
Software
One side length of sensing target d (mm) One side length of sensing target d (mm)

D-33
PRCM Series
Sensing

Sensing Distance Feature Data by


area (Y)
Sensing
target

Parallel (Left/Right) Movement Detecting

distance (X)
Method

Sensing
P
 RCMT12-2D /4D , P
 RCMT18-5D /8D , P RCMT30-10D /15D ,
PRCM12-2A /4A PRCM(L)18-5A /8A PRCM(L)30-10A /15A
4.0 0.8 15.0

3.5

14.0
3.0 0.6

2.5
12.0
2.0 0.5
Sensing distance X (mm)

1.7 10.0

Sensing distance X (mm)


Sensing distance X (mm)

1.5 0.4

1.3 8.0

1.0 0.3
6.0
0.7

0.5 0.2
4.0

0.4

0.1 0.1 2.0


4.0 3.0 2.0 1.0 0.0 0.5 1.0 1.5 2.0 0.8 0.6 0.4 0.2 0.0 0.2 0.4 0.6 0.8 20.0 15.0 10.0 5.0 0.0 5.0 10.0 15.0 20.0
Left ← Center → Right Left ← Center → Right Left ← Center → Right
Sensing area Y (mm) Sensing area Y (mm) Sensing area Y (mm)

PRCMT12-2D , PRCMT18-5D , PRCMT30-10D ,


PRCM12-2A PRCM(L)18-5A PRCM(L)30-10A
PRCMT12-4D , PRCMT18-8D , PRCMT30-15D ,
PRCM12-4A PRCM(L)18-8A PRCM(L)30-15A

P
 RCM(L)12-2D P
 RCM(L)18-5D /8D P
 RCM(L)30-10D /15D
PRCM12-4D
4.0 0.8 15.0

3.5

14.0
3.0 0.6

2.5
12.0
2.0 0.5

1.7 10.0
Sensing distance X (mm)
Sensing distance X (mm)

Sensing distance X (mm)

1.5 0.4

1.3 8.0

1.0 0.3
6.0
0.7

0.5 0.2
4.0

0.4

0.1 0.1 2.0


3.0 2.0 1.0 0 1.0 2.0 3.0 10.0 5.0 0.0 0.5 10.0 20.0 15.0 10.0 5.0 0.0 5.0 10.0 15.0 20.0
Left ← Center → Right Left ← Center → Right Left ← Center → Right
Sensing area Y (mm) Sensing area Y (mm) Sensing area Y (mm)

PRCM(L)12-2D PRCM(L)18-5D PRCM(L)30-10D


PRCM12-4D PRCM(L)18-8D PRCM(L)30-15D

D-34
Cylindrical Connector type
Proper Usage (A)
Photoelectric
Load connections Sensors

Brown Brown Brown


Load Load (B)
Fiber
+ + 100- Optic
240VAC Sensors
POWER 24VDC
- - 50/60Hz
Blue Blue Blue (C)
Load Load Door/Area
Sensors
< DC 2-wire type & AC 2-wire type > < DC 2-wire type > < AC 2-wire type >
(D)
When using DC or AC 2-wire type proximity sensor, the load must be connected, otherwise internal components may be Proximity
Sensors
damaged. The load can be connected to either wire.
(E)
Load connections Pressure
Sensors

● AC 2-wire type It may cause return failure of load by residual voltage.


If the load current is under 5mA, please make sure the (F)
Rotary
Brown
Load residual voltage is less than the return voltage of the load Encoders

by connecting a bleeder resistor in parallel with the load as (G)

Bleeder resistor(R) Vs shown in the diagram. Connectors/


Connector Cables/
Sensor Distribution
Blue Boxes/Sockets
Vs Vs2
110VAC: Min. 20kΩ 3W R≤ (kΩ) P> (W)
220VAC: Min. 39kΩ 10W
I R (H)
Temperature
Controllers
[ I:Action current of load, R:Bleeder resistance, P:Permissible power]
Please make the current on proximity sensor smaller than
● DC 2-wire type (I)

Brown the return current of load by connecting a bleeder resistor SSRs / Power
Controllers
Load in parallel.
+ ※W value of Bleeder resistor should be bigger for proper (J)
Bleeder resistor(R) Vs
- heat dissipation. Counters
Blue
Vs Vs2
R≤ (kΩ) P> (W)
Io-Ioff R (K)
Timers
Io: Min. action current of proximity sensor,
[ Vs: Power supply,
Ioff: Return current of load, P : Number of Bleeder resistance watt
]
(L)
Panel
Meters
Mutual-interference & Influence by surrounding metals
(M)
When several proximity sensors are mounted close to one another a malfunction of the may be caused due to mutual Tacho /
Speed / Pulse
interference. Therefore, be sure to keep a minimum distance between the two sensors as below chart indicates. Meters

(N)
Display
Units

Parallel B
(O)
A Sensor
Controllers
Face to Face
(P)
When sensors are mounted on metallic panel, it is required to protect the sensors from being affected by any metallic Switching
Mode Power
object except target. Therefore, be sure to provide a minimum distance as below chart indicates. Supplies

(Q)
Stepper Motors
& Drivers
m & Controllers

Ød n
(R)
Graphic/
ℓ Logic
Panels

ℓ (S)
Field
Network
(unit: mm) Devices

Model
PRCMT12-2D□ PRCMT12-4D□ PRCMT18-5D□ PRCMT18-8D□ PRCMT30-10D□ PRCMT30-15D□ (T)
PRCM12-2D□ PRCM12-4D□ PRCM(L)18-5D□ PRCM(L)18-8D□ PRCM(L)30-10D□ PRCM(L)30-15D□ Software

PRCM12-2A□ PRCM12-4A□ PRCM(L)18-5A□ PRCM(L)18-8A□ PRCM(L)30-10A□ PRCM(L)30-15A□


Item
A 12 24 30 48 60 90
B 24 36 36 54 60 90
ℓ 0 11 0 14 0 15
Ød 12 36 18 54 30 90
m 6 12 15 24 30 45
n 18 36 27 54 45 90

D-35