RED GREEN
12”
115V 30V
BLACK BLUE
115V 30V
BLACK BLUE
5.6”
Weight = 11 LB
Open Circuit Test (core loss test): Voltage input Current input Power lost
TEST CONDITION: Apply variable voltage to primary coils (in 120V .04A 5W
parallel). Set voltages 120 and 140VAC at 60Hz. No load on secondary
coils. Measure the primary current and input power.
140V .11A 12W
Short Circuit Test (copper loss test): Voltage input Current rated Power lost
TEST CONDITION: Short all secondary coils, and apply variable 5.5V 4.2A 23W
voltage to (parallel) primary coils. Varies the voltage from 0-20VAC at
60Hz and freeze the voltage at rated primary current.
Load Test (operation test): Voltage output Current output Power output
TEST CONDITION: Input 120VAC 60Hz to the primary coils (in 30.8V 0.0A 0W
parallel), Output 1 and 2 in parallel to load, and measure voltage and
30.0V 7.8A 234W
current at different load levels.
29.7V 15.8A 469W