You are on page 1of 2

 

INERTIA BASE LOAD CALCULATION

For primary pumps

Operating Weight of the Pump 358 Kg


Size of Inertia Base 1650 * 900* 200 mm

Density of RCC 2450 Kg /M3

Weight of RCC 705.6 Kg

Weight of inertia base (Approx.) 100 Kg

Steel Wight (10% of RCC Weight) 70.56 Kg

Total Weight 1234.16 Kg

With Safety Factor ( 25%) 1542.7 Kg

Load Acting Points 4 Nos

Point Load 385.675 Kg

Spring Selection Load 390 Kg

Design Summary

1650m m * 9 00 m m * 2 00 m m i n e r t i a ba s e wit h 4 point load each poi nt having 390 kg 


v i b r a t i o n s pring isolators 

For Secondary Pumps

Operating Weight of the Pump 736 Kg


Size of Inertia Base 2050 * 1100* 250 mm

Density of RCC 2450 Kg /M3

Weight of RCC 1360.975 Kg

Weight of inertia base (Approx.) 200 Kg

Steel Wight (10% of RCC Weight) 136.0975 Kg

Total Weight 2433.0725 Kg

With Safety Factor ( 25%) 3041.340625 Kg

Load Acting Points 4 Nos

Point Load 760.3351563 Kg

Spring Selection Load 765 Kg

Design Summary

2050m m * 1 1 00 m m * 2 50 m m i n e r t i a ba s e wit h 4 point load each poi nt having 765 kg 


v i b r a t i o n s pring isolators 