Overview............................................................................ 2
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Airflow Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Downflow/Underfloor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Glycol Correction Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Sound Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Sound pressure measurement positioning . . . . . . . . . . . . . . . 11
Fan module under raised floor, open on all sides . . . . . . . . . . 11
Fan module above raised floor, bottom supply . . . . . . . . . . . . 12
Fan module under raised floor, front or rear supply . . . . . . . . 12
Microprocessor Controller................................................21
Seven-inch Touch Screen Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Alarm LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Link-RX/TX (10/100) LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Display interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Open architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Control type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Warranty ..........................................................................25
Three-Phase Power Products or Cooling Solutions One-Year Factory Warranty25
AIRFLOW PATTERN
D = DOWNFLOW
FAN TYPE
V = CENTRIFUGAL (EC) FANS WITH BACKWARD-CURVED
BLADES WITH ELECTRONIC COMMUTATION
MODEL NUMBER
45 = 150 kW, 50 = 180 kW
na4900a
POWER SUPPLY VOLTAGE
D = 208–230V/3Ph/60Hz
G = 460V/3Ph/60Hz
L = 575V/3Ph/60Hz
Downflow units uniformly distribute large volumes of air into the environment by means of a void under a raised
access floor. The air enters the unit directly from the environment or through a ventilated or false ceiling.
na5197a
TOP RETURN TOP RETURN
WITH UNDERFLOOR SIDE AND FRONT WITH ABOVEFLOOR BOTTOM SUPPLY
SUPPLY
Note: All values are accurate to +/– 5% and based on nominal fan speed with standard filter.
Note: Contact the local sales representative for special conditions.
Note: All values are accurate to +/– 5% and based on nominal fan speed with standard filter.
Note: Contact the local sales representative for special conditions.
Note: All values are accurate to +/– 5% and based on nominal fan speed with standard filter.
Note: Contact the local sales representative for special conditions.
*Includes Motor Heat, with equal loading on each phase, rated at 208-230V/3-phase and 480V/3-phase
**Connections sizes, not recommended piping sizes
†Cooling unit with fan module
††Two valves are present.
1 m (3.28 ft)
2 m (5.56 ft)
na5180a
Fan module under raised floor, open on all sides
Hz Linear Frequency (dB)
Airflow
Model Fan Speed dB (A)
m3/h @ 20 Pa (CFM)
63 125 250 500 1000 2000 4000 8000
40% 15 589 (9,175) 49.2 56.1 56.1 53.7 49.3 50.7 48.4 42.7 56.3
50% 20 943 (12,327) 54.4 60.6 61.3 59.3 54.4 56.0 53.5 47.6 61.7
60% 25 626 (15,083) 58.5 64.2 65.9 63.9 58.7 60.1 57.5 51.2 66.3
HDCV4500 70% 29 533 (17,382) 60.8 67.0 69.6 67.5 62.0 63.4 60.7 54.1 69.8
80% 33 480 (19,706) 61.7 69.9 72.6 70.3 64.7 66.1 63.4 56.6 72.4
90% 36 190 (21,301) 63.3 72.1 74.7 72.2 66.6 68.0 65.4 58.6 74.3
100% 37 491 (22,066) 64.8 72.8 75.9 73.4 67.7 69.1 66.5 59.9 75.3
40% 20 347 (11,976) 50.6 57.5 57.4 55.0 50.5 52.0 49.6 44.0 57.5
50% 27 129 (15,968) 55.6 61.9 62.5 60.4 55.6 57.2 54.7 48.9 62.9
60% 33 204 (19,543) 59.9 65.3 66.9 65.0 59.8 61.3 58.6 52.5 67.4
HDCV5000 70% 38477 (22,647) 62.3 67.9 70.6 68.6 63.1 64.5 61.8 55.3 70.9
73.5 43 886 (25,830) 63.1 70.6 73.7 71.4 65.8 67.2 64.5 57.7 73.5
90% 47 598 (28,015) 64.3 72.6 75.8 73.4 67.7 69.1 66.5 59.7 75.3
100% 49 377 (29, 062) 65.5 73.4 77.0 74.5 68.8 70.2 67.6 60.9 76.3
40% 14 484 (8,525) 49.7 56.6 56.4 53.8 49.4 50.8 48.3 42.8 56.4
50% 18 919 (11,135) 54.5 61.0 61.2 59.0 54.3 55.8 53.4 57.7 61.5
60% 23 024 (13,551) 58.8 64.0 65.2 63.2 58.3 59.8 57.2 51.3 65.8
HDCV4500 70% 26 928 (15,849) 61.8 66.0 68.7 66.7 61.5 62.9 60.1 54.0 69.2
80% 61 194 (36,017) 62.6 68.0 71.8 69.7 64.2 65.5 62.7 56.2 71.8
90% 34 173 (20,113) 62.9 69.7 74.1 71.7 66.0 67.4 64.7 58.0 73.6
100% 35 601 (20,954) 63.4 70.5 75.3 72.8 67.1 68.6 65.9 59.1 74.5
40% 18 820 (11,077) 51.2 58.0 57.7 55.1 50.7 52.1 49.6 44.0 57.7
50% 24 415 (14,370) 55.8 62.4 62.4 60.1 55.6 57.0 54.6 49.0 62.8
60% 29 626 (17,437) 60.1 65.4 66.3 64.3 59.4 60.9 58.3 52.6 67.0
HDCV5000 70% 34 732 (20,442) 63.3 67.3 69.7 67.7 62.6 64.0 61.3 55.2 70.3
73.5 40 514 (23,846) 64.2 68.9 72.8 70.7 65.2 66.6 63.8 57.3 72.9
90% 44 601 (26,251) 64.3 70.4 75.1 72.7 67.1 68.5 65.8 59.0 74.6
100% 46 560 (27,404) 64.5 71.1 76.3 73.9 68.2 69.7 67.0 60.1 75.6
NOTE: With standard filter installed.
40% 14 787 (8,703) 49.6 56.4 56.3 53.8 49.3 50.8 48.3 42.8 56.3
50% 19 453 (11,450) 54.4 60.8 61.2 59.0 54.3 55.8 53.4 47.7 61.6
60% 23 744 (13,975) 58.8 63.9 65.4 63.4 58.4 59.8 57.3 51.3 66.0
HDCV4500 70% 27 682 (16,293) 61.5 66.2 68.9 67.0 61.6 63.0 60.3 54.0 69.4
80% 31 881 (18,764) 62.3 68.5 72.1 69.9 64.3 65.7 62.9 56.3 72.0
90% 34 781 (20.471) 62.9 70.3 74.3 71.9 66.2 67.6 64.9 58.1 73.8
100% 36 173 (21,291) 63.6 71.1 75.5 73.0 67.3 68.8 66.1 59.3 74.7
40% 19 254 (11,332) 51.0 57.8 57.6 55.1 50.6 52.0 49.6 44.0 57.6
50% 25 129 (14,790) 55.7 62.2 62.4 60.2 55.6 57.1 54.6 49.0 62.8
60% 30 595 (18,008) 60.1 65.2 66.5 64.4 59.5 61.0 58.4 52.6 67.1
HDCV5000 70% 35 806 (21,075) 63.0 67.3 69.9 68.0 62.7 64.1 61.4 55.2 70.4
73.5 41 514 (24,434) 63.8 69.2 73.1 70.9 65.4 66.7 64.0 57.4 73.1
90% 45 501 (26,781) 64.1 70.9 75.3 72.9 67.3 68.7 66.0 59.2 74.8
100% 47 408 (27,903) 64.6 71.7 76.5 74.0 68.4 69.8 67.2 60.3 75.8
NOTE: With standard filter installed.
C
B
A
na4891a
7 4500 Downflow 1960 (77.2) 2580 (101.5) 865 (34) 810 (1785)
8 5000 Downflow 1960 (77.2) 3110 (122.4) 865 (34) 890 (1962)
na4841a
B
7 4500 Downflow 550 (21.6) 2580 (101.5) 865 (34) 260 (573)
8 5000 Downflow 550 (21.6) 3110 (122.4) 865 (34) 310 (683)
C
B
A
na4890a
in.)
m (32
800 m
na4834a
Floor cutout
A
B
na5580a
Dimensions mm (in.)
Model Frame Size
A B
HDCV4500 7 2485.90 (97.87) 770.89 (30.35)
HDCV5000 8 3014.98 (118.70) 770.89 (30.35)
C
C B
B
A A
na5177a
TOP AIR RETURN PLENUM W/ BAG FILTER TOP AIR RETURN PLENUM
500 mm (20 in.) 305 mm (12 in.)
A A
ACFS76080 ACFS76081
C C
B B
A A
ACFS76082
ACFS76083
D
E
na5194a
TOP VIEW
*Center-to-center
**Edge-to-edge
†Factory adjusted height shown. Floorstand has adjustable feet allowing for a height range of 55.24 mm (2.17 in.) to 69.85 mm (2.75 in.).
††Factory adjusted height shown. Floorstand has adjustable feet allowing for a height range of 340.7 mm (13.4 in.) to 376.4 mm (14.8 in.).
Display
Reset 10/100
Micro
SD
Service
Port
USB
Console
na4820a
Item Description Function
When this LED is illuminated, a new entry has been made to the
Check Log LED
event log.
Alarm LED
Condition Description
Off No Alarms
Solid yellow Warning Alarm
Display interface
The display interface main screen displays the system state information.
• Time, date (if the clock card is inserted), and number of the unit in the LAN network
• Room temperature and the percentage of humidity (if the temperature and humidity sensor is installed)
• Information regarding unit status
Open architecture
The Uniflair CW protocol is open for integration with all building management systems. Communication
interfaces available are Modbus RTU, Modbus TCP/IP, HTTP, SNMP, LON FIT10, BACNET MSTP, BACNET
IP, and TREND.
Control type
Functions
• Status Report
• System Control
• Event Logging
• Redundant Unit Group
• Static Pressure Adjustment
• Input/Output Module Programming
Logging
The event log keeps a record of all alarms and events. Each event log contains a time/date stamp as well as
operating conditions at the time of occurrence. The controller also displays run time, in hours, for major
components (air filters, heaters, humidifier, dehumidification, and unit).
The data log displays measurements about the cooling unit, the power input to the cooling unit, and the ambient
temperature of the cooling unit.
Control
The touchscreen LCD display interface provided on Uniflair CW HDCV models is protected by a configurable
password and provides access to information and settings for the unit.
• Airflow Setpoint
• High Humidity Alarm
• High Temperature Alarm
• Humidity Setpoint
• Low Humidity Alarm
• Low Temperature Alarm
• Dual Temperature Setpoint
• Set Date/Time
• Remote Unit Switch On/Off
• Alarms
• Operating Time Scheduling
• Manual Control of Components
Terms of warranty
Schneider Electric warrants that the product shall be free from defects in materials and workmanship for a
period of one year from the date of product start-up when start-up is performed by Schneider Electric
authorized service personnel and occurs within six months of the Schneider Electric shipment date. This
warranty covers repairing or replacing any defective parts including on-site labor and travel. In the event that
the product fails to meet the foregoing warranty criteria, the warranty covers repairing or replacing defective
parts at the sole discretion of Schneider Electric for a period of one year from the shipment date. For Schneider
Electric cooling solutions, this warranty does not cover circuit breaker resetting, loss of refrigerant,
consumables, or preventive maintenance items. Repair or replacement of a defective product or part thereof
does not extend the original warranty period. Any parts furnished under this warranty may be new or factory-
remanufactured.
Non-transferable warranty
This warranty is extended to the first person, firm, association or corporation (herein referred to by “You” or
“Your”) for whom the Schneider Electric product specified herein has been purchased. This warranty is not
transferable or assignable without the prior written permission of Schneider Electric.
Assignment of warranties
Schneider Electric will assign you any warranties which are made by manufacturers and suppliers of
components of the Schneider Electric product and which are assignable. Any such warranties are assigned “AS
IS” and Schneider Electric makes no representation as to the effectiveness or extent of such warranties,
assumes no responsibility for any matters which may be warranted by such manufacturers or suppliers and
extends no coverage under this Warranty to such components.
Warranty claims
Customers with warranty claims issues may access the Schneider Electric customer support network through
the Support page of the Schneider Electric Web site, www.schneider-electric.com/ > Support > Operations
around the world. Select your country from the country selection pull-down menu at the top of the Web page.
Select the Support tab to obtain contact information for customer support in your region.
For information on how to obtain local customer support, contact the representative or other distributors
from whom you purchased your product.
As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this publication.
© 2015 Schneider Electric. All Rights Reserved.
Uniflair and the Schneider Electric logo are trademarks owned by Schneider Electric Industries SAS S.A.S., or its affiliated companies. All other
trademarks are the property of their respective owners.
990-9654B-001 7/2015