A UTC Fire & Security Company

BS-EN12094-1
KM 96761

SYNCRO XT+
Extinguishant Control Panel

Features

Approved to EN12094-1, EN54-2 and EN54-4 
Countdown indicator shows time until release in
 detection zones
16 seconds
 to 4 extinguishant areas
Up 
Mode select and manual release controls per area

Dual extinguishant outputs for each area (configurable as 
Monitored remote manual release input
Main/Reserve) 
Monitored remote hold input

First and second stage sounder outputs for each area 
Monitored remote mode select (door interlock)

First and second stage volt free changeover contacts for input
each area 
Monitored remote released pressure switch input

Released volt free contact per area 
Monitored Abort input

Fault volt free contact per area 
Serial connections for Sigma Si status units and

Programmable extinguishant delay ancillary boards. (K588)

Programmable output duration

Description
Syncro XT+ multi area addressable control panel enables extinguishing status indication and control units, or ancillary relay boards connected via a
systems to use all the features and benefits of the more sophisticated simple four-core cable.
detection techniques provided by addressable fire detectors. It also
includes other benefits of analogue addressable systems such as control With the addition of a Syncro network card, Syncro XT+ control panels can
of loop connected sounders, beacons and input/output modules. be networked to provide scalable extinguishing systems for
all sizes of installation.
With up to 16 zones of addressable detection over one or two loops it
ensures every detector can contribute to the extinguishant release.

The Syncro XT+ has up to four extinguishing areas and two releasing
outputs per area which can be controlled via simple coincidence detection
or via more complex cause and effects configured by the Loop Explorer
configuration programme.

Each extinguishant area has a comprehensive set of inputs and outputs and
is configurable via the Loop Explorer configuration programme.
All extinguishant areas may have up to seven serially connected Sigma Si

Panels

Product Code Loop Area Size (mm)


#31161M3 1 1 385 x 520x 110

#32161M3 2 1 385 x 520x 110

#31162M3 1 2 385 x 520x 110

#32162M3 2 2 385 x 520x 110

#31163M4 1 3 385 x 700x 145

#32163M4 2 3 385 x 700x 145

#31164M4 1 4 385 x 700x 145

#32164M4 2 4 385 x 700x 145

‘#’ - replace with ‘A’ for Apollo protocol or ‘H’ for Hochiki protocol.

For further information visit www.kentec.co.uk


Specification

Construction 1.2mm mild sheet steel

IP Rating IP30

Finish Epoxy powder coated

Colour - lid & box BS 00 A 05 grey - fine texture

Colour - control panel & labels RAL 7047 light grey - satin

Weight 10kg

Mains supply 230V AC +10%/-15% (100 Watts maximum)

Mains supply fuse 1.6 Amp (F1.6A L250V)

Power supply rating (1 & 2 area units) 3 Amps total including battery charge 28V +/- 2V

Power supply rating (3 & 4 area units) 4 Amps including battery charge 28V +/- 2V

Maximum ripple current 200 millivolts

Battery charge voltage 27.6VDC nominal (temperature compensated)

Battery charge current 0.7A maximum

Battery fuse 20mm, 3.15A glass

Current draw in mains fail condition 54 milliamps per extinguishing module

3A (#31161M3, #32161M3, #31162M3, #32162M3)


Maximum current draw from batteries 5.25A (#31163M4, #32163M4, #31164M4, #32164M4)

Sigma XT+ module Aux 24V output Fused at 500mA with electronic fuse - 1 per extinguishant area

Syncro AS Aux 24V output Fused at 2.5A - not available to user

1st and 2nd stage Sounder outputs 21 to 28V DC Fused at 1A with electronic fuse

Fault relay contact rating 5 to 30VDC 1A Amp maximum for each

Fire relay contact rating 5 to 30VDC 1A Amp maximum for each

Local fire relay contact rating 5 to 30VDC 1A Amp maximum for each

First stage contact rating 5 to 30VDC 1A Amp maximum for each

Second stage contact rating 5 to 30VDC 1A Amp maximum for each

Extract contact rating 5 to 30VDC 1A Amp maximum for each

Zone quiescent current 2mA maximum

Terminal capacity 0.5mm2 to 2.5mm2 solid or stranded wire

Number of sounders per circuit Dependent on type and current consumption - typically 20+

Monitored input end of line 6K8 5% ½ Watt resistor

Sounder circuit end of line 10K 5% ¼ Watt resistor

Extinguishant output EOL 1N4004 Diode

No. of detection circuits 1 or 2

No. of zones 16

No. of sounder circuits Dependent on model 21 to 28V DC

Extinguishant release output 21 to 28V DC. Fused at 1 Amp

Extinguishant release delay Adjustable 0 to 60 seconds (+/- 10%)

Extinguishant release duration Adjustable 60 to 300 seconds

SIL, AL, FLT, RST inputs Switched -ve, min resistance 0 ohms, max resistance 100 Ohms

For further information visit www.kentec.co.uk


Specification

Cabling FP200 or equivalent (max capacitance 1uF max inductance 1 mH

Monitored inputs normal threshold 10K ohm to 2K ohm

Monitored inputs alarm threshold 2K ohms to 150 ohms +/- 5%

Monitored inputs Short circuit threshold 140 ohms to 0 ohms +/- 5%

Status unit/Ancillary board connection Two wire RS485 connection (EIA-485 specification)

Status unit power output 21 to 28V DC. Fused at 500mA with electronic fuse

Datasheet DS58/10/17
For further information visit www.kentec.co.uk
Kentec Electronics Ltd. reserves the right to alter the specification of its products from time to time without notice.
Although every effort has been made to ensure the accuracy of the information contained in this document it is not
warranted or represented by Kentec Electronics Ltd. to be a complete and up-to-date description.
PP2606/2021/Issue 2
Page 1 of 3

Discovery
Optical Smoke Detector
Technical data
All data is supplied subject to change without notice.
Specifications are typical at 24V, 25°C and 50% RH unless
otherwise stated.
Detection principle Photo-electric detection of light
scattered in a forward direction by
smoke particles
Chamber configuration Horizontal optical bench housing an
infrared emitter and sensor arranged
radially to detect forward scattered
light
Sensor Silicon PIN photo-diode
Emitter GaAlAs infra-red light emitting diode
Sampling frequency Once per second
Supply Wiring Two wire supply, polarity insensitive
Terminal functions L1 & L2 Supply in & out connections
+R Remote indicator positive
Product overview connection (internal 2.2 kΩ
resistance to positive)
Product Optical Smoke Detector
–R Remote indicator negative
Part No. 58000-600 connection (internal 2.2 kΩ
resistance to negative)
Digital Communication Discovery (XP95 and Digital communication Discovery, (XP95and CoreProtocol
CoreProtocol® compatible) compatible)
Modulation voltage 5–9 V peak to peak
Compliance Operating voltage 17 V - 28 V dc
Quiescent current 300 µA
Power-up surge current 1mA
Maximum power-up time 10 seconds
Alarm indicator Two clear 360º viewable light emitting
diode (LED) illuminating red in alarm.
Optional remote LED
Alarm current, LED 3.5 mA
illuminated
Product information Remote output Connects to positive line through
characteristics 4.5 kΩ (5 mA maximum)
The Discovery Optical Smoke Detector works on the light Clean-air analogue value 23 +4/-0
scatter principle and is ideal for applications where slow Alarm level analogue value 55
burning or smouldering fires are likely. Operating temperature -40°C to +70°C
• Responds well to slow burning, smouldering fires Storage temperature -40ºC to +80ºC
Humidity 0% to 95% RH (no condensation or
• Well suited for accommodation decks, passages and icing)
escape routes
Vibration, impact and shock EN54 - 7
• Unaffected by wind or atmospheric pressure Standards and approvals EN 54-7, CPR, LPCB, VdS, BOSEC,
SBSC, FG, CCMG, Kazaksthan
• Rejection of transient signals
Dimensions 100 mm diameter x 42 mm height
• Remote test feature (50 mm height with XPERT 7 base)
Weight 105 g
• Five EN54 approved response modes
(160 g with XPERT 7 mounting base)
Note: For system compatibility and feature support of this device, Materials Housing White flame-retardant polycarbonate
please refer to your chosen panel manufacturer. Terminals Nickel plated stainless steel

All information in this document is given in good faith but Apollo


Fire Detectors Ltd cannot be held responsible for any omissions or
36 Brookside Road, Havant Tel: +44 (0)23 9249 2412 Email: sales@apollo-fire.com errors. The company reserves the right to change the specifications
Hampshire, PO9 1JR, UK. Fax: +44 (0)23 9249 2754 Web: www.apollo-fire.co.uk of products at any time and without prior notice.

MANAGEMENT MANAGEMENT PRODUCTCT


SYSTEMS SYSTEMS TION
CERTIFICATION

Assessed to ISO 9001:2015 Assessed to ISO 14001:2015 Cert/LPCB ref. 010


© Apollo Fire Detectors Ltd 2021
Cert/LPCB ref. 010 Cert/LPCB ref. 010 EMS
PP2606/2021/Issue 2
Page 2 of 3

Operation Features
The Discovery Optical Smoke Detector has a white moulded Response modes
polycarbonate case with wind-resistant smoke inlets.
The indicator LEDs are colourless when the detector is in Discovery Optical Smoke Detectors can be operated in
quiescent state and red in alarm. Within the case is a printed any one of five EN54 approved response modes, which
circuit board which on one side has the light proof labyrinth can be selected through the fire control panel. Each mode
chamber with integral gauze surrounding the optical corresponds to a unique response behaviour, which is related
measuring system and on the other the address capture, to sensitivity to fire. Mode 1 gives a higher sensitivity to fire
signal processing and communications electronics. than Mode 5.

An infrared light emitting diode within its collimator is Discovery Optical Smoke Detector
arranged at an obtuse angle to the photo-diode. The photo- Response Times
diode has an integral daylight blocking filter.
Alarm Minimum
The IR LED emits a burst of collimated light every second. In Mode threshold dB/m time to alarm
clear air the photo-diode receives no light directly from the (%/m) (Seconds)
IR LED because of the angular arrangement and the chamber 1 1.4 0.08 5
baffles. When smoke enters the chamber it scatters light 2 1.4 0.08 30
from the emitter IR LED onto the photo-diode in an amount
related to the smoke characteristics and density. The photo- 3 2.1 0.12 5
diode signal is processed to provide an analogue value for 4 2.1 0.12 30
transmission when the detector is interrogated. 5 2.4 0.14 5
Discovery Optical Smoke Detector
schematic diagram Flashing LEDs
Discovery Optical Smoke Detectors have two integral LED
indicators, which can be illuminated at any time by the
Address buttons fire control panel to indicate detectors in alarm. A flashing
Optical chamber LED mode can also be programmed to activate each time a
detector is polled.
Photo-diode
PCB cover Remote test feature
The remote test feature is enabled from the fire control panel.
On receipt of the command signal from the fire control panel,
the detector is forced electrically into alarm. An analogue
value of 85 is returned to the fire control panel to indicate
that the detector is working correctly.

Case molding Infra-red LED Rejection of transient signals


Discovery detectors are designed to give low sensitivity to
very rapid changes in the sensor output, since these are
unlikely to be caused by real fire conditions, resulting in
fewer false alarms.

Electrical description Drift compensation


The Discovery Optical Smoke Detector is designed to be Discovery Optical Smoke Detectors include compensation for
connected to a two wire loop circuit carrying both data and signal drift to compensate for changes in the sensor output
a 17 V to 28 V dc supply. The detector is connected to the caused, for example by dust in the chamber, and will therefore
incoming and outgoing supply via terminals L1 and L2 in the hold the sensitivity at a constant level even with severe
mounting base. A remote LED indicator requiring not more chamber contamination. This increased stability is achieved
than 4 mA at 5 V may be connected between the +R and -R without significantly affecting the detectors sensitivity to fire
terminals. An earth connection terminal is also provided. The whilst still meeting the requirements of the EN54 standard.
detector is calibrated to give an analogue value of 23 +4/-0
counts in clean air. This value increases with smoke density.
A count of 55 corresponds to the alarm level analogue value.
PP2606/2021/Issue 2
Page 3 of 3

EMC Directive 2014/30/EU


The Discovery Optical Smoke Detector complies with the
essential requirements of the EMC Directive 2014/30/EU,
provided that it is used as described in this data sheet.
A copy of the Declaration of Conformity is available from the
Apollo website: www.apollo-fire.co.uk.
Construction Products Regulation 305/2011/EU
The Discovery Optical Smoke Detector complies with
the essential requirements of the Construction Products
Regulation 305/2011/EU.
A copy of the Declaration of Performance is available from
the Apollo website: www.apollo-fire.co.uk

Discovery Optical Smoke Detector dimensions

Response characteristics of Discovery Optical Smoke


Detectors
Type of fire Response
Overheating/thermal combustion Very Good
Smouldering/glowing combustion Moderate/Good
Flaming combustion Good
Flaming with high heat output Good
Flaming - clean burning Poor
2-31-090 / Fire & ind us trial vis ual s ignals

AL100X Alarm Horn Sounder &


Xenon Strobe Beacon
The AL100X is a compact, high output, 110dB(A) alarm horn sounder with a 5
Joule, 200cd Xenon strobe beacon. CPR complaint, EN54-3 & EN54-23 tested
and UL/cUL approved for private mode fire use. Featuring 64 alarm tone
frequencies and 4 remotely activated stages/channels.
The AL100X features the A100 alarm ho rn so under co mbined with the L101X Xeno n stro be
beaco n. The co mpact, ro bust enclo sure is ideal fo r all general signalling applicatio ns including
fire, security and pro cess co ntro l. The alarm ho rn so under & Xeno n stro be beaco n may be
co nnected fro m a single o r separate supplies fo r simultaneo us o r independent o peratio n.

Features
Automatic synchronisation
Continuously rated
Dual M20 or 1/2"NPT clearance cable entries
Duplicate pluggable cable terminations – Class A
Ingress protection IP66 Type 3R/13
64 alarm tone frequencies and 4 remotely activated alarm stages
Available with custom tone configurations and frequencies
Diode polarized for use in supervised circuits

Ap p ro vals
UL: UL464, UL464A, UL1638, UL1638A
cUL: CSA C22.2 No 205-17
ULC: CAN/ULC-S525 & CAN/ULC-S526
UL EU: (EN54-3 & EN54-23) UL-EU-01154-CPR
CPR 305/2011: 2821-CPR-0109
EAC CU TR 043/2017: B.00291/21
EAC: RU D-GB.GA05.B.12595-20
RMRS Marine: No. 19.00193.278
CE, UKCA
S p ecif icatio n Part C o d es
A l ar m H or n : Var i ab l e: I d en ti f i er : D esc r i p ti on :
Maximum output: 110dB(A) @ 1 m ±3dB
Product type: AL100X Combined alarm horn sounder & Xenon strobe
[101dB(A) @ 10ft/3m ±3dB]
Voltage: DC012 12Vdc (11.5-14Vdc)
Nominal output: 102dB(A) @ 1m ±3dB
DC024 24Vdc (20-28Vdc)
[93dB(A) @ 10ft/3m ±3dB]
DC048 48Vdc (42-54Vdc)
No. of tones: 64 (UKOOA / PFEER compliant) AC024 24Vac 50/60Hz
AC048 48Vac 50/60Hz
No. of stages: 4
AC115 115Vac 50/60Hz
Volume control: -12dB(A) tone dependent AC230 230Vac 50/60Hz
Effective range: 38m/124ft @ 1KHz Back box/cable M Back box with mounting lugs – 2 x M20,
entries: [e] 1/2"NPT clearance
In rush: 636mA within 4.0ms @ 24Vdc
Stopping plug A ABS
Stage switching: Negative (common positive)
material: [m]
Xen on Str ob e:
Equip. tag/Duty 0 No equip. tag or Duty label
Energy: 5 Joules(5Ws) label: [s] 1 316 (A4) St/St Equip. tag/Duty label
Flash rate: 1Hz (60 fpm) 2 Metalised Polyester Equip. tag/Duty label
DC units: 1.5Hz (90 fpm) & Double strike Product version: A UL/cUL, CPR, RMRS, EAC, CE, UKCA
Peak Candela: 500,000 cd – calculated from energy (J) [v]
Effective cd: 250 cd – calculated from energy (J) Product option: 1 Standard product
[o] X Custom configuration – contact E2S
Peak Candela: 86,935 cd* – measured ref. to I.E.S. Z Custom alarm tone software – contact E2S
Effective cd: 200 cd* – measured ref. to I.E.S. Enclosure: [x] R Red (RAL 3000)
Tube life: Emissions may reduce to 70% after 8 million flashes G Grey (RAL7038)
W White
Gen er al :
Ingress protection: IP66 Type 3R/13 Lens colour: [y] A Amber
B Blue
Enclosure: High impact UL94 V0 & 5VA FR ABS/PC C Clear
Lens colour filter: Field replaceable UV stable PC G Green
M Magenta
Terminals: 0.5 – 2.5mm² (20-14 AWG) R Red
Line monitoring: Diode polarized for use in supervised circuits Y Yellow

Operating: -40 to +66°C [-40° to +151°F]


Storage: -40 to +70°C [-40° to +158°F]
Relative humidity: 95% at 20°C [68°F]
Vibration test: 35Hz for a duration 4Hr (UL464/UL1638)
Jarring test: 3ft/lb Energy (UL464/UL1638)
Impact test: 3x 5lb (UL464/UL1638)
MTBF DC: 114.79 years / 1,005,530 hours – MIL 217
MTBF AC: 86.29 years / 755,857 hours – MIL 217
Weight DC: 0.46kg / 1.01lbs
Weight AC: 0.57kg / 1.25lbs
C urrent C o nsump tio n
P r od u c t
Nom i n al Vol tage: Vol tage Ran ge: Beac on Cu r r en t: H or n Cu r r en t:
Ver si on :
DC012 12Vdc 11.5-14Vdc 341mA 17mA
DC024 24Vdc 20-28Vdc 250mA 33.5mA
DC048 48Vdc 42-54Vdc 170mA 113mA
AC024 24Vac 24-28Vac 50/60Hz 300mA 42.5mA
AC048 48Vac ±10% 50/60Hz 250mA 42.5mA
AC115 115Vac ±10% 50/60Hz 70mA 25mA
AC230 230Vac ±10% 50/60Hz 35mA 17mA
T o ne tab le
S 1 D e s c ri p t i o n S 2 S 3 S 4 S 1 D e s c ri p t i o n S 2 S 3 S 4
T 1 1000 Continuous - PFEER Toxic Gas Any T 2 T 44 T 33 800 (0.25s on, 1.00s off) Intermittent Any T 24 T 8
T2 1200/500 @ 1Hz Sweeping - DIN / PFEER P.T.A.P. Any T 3 T 44 T 34 800 @ 2Hz (0.25s on, 0.25s off) - IMO code 3.... Any T 24 T 8
T3 1000 @ 0.5Hz (1s on, 1s off) Intermittent - P... Any T 2 T 44 T 35 1000 @ 1Hz (0.50s on, 0.50s off) Intermittent Any T 24 T 8
T4 1.4KH-1.6KHz 1s, 1.6KHz-1.4KHz 0.5s - NF C 48... Any T 24 T 1 T 36 2400 @ 1Hz (0.50s on, 0.50s off) Intermittent Any T 24 T 8
T5 544(100mS)/440 (400mS) - NF S 32-001 Any T 19 T 1 T 37 2900 @ 5Hz (0.10s on, 0.10s off) Intermittent Any T 24 T 8
T6 1500/500 - (0.5s on , 0.5s off) x3 + 1s gap -... Any T 44 T 1 T 38 363/518 @ 1Hz (0.50s / 0.50s) Alternating Any T 8 T 19
T7 500-1500Hz Sweeping 2 sec on 1 sec off - AS4428 Any T 44 T 1 T 39 450/500 @ 2Hz (0.25s / 0.25s) Alternating Any T 8 T 19
T8 500/1200Hz @ 0.26Hz(3.3s on, 0.5s off) - NEN ... Any T 24 T 35 T 40 554/440 @ 1Hz (0.50s / 0.50s) Alternating Any T 24 T 19
T9 1000 (1s on, 1s off)x7 + (7s on, 1s off) - IM... Any T 34 T 1 T 41 554/440 @ 0.65Hz (0.76s / 0.76s) Alternating Any T 8 T 19
T 10 1000 (1s on, 1s off)x7 + (7s on, 1s off) - IM... Any T 34 T 1 T 42 561/760 @ 0.83Hz (0.60s / 0.60s) Alternating Any T 8 T 19
T 11 420(0.5s on, 0.5s off)x3 + 1s gap - ISO 8201 ... Any T 1 T8 T 43 780/600 @ 0.96Hz (0.52s / 0.52s) Alternating Any T 8 T 19
T 12 1000(0.5s on, 0.5s off)x3 + 1s gap - ISO 8201... Any T 1 T8 T 44 800/1000 @ 2Hz (0.25s / 0.25s) Alternating Any T 24 T 19
T 13 422/775 - (0.85 on, 0.5 off) x3 + 1s gap - ... Any T 1 T8 T 45 970/800 @ 2Hz (0.25s / 0.25s) Alternating Any T 8 T 19
T 14 1000/2000 @ 1Hz - Singapore Any T 3 T 35 T 46 800/1000 @ 0.875Hz (0.57s / 0.57s) Alternating Any T 24 T 19
T 15 300 Continuous Any T 24 T 35 T 47 2400/2900 @ 2Hz (0.25s / 0.25s) Alternating Any T 24 T 19
T 16 440 Continuous Any T 24 T 35 T 48 500/1200 @ 0.3Hz (1.67s / 1.67s) Sweeping Any T 24 T 12
T 17 470 Continuous Any T 24 T 35 T 49 560/1055 @ 0.18Hz (2.73s / 2.73s) Sweeping Any T 24 T 12
T 18 500 Continuous - IMO code 2 (Low) Any T 24 T 35 T 50 560/1055 @ 3.3Hz (0.15s / 0.15s) Sweeping Any T 24 T 12
T 19 554 Continuous Any T 24 T 35 T 51 600/1250 @ 0.125Hz (4s / 4s) Sweeping Any T 24 T 12
T 20 660 Continuous Any T 24 T 35 T 52 660/1200 @ 1Hz (0.50s / 0.50s) Sweeping Any T 24 T 12
T 21 800 Continuous - IMO code 2 (High) Any T 24 T 35 T 53 800/1000 @ 1Hz (0.50s / 0.50s) Sweeping Any T 24 T 12
T 22 1200 Continuous Any T 24 T 35 T 54 800/1000 @ 7Hz (0.07s / 0.07s) Sweeping Any T 24 T 12
T 23 2000 Continuous Any T 3 T 35 T 55 800/1000 @ 50Hz (0.01s / 0.01s) Sweeping Any T 24 T 12
T 24 2400 Continuous Any T 20 T 35 T 56 2400/2900 @ 7Hz (0.07s / 0.07s) Sweeping Any T 24 T 12
T 25 440 @ 0.83Hz (0.60s on, 0.60s off) Intermittent Any T 44 T 8 T 57 2400/2900 @ 1Hz (0.50s / 0.50s) Sweeping Any T 24 T 12
T 26 470 @ 0.9Hz (0.55s on, 0.55s off) Intermittent Any T 44 T 8 T 58 2400/2900 @ 50Hz (0.01s / 0.01s) Sweeping Any T 24 T 12
T 27 470 @ 5Hz (0.10s on, 0.10s off) Intermittent Any T 44 T 8 T 59 2500/3000 @ 2Hz (0.25s / 0.25s) Sweeping Any T 24 T 12
T 28 544 @ 1.14Hz (0.43s on, 0.44s off) Intermittent Any T 24 T 8 T 60 2500/3000 @ 7.7Hz (0.65s / 0.65s) Sweeping Any T 24 T 12
T 29 655 @ 0.875Hz (0.57s on, 0.57s off) Intermittent Any T 44 T 8 T 61 800Hz Motor Siren Any T 24 T 12
T 30 660 @ 0.28Hz (1.80s on, 1.80s off) Intermittent Any T 24 T 8 T 62 1200Hz Motor Siren Any T 24 T 12
T 31 660 @ 3.3Hz (0.15s on, 0.15s off) Intermittent Any T 24 T 8 T 63 2400Hz Motor Siren Any T 24 T 12
T 32 745 @ 1Hz (0.50s on, 0.50s off) Intermittent Any T 24 T 8 T 64 Simulated Bell Any T 21 T 12

E2 S Warning S ignals s ales @ e2 s .com www.e2 s .com 23 Dec 2021


No liability is accepted for any consequence of the use of this document. The technical specification of this unit is subject to chang e without notice due to our policy of continual product development. All dimensions are approximate. This unit is sold subject to our standard
conditions of sale, a copy of which is available on request.
PP2609/2019/Issue1
Page 1 of 4

Discovery
Optical/Heat Multisensor Detector
Technical data
All data is supplied subject to change without notice. Specifications
are typical at 24V, 25°C and 50% RH unless otherwise stated.
Detection principle Smoke: Photo-electric detection of light
scattered by smoke particles
Heat: Temperature-dependent resistance
Supply Wiring Two wire supply, polarity insensitive
Terminal functions L1 & L2 Supply in & out connections
+R Remote indicator positive
connection (internal 2.2kΩ
resistance to positive)
–R Remote indicator negative
connection (internal 2.2 kΩ
resistance to negative)
Operating voltage 17 - 28 V dc
Communication protocol Discovery (XP95 and CoreProtocol
compatible)
Modulation voltage 5 –9 V peak to peak
Product overview Quiescent current 400 µA

Product Optical/Heat Multisensor Power-up surge current 1 mA


Detector Maximum power-up time 10 seconds
Alarm current, LED 3.5 mA
Part No. 58000-700 illuminated
Digital Communication Discovery (XP95 and Remote output Connects to a positive line through
CoreProtocol® compatible) characteristics 4.5 kΩ (5 mA maximum)
Clean air analogue value 23 +4/-0
Alarm level analogue 55
Compliance value
Alarm indicator Two whie diffused LEDs, illuminated red in
alarm. Optional remote LED
Operating temperature -40°C to +70°C
Storage temperature -40°C to +80°C
Humidity 0% to 95% RH (no condensation or icing)
Effect of temperature on Less than 15% change in sensitivity
optical sensor over rated change. Slow changes in
ambient conditions will automatically be
compensted and will not affect sensitivity
Product information
Effect of wind speed on None
The Discovery Optical / Heat Multisensor Detector contains an optical sensor
optical smoke sensor and a thermistor temperature sensor Vibration, impact and EN 54-7
whose outputs are combined to give the final analogue value. shock
IP Rating IP44
• Ideal for a wide range of applications
Standards and approvals EN 54-5, EN 54-7, CPR, LPCB, VdS, BOSEC,
• Enhanced false alarm management SBSC, FG, CCMG, Kazaksthan
• Unaffected by wind or atmospheric pressure Dimensions 100 mm, diameter x 50 mm height
Weight 105 g
• Well suited to sensitive environments
Materials Housing: White flame-retardant
• Five EN54 approved response modes polycarbonate
Terminals: Nickel plated stainless steel
• Heat only and optical only options
Smoke element only
• Remote test feature Chamber configuration Horizontal optical bench housing infra-red
emitter and sensor, arranged radially to
detect forward scattered light
Note: For system compatibility and feature support of this device,
please refer to your chosen panel manufacturer. Sensor Silicon PIN photo-diode
Emitter GaAIAs infra-red light emitting diode
Sampling frequency Once per second
All information in this document is given in good faith but Apollo
36 Brookside Road, Havant Tel: +44 (0)23 9249 2412 Email: sales@apollo-fire.com Fire Detectors Ltd cannot be held responsible for any omissions or
Hampshire, PO9 1JR, UK. Fax: +44 (0)23 9249 2754 Web: www.apollo-fire.co.uk errors. The company reserves the right to change the specifications
of products at any time and without prior notice.

MANAGEMENT
SYSTEMS
MANAGEMENT
SYSTEMS
PRODUCT
CERTIFICATION
© Apollo Fire Detectors Ltd 2019
Assessed to ISO 9001:2015 Assessed to ISO 14001:2015 Cert/LPCB ref. 010
Cert/LPCB ref. 010 Cert/LPCB ref. 010 EMS
PP2609/2019/Issue1
Page 2 of 4

Operation Features
The way in which the signals from the two sensors are Response modes
combined depends on the response mode selected. The five
modes provide response behaviour which incorporates pure Discovery Optical/Heat Muitisensor detectors can be
heat detection, pure smoke detection and a combination of operated in any one of five EN54 approved response modes,
both. The multisensor detector is therefore useful over the which can be selected through the fire control panel. Each
widest range of applications. mode corresponds to a unique response behaviour, which is
related to sensitivity to fire. Mode 1 gives a higher sensitivity
The signals from the optical smoke sensing element and to fire than Mode 5.
the temperature sensor are independent and represent
the smoke level and the air temperature respectively in Discovery Optical/Heat Multisensor detector
the vicinity of the detector. The detectors micro-controller operating modes
processes the two signals according to the mode selected. Smoke Minimum
sensitivity Temp
When the detector is operating as a multisensor (i.e. modes Response time to
Mode (grey smoke) sensitivity
type alarm
1, 3 and 4) the temperature signal processing extracts only (relative)
%/m dB/m (seconds)
rate-of-rise information for combination with the optical
signal. 1 1.1 0.06 High Multisensor 20
2 2.1 0.12 Not set to Optical 30
In these modes the detector will not respond to a slow heat response
temperature increase - even if the temperature reaches
3 2.8 0.16 Low Multisensor 20
a high level. A large, sudden change in temperature can,
however, cause an alarm without the presence of smoke if 4 4.2 0.24 2.1 Multisensor 20
sustained for 20 seconds. 5 † No response See Mode 5 †
Heat A1R 15
to smoke
Additional heat sensor information
Characteristics of the response modes
The Discovery Optical/ Heat Multisensor detector incorporates
additional temperature information intended for use in signal The processing algorithms in modes 1 to 4 incorporate drift
processing. compensation. The characteristics of the five response
modes listed above are summarised as follows:
Temperature data can be read separately by the control
panel* and used to validate an alarm signalled by the Mode 1 has very high smoke sensitivity combined with high
multisensor analogue value. An example of this would be heat sensitivity. This gives a high overall sensitivity to both
a high multisensor analogue value not accompanied by an smouldering and flaming fires.
increase in heat: this would indicate that an agent other than Mode 2 has a smoke sensitivity similar to that of a normal
smoke, e.g. steam, had caused the high analogue value. optical smoke detector. This mode is therefore equivalent
Electrical description to a standard optical detector. It is suitable for applications
in which wide temperature changes occur under normal
The Discovery Optical/ Heat Multisensor detector is designed conditions.
to be connected to a two wire loop circuit carrying both data
and a 17 V to 28 V dc supply. The detector is connected to the Mode 3 has moderate smoke sensitivity combined with a
incoming and outgoing supply via terminals L1 and L2 in the moderate sensitivity to heat. This combination is considered
mounting base. A remote LED indicator requiring not more the optimum for most general applications since it offers
than 4 mA at 5 V may be connected between the +R and -R good response to both flaming and smouldering fires.
terminals. An earth connection terminal is also provided. Mode 4 has lower than normal smoke sensitivity combined
with high heat sensitivity. This makes it suitable for
applications in which a certain amount of fumes or smoke is
considered normal.
Mode 5† has no smoke sensitivity at all but gives a pure heat
detector response meeting the response time requirements
for a Class A1R detector in the European Standard EN 54-
5. In this mode the detector will respond to slowly changing
temperatures and has a ‘fixed temperature’ alarm threshold
at 58OC. The analogue value in this mode will give the
approximate air temperature over the range 15OC to 55ºC.
In Mode 5 the smoke sensor is still active though it does not
contribute to the analogue signal. As a consequence, if the
detector is used in a dirty or smoky environment the optical
sensor drift flag may be activated in the heat only mode.
PP2609/2019/Issue1
Page 3 of 4

Notes:
Discovery Optical/Heat Multisensor detector
1. *This applies only to the control panels that have been dimensions
programmed to read the additional information.
Address Card 38531-771
2. In-situ testing of a multisensor detector should be done supplied loose with base

as for smoke detectors in response Mode 2 and for heat


detectors in response Mode 5. Both optical and heat modes
should be tested in Modes 1, 3 and 4.

4.50

9.00
3. If the multisensor detector is to be used in Mode 5, heat
detector spacing/coverage should be applied.
Flashing LEDs
Fixing slot details

Discovery Optical / Heat Multisensor detectors have two


integral LED indicators, which can be illuminated at any
50.80

72.00

time by the fire control panel to indicate detectors in alarm.


A flashing LED mode can also be programmed to activate 42.00

each time a detector is polled.


110.00 Hand removal dimension

Remote test feature


The remote test feature is enabled from the fire control
panel. On receipt of the command signal from the fire
control panel, the detector is forced electrically into alarm.
An analogue value of 85 is returned to the fire control panel
to indicate that the detector is working correctly.
Rejection of transient signals
Discovery detectors are designed to give low sensitivity to
very rapid changes in the sensor output, since these are
unlikely to be caused by real fire conditions, resulting in
fewer false alarms.
Drift compensation
Discovery Optical / Heat Multisensor detectors include
compensation for signal drift to compensate for changes
in the sensor output caused, for example by dust in the
chamber, and will therefore hold the sensitivity at a
constant level even with severe chamber contamination.
This increased stability is achieved without significantly
affecting the detectors sensitivity to fire whilst still meeting
the requirements of the EN54 standard.
EMC Directive 2014/30/EU
The Discovery Optical/Heat Multisensor detector complies
with the essential requirements of the EMC Directive
2014/30/EU, provided that it is used as described in this data
sheet.
A copy of the Declaration of Conformity is available from
Apollo on request.
Construction Products Regulation 305/2011/EU
The Discovery Optical/Heat Multisensor detector complies
with the essential requirements of the Construction Products
Regulation 305/2011/EU.
A copy of the Declaration of Performance is available from
Apollo on request.
PP2609/2019/Issue1
Page 4 of 4

This page has intentionally been left blank


Optical / Acoustical Indicators

LF20W – Fire Alarm Panel


• Power Supply: 18V-30V
• Sound power (Max) 92 dB(A) @ 1m
• High Sound Level Buzzer
• Selectable Buzzer
• New Design, Less Thick
• Wall Mounting
• EN 54-3:2001 + A1:2002 + A2:2006

LF20W is an audio warning panel, available in different models and suited for any emergency situation such as fire,
flooding, gas leaks, etc., where audio information is needed. Its special design, very pleasant is particularly suited for
hotels, shops, malls and cinemas.

Technology and Design


Thickness
A special light diffuser guarantees the uniform lighting of the panel’s label. A
14mm
high sound level buzzer ensures an efficient acoustic warning in case of
alarm, granting the compliance to the norm UNI EN54-3.
The label inside the panel is provided with the standard sentence “FIRE
ALARM”, but labels with different messages and languages are available as
accessory. Thin and special design make LF20W warning panel unique for
technology and efficiency.

2852

General Specifications
Product code LF20W (Wall mount model) Sound power (min) 79 dB(A) @ 1m
Material ABS + PMMA Sound power (max) 92,3 dB(A) @ 1m
Installation Wall mount Buzzer frequency 2,8Khz
Nominal Voltage: 24 Vd.c. Sound model Pulsed, 1Hz (500ms on,
Absorption 21mA (average) 500ms off)
Protection Class IP21C*
Type of connection With terminals
Dimensions with backbox 292x130x55mm (L x H x P)
Operating temperature Da -10°C a +55°C

*Using conduits DX54216, DX43220 o GW52004

www.synaps-technology.com
info@synaps-technology.com
Synaps Technology S.r.l. – Via pietraferrata 9/1, 34147 – Trieste (Italy) 2020-10-01, TSD-FOP00-21A
Optical / Acoustical Indicators

Assembly instructions

- Make four holes into the wall to fit the holders (1, fig 2)
- Fix the mounting box with the four screws (2, fig 2)
- Connect the power supply to the terminals (Figure 1)
- If the sounder is not needed, connect jumper SILENT (Figure 2)
- Fix the central part to the mounting box with the four screws (3, fig 2)
- Hook the cover and screw it (4, fig 2)

Figure 1 Figure 2

www.synaps-technology.com
info@synaps-technology.com
Synaps Technology S.r.l. – Via pietraferrata 9/1, 34147 – Trieste (Italy) 2020-10-01, TSD-FOP00-21A
JE-H(St)H FE180 E30-E90 JE-H(St)H ..Bd FE180 E30-E90

09 Bezhalogeni instalacijski kabel za industrijsku elektroniku, poboljšanih


norme: DIN VDE 0815

svojstava za slučaj požara, s očuvanom el. funkcionalnošću između 30 i 90 minuta

J - instalacijski kabel
FE180: IEC 60331, DIN VDE 0472 dio 814
E30-E90: DIN VDE 4102 dio 12

E - za elektroniku
H - bezhalogena izolacija
kabeli bez halogena

(St) - elektrostatički zaslon od plastično-metalne folije


Telekomunikacijski

H - bezhalogeni plašt
..Bd - použen u svežnjevima
FE180 - očuvanje izolacijskih svojstava kabela u požaru 180 minuta
E30-E90 - očuvanje električne funkcionalnosti sustava u požaru između
30 i 90 minuta, ovisno o tehnici instalacije

ø Tehnički podaci Konstrukcija


Granični temperaturni uvjeti: 1. Vodič: bakreni goli vodič punog presjeka, promjera 0,8
• pri polaganju i s pomicanjem: -5 °C do +50 °C mm
• fiksno ugrađeni: -30 °C do +70 °C 2. Izolacija: umreženi (unakrsno povezani) polimer bez
halogena (kod nekih proizvođača i liskunska traka kao prvi
Radni napon: maks. 225 V (kabel nije predviđen za jaku
sloj izolacije visokih vatrootpornih svojstava, eng. mica
struju i instalaciju za napajanje)
tape)
Ispitni napon:
• po dva vodiča uvijena su u paricu, svake četiri parice
• žila - žila: 500 V použene su u svežanj, a svežnjevi su použeni u slojeve
• žila - zaslon: 2000 V • svežnjevi mogu biti označeni omotanim numeriranim
Otpor petlje pri 20°C: 73,2 Ohm/km za vodič promjera 0,8 mm filmom
Otpornost izolacije: 100 MΩxkm • kodiranje žila bojom definirano je prema DIN VDE
Radni kapacitet: (pri 800 Hz) max. 120 nF/km 1) 0815 za industrijske elektroničke kabele - osnovnom
1)
Ova vrijednost može se povećati za 20%, za kabele do 4 parice
bojom izolacije te bojom i grupom prstena na izolaciji
(pogledajte str. 349 u katalogu)
Kapacitivna sprega K1: (pri 800 Hz) 200 pF/100m
3. Separator: PEPT - plastična traka od poli(etilen/propilena)
Induktivnost: oko 0,65 mH/km
ili poliesterska traka
Linearno prigušenje: (pri 800 Hz) oko 1,2 dB/km
4. Elektrostatički zaslon (St): aluminij-laminirana
poliesterska traka i pokositreni bakreni kontaktni vodič
Svojstva kabela u požaru: promjera 0,8 mm (presjeka 0,5 mm2)
Samogasivost (flame retardant): prema IEC 60332-1 / 5. Plašt: umreženi (unakrsno povezani) termoplastični
EN 60332-1 (prije EN 50265-2-1) / VDE 0482-332-1 poliolefinski spoj bez halogena koji usporava gorenje,
Bez širenja plamena u okomitom snopu kabela (no HM2 prema HD 604 S1 i VDE 0207 dio 24
flame propagation): prema IEC 60332-3 kat. A / EN • boja plašta: narančasta
50266-1,-2 / DIN VDE 0482-266-2-4 (isto kao DIN VDE 0472
dio 804 test metoda C)
Bezhalogenost: prema IEC 60754-1 / EN 50267 -1,-2-1 /
DIN VDE 0482-267 -1,-2-1 (isto kao DIN VDE 0472 dio 815)
Nekorozivni plinovi izgaranja: prema IEC 60754-2 / EN
50267-2-2 / DIN VDE 0482-267-2-2 (isto kao DIN VDE 0472
dio 813)
Niska gustoća dima: prema IEC 61034-2 / EN 61034-2
(prije EN 50268) / DIN VDE 0482-1034-2 (isto kao DIN VDE
0472 dio 816) - vidljivost > 70%
Očuvanje izolacijskih svojstava u požaru, bez kratkog
spoja (insulation integrity) FE180
• vatrootpornost: prema IEC 60331 / EN 50200 / DIN VDE
0482-1 (isto kao DIN VDE 0472 dio 814) - na temperaturi od
800 °C, 180 minuta
Očuvanje električne funkcije sustava u požaru (circuit
integrity) E30-E90: prema DIN 4102 dio 12, 30-90 minuta

164
09

kabeli bez halogena


Telekomunikacijski
Primjena
Bezhalogeni instalacijski kabel za industrijsku elektroniku s poboljšanim svojstvima za slučaju požara, upotrebljava se unutar sustava za
mjerenja, podatkovnih i upravljačkih sustava. Elektrostatički zaslon štiti prijenosne krugove od vanjskih ometajućih elektromagnetskih
utjecaja.
Primjereni su za fiksnu instalaciju unutar suhih ili vlažnih prostorija, gdje u slučaju požara treba zaštititi ljude i materijalna dobra. Prepo-
ručljivi su za javne i industrijske objekte u kojima se okuplja puno ljudi i za objekte visoke materijalne vrijednosti.
Ne smiju se polagati direktno u zemlju niti u vodu, nisu za vanjsku uporabu (osim uz primjerenu zaštitu od sunca), nisu predviđeni za
napajanje.
Kabel je siguran prema testu od 180 minuta - izolacija ostaje cjelovita kod utjecaja otvorenog plamena za vrijeme testnog perioda od
180 minuta.
Očuvana funkcionalnost 30 ili 90 minuta ovisi o tehnici instalacije.
E30: Kabel omogućava funkcionalnost sustava u trajanju od 30 minuta u slučaju požara, što ljudima i životinjama omogućava spašava-
nje iz zgrade koja gori. 30 minuta omogućava funkcionalnost alarmnih sustava, nužne rasvjete, dizala za putnike za slučajeve evakuaci-
je izuzev kabela koji su instalirani unutar ljestvi za okna i strojarnicama.
E90: Kabel omogućava funkcionalnost sustava u trajanju od 90 minuta u slučaju požara, u podmorskim postajama pod povećanim
tlakom da bi se izbjegao dim i povećanje temperature na sigurnosnim stepenicama i unutarnjim prostorijama, ljestvama za okna i
strojarnicama, za dizala za vatrogasne brigade, te u dizalima u bolnicama.
Prednosti:
• bez halogena, bez ispuštanja otrovnih i korozivnih plinova u slučaju požara
• reducirana pojava dima u slučaju požara
• ne širi plamen u okomitom snopu kabela, teško zapaljiv
• očuvana električna funkcija sustava u zadanom vremenu

Dimenzije - broj žila x Vanjski promjer Debljina izolacije Požarno opterećenje Težina Cu Težina kabela Pakovanje*
promjer vodiča
nazivno približno nazivno približno
N x mm mm mm kWh/m kg/km kg/km
1 x 2 x 0,8 5,5 0,3 0,095 15 40 REZ
2 x 2 x 0,8 6 0,3 0,123 25 56 REZ
4 x 2 x 0,8 8,7 0,3 0,21 45 96 REZ
8 x 2 x 0,8 13,7 0,3 0,52 85 218 REZ
12 x 2 x 0,8 14,6 0,3 0,58 126 270 REZ
16 x 2 x 0,8 16 0,3 0,69 166 337 REZ
20 x 2 x 0,8 18 0,3 0,80 206 403 REZ
32 x 2 x 0,8 21,8 0,3 1,02 326 570 REZ
40 x 2 x 0,8 25,3 0,3 1,38 407 739 REZ
52 x 2 x 0,8 27,6 0,3 1,59 529 906 REZ

*) Pakovanje: REZ = kabel je u različitim duljinama na bubnju ili špuli i moguće ga je rezati na željenu duljinu

165
EQPT SPECIFICATION / DATA SHEET (5)

PASTOR INŽENJERING d.d.

CUSTOMER APPROVAL CODE

1 REJECTED

2 APPROVED WITH COMMENTS

PROJECT: K371
EMPLOYER INA Industrija Nafte, d.d. 3 APPROVED WITHOUT COMMENTS
PROJECT TITLE Rijeka Refinery Upgrade Project

M.R. N° K371-350-000-MR-1900-02 4 FOR INFORMATION ONLY

P.O. N° 200-OR-EG-21211

Equipment: GAS EXTINGUISHING SYSTEM (NOVEC) U.O.: KT S.p.A

VR Doc. CODE: A1001 BY: DATE:

KT Doc. CODE: K371-350-000-MR-1900-02-A1001-0001 Rev: 0


XLS - MOD-VDL - Rev.1

1 13.03.2022. Issue for review


0 7.03.2022. Issue for review
Revision
Date Reason for Issue - Revision Description
Index
Number of
Pos. Title Note
Pages

1 C_22-22080-600_i_1 1 PDF document in attach


2 C_22-27222-140_e_1 1 PDF document in attach
3 C_22-27242-140_g_1 1 PDF document in attach
4 C_22-32510-200_s_1 1 PDF document in attach
5 C_22-37870-356_g_1 1 PDF document in attach
6 C_22-37880-406_n_1 1 PDF document in attach
7 C_22-37880-407 1 PDF document in attach
8 C_22-37880-407_g_1 1 PDF document in attach
9 C_22-37880-442_b_1 1 PDF document in attach
10 C_22-37880-501_a_1 1 PDF document in attach
11 C_701-22-27222-141_a_1 1 PDF document in attach
12 C_701-22-37880-400_0_1 1 PDF document in attach
13 C_701-22-37880-406_b_1 1 PDF document in attach
14 C_701-22-37880-501_c_1 1 PDF document in attach
15 El1_DS58-Syncro-XT-datasheet-6-18 3 PDF document in attach