Module 7.2

Application
of
Transformers
Module 7.2 Application of Transformers

Shell Global Solutions

Specifying Transformers

• The DPU design called for 2 off 6.3 MVA 33/6.6 kV


transformers
• These are to be specified for procurement by data requisition
sheets
• In this session you will complete the data requisition sheets for
these units as if for quotation and purchase

Module 7.2 Application of Transformers

Shell Global Solutions 2

1
Shell Global Solutions

Data requisition Sheet


Transformer Conditions
• Temperature 40°C unless otherwise stated
• SC withstand 2 Secs. nominal
• 7.15% Dep for 6.3MVA
• Dyn 11 for 6.3MVA
• Provide for fans only over 10MVA
• 6.3MVA 6.6 kV cable to be sized

Module 7.2 Application of Transformers

Shell Global Solutions 3

Shell Global Solutions R equisition s heet for Design book N o. : page:


POW ER TR AN S F OR MER S C ontr. job N o. :
M ESC N o. : 65
R EQU IR EM EN TS A N D C ON D ITION S PR IM A R Y TER M IN A TION
Specific ation : DEP 33.65.40.31-Gen. Ov erhead lines : n /a x x mm2
Location : o u td o o r s /indoors Bus bars : n /a x x mm
M ax im um tem perature : 40/ ºC C able -ty pe : X L PE / SW A / PVC
Duty : g en eral ser vice /generator unit/ - data : 1 x 3 x 120 mm2
m otor unit/Korndorfer Dia, ov erall/ov erlead : 91 mm/ n /a mm
R ated pow er : 6300 kVA C able box filling : air/
R ated prim ary v oltage : 33000 V C able entry : sleev e/ g lan d /cone
R ated s econdary v oltage : 6900 V C T s required : n o /y es (attachm ent )
N um ber of phases : 3
F requency : 50 Hz SEC ON D A R Y TER M IN A TION
Short circuit lev el : 1500 M VA at prim ary side Ov erhead lines : n /a x x mm2
Short tim e w ithstand capability : 2/ s Bus bars : n /a x x mm
Im pedenc e v oltage : as per IEC 76/ 7.15 % C able - ty pe : EPR in su lated -PVC sh eath ed , u n arm o u r ed
C onnec tion Sy m bol : Dy n 11/ - data : 3 x 1 x 400 mm2
T y pe : o il im m ersed /dry Dia, ov erall/ov erlead : 42 m m / n /a mm
T ank enclosure : sealed /b reath in g C able box filling : air/
F illing : o il, Diala Dx /Bx /Sy nthetic liquid C able entry : sleev e/ g lan d /cone
Aux iliary supply : n /a V, ph+n, Hz Size of neutral earthing gland: EPR in su lated -PVC sh eath ed , u n ar m o u red 1 x 400
Alarm /trip s upply : d c /ac, 110 V, Hz C T in neutral to earth conn.: yes 600 / 1 A/no
T y pe of c ooling : ON AN / Other C T s required : n o /y es (attachm ent )
T em perature indicator w ith 2 contacts : no/ yes
M ounting : skid/
Enclosure for dry ty pe : no/ n /a
Surge arres ters required : no/ yes (attachm ent )

ON -L OA D TA P C H A N GER
R equired : no/ yes
R em ote c ontrol panel : yes /no
T apping range : + 10 / - 10 %
T apping s teps : 1.25/ %
Parallel operation : yes /no
R eference v oltage (VT s ec) : 110 V
SPEC IA L R EQU IR EM EN TS A N D R EM A R K S R EM A R K S ON R EVISION S
Module 7.2 Application of Transformers

Shell Global Solutions 4

2
Shell Global Solutions Part of Standard drawing S 68-022

Module 7.2 Application of Transformers

Shell Global Solutions 5

Shell Global Solutions

Summary

Having reached the end of this session you have now learnt how to:

• Specify a transformer

Module 7.2 Application of Transformers

Shell Global Solutions 6