Professional Documents
Culture Documents
1.0 PURPOSE
2.0 SCOPE
The requirements listed in this Chapter apply to GM owned and managed facilities
globally. Applicable local regulations may supersede the GM standards.
3.0 STANDARDS
Design and install emergency egress components to meet applicable laws and
regulations. Design new facilities to allow for prompt egress.
Do not interrupt the path of travel along a means of egress by any building element
other than a component of the means of egress.
3.1.1 Aisles
3.1.2 Exits
1
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
In new office buildings with two or more floors, provide at least two means of exit,
remote from each other, for each floor. These exit pathways must include fully
enclosed fire-rated stairways leading directly to the outside.
3.1.3 Stairs
Arrange stairs and other means of exit to clearly identify the direction of egress to a
public way.
3.1.4 Lighting/Power
For one or two story non-manufacturing buildings that meet the following criteria:
one or two stories
non-manufacturing
non-warehousing
stand alone – not part of a campus
limited or no security presence
3.1.6 Signage
Provide visible exit signs and exit lighting as necessary to direct employees toward
exits.
2
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
Prominently display the telephone number to call for assistance in the event of fire
or other emergencies on or near each facility telephone to ensure a prompt
response is obtained.
3
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
Establish a written hot work permit process at each facility. Hot work includes
welding, cutting, grinding, or similar processes. The permit system must be under
the control of Security.
Permit procedures also apply to new building construction activities and demolition
activities.
Before welding or cutting is permitted, the individual issuing the permit must
inspect the area in which cutting or welding is to be performed and determine the
hazards and the precautions to be taken.
The inspection must also verify that the cutting and welding equipment to be
used is in satisfactory operating condition, and in good repair.
Prior to issuing a permit where flammable liquids are stored, dispensed, handled
and/or sprayed, approval from a security supervisor must be obtained. Additional
precautions for a paint spray booth permit must be developed at the local level.
The permit must indicate the area and type of operation for which it applies. If the
welding or cutting operation is moved from the original area, a new permit must be
obtained for each new location.
Each person welding or cutting must be issued a separate permit. The individual
must be present for the inspection prior to the permit being issued and the permit
must be issued directly to the person welding or cutting.
The permit must expire upon completion of the job at any one location. If work at a
location continues for more than one shift, a new permit must be issued for each
shift.
4
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
OR
Sprinklers are out of service in the area and available alternative means of
protection are insufficient.
See General Motors FPG-28 Hot Work - Cutting, Welding, and the Allied
Processes Guideline and FPG-18 Fire Prevention & Protection for Roofing
Operations Requiring Open Flame Guidelines for guidance.
Establish a program which includes procedures for the inspection, testing and
maintenance of fire protection related equipment and devices at each facility.
Document all inspection, testing and maintenance schedules and results, with
records retained in accordance with GM Information Lifecycle Management (ILM)
retention schedules and local code requirements, if applicable.
Ensure the fire protection inspection, testing and maintenance program includes
the equipment and system components identified below. Guidance on additional
fire protection equipment inspection, testing and maintenance may be found on the
GM Global Security Fire Guidelines website.
Establish a regular inspection procedure to ensure fire barrier partitions and fire
walls remain continuous and intact.
5
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
Visually inspect Heat and smoke vents annually to ensure their functionality.
Conduct weekly fire pump testing. Pumps must be automatically started and
arranged for manual stop.
Maintain the fire protection mains, including hydrants, free of obstructions and in
proper operating condition.
Visually inspect system control, sectional control, fire pump, water supply and all
other fire protection valves two inches (51 mm) or larger at least weekly (monthly if
locked or supervised) to ensure they are in the normal position and properly
maintained.
Test each wet pipe sprinkler system quarterly at the inspector’s test connection to
assure the waterflow alarm device is functioning properly and the signal is received
at the alarm system control station.
On a quarterly schedule, inspect each fire hose location and roof hose cabinet to
ensure all equipment is in place, there are no obstructions and the hose has not
been damaged.
6
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
Test the following initiating and transmitting devices to assure the alarms are
received at the proprietary alarm console:
Waterflow alarms – quarterly
Supervised valves – semi-annually
Manual pull alarms – annually
Smoke/Heat detectors – annually
Inspect and test the site fire truck on at least a weekly basis.
3.7 Smoking
7
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
floor markings to indicate the extent and nature of the hazard. Develop written
smoking regulations for each facility.
3.8 Housekeeping
Remove all combustible waste, rubbish, debris, and other trash material from work
areas as soon as practical and do not allow these materials to accumulate.
Establish an incipient stage fire brigade for each General Motors manufacturing
facility. Structural fire brigades are required for any General Motors manufacturing
facilitiy if the public fire response is insufficient.
8
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
Immediate notification (within one hour) should be made to the Global Security
Staff for the following:
Any major fire protection impairment impacting site water supply capability, special
hazard processes, or sprinkler coverage for more than eight sprinkler systems,
must be reported by telephone to the Global Security Staff within 24 hours of
occurrence;
Follow all telephone notifications with the submission of a GMGS Incident Form.
(See INVG-03-A3 Notification & Reporting Template) Local reporting procedures
relative to divisional, group or subsidiary practices must also be followed.
Applicable standards throughout this Chapter also apply during construction and
demolition activities. See the operations guideline SECG-12 Site Security During
New Construction for additional information.
Assign a Security person to ensure fire prevention and protection requirements are
adhered to by the contractors. This individual will also support the GM
Construction Managers in overseeing the installation of fire protection such as
underground fire main installation, sprinkler systems, etc.
9
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
The fire safety program is the responsibility of the General Contractor and must be
included in the contract or purchase order agreement.
4.0 RECORDS
5.0 REFERENCES
FPG-28 Hot Work - Cutting, Welding, and the Allied Processes Guideline
FPG-18 Fire Prevention & Protection for Roofing Operations Requiring Open
Flame Guideline
FPG-19 Fire Protection – Detection System Impairment Management Guideline
7.0 DEFINITIONS
10
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
8.0 APPENDIX
8.3.1.2 Exits
For new construction, two exits are desirable for high hazard rooms such as the
following:
Engine Test Cells
Engine Test Cell Enclosure
Engine Hot Test Areas
Flammable Storage Rooms
Flammable Dispensing and Mixing Rooms
Liquid Spray and Powder Coating Finishing
Dipping and Coating Operations
Diagrams should clearly identify emergency routes from the building and to
designated shelter areas. This may be accomplished by the use of floor plans or
workplace maps that clearly show the emergency escape routes. Color-coding
may aid employees in determining their route assignments.
11
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
Notification Appliances
Audible devices should be of the speaker type and be sized appropriately for the
application.
The system should be designed to a sound level at least 15 decibels above the
average ambient noise level taken over a 24-hour period using a calibrated testing
device.
Evacuation Signal
Voice Communication
12
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
All speakers should be designed for use with the specific fire alarm system and
electrically supervised.
The public fire service should be invited to visit the facility on an annual basis to
coordinate their response plans and standard operating procedures with the
facility’s Emergency Response Plan. The public fire service should also be made
aware of site processes and high hazard areas. The establishment of staging
areas and diagrams for the public fire service use is recommended. Simulated fire
responses by the public fire service and other surrounding communities can
provide beneficial planning information.
In areas where the public fire service has limited resources, the local facility should
assure that appropriate mutual aid agreements with neighboring public fire service
agencies exist. A close working relationship should be established between
appropriate facility personnel and the public fire service.
Observation should be made to assure that vents are not wired or bolted shut and
linkage mechanisms are free to operate quickly in the event of an emergency.
Powered vents may be designed to operate upon sprinkler water flow. In such
cases, operation of the vents should be verified while conducting waterflow alarm
testing.
13
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
All diesel-driven fire pumps should be automatically started at least weekly and
operated for at least 30 minutes. Electrically driven fire pumps should be
automatically started weekly and operated for a minimum of ten minutes.
The underground loop or ring main, including all hydrants, should be flushed
annually. Hydrant houses should be sealed or, if located outside the fenced area,
equipped with locks. Emergency responders should be given key access. Hydrant
houses should be inspected at least monthly to ensure all equipment is available
and maintained in good condition.
Each dry pipe valve should be tested, cleaned and reset annually during warm
weather.
A periodic review of the sprinkler piping and heads throughout the facilities should
be conducted. Bent piping, broken hangers, damaged sprinklers, etc., should be
corrected. Sprinklers coated with paint overspray should be replaced. Sprinklers in
paint spray booths, flow coaters or other flammable or combustible coating
operations should be covered and the coverings replaced frequently so that heavy
deposits of residue do not accumulate.
14
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
agreed upon by site management, site security personnel and reviewed with the
local responding fire service, if required.
The site should have an effective method of alerting fire brigade personnel and
indicating the area of the fire.
Composition
A fire brigade should be maintained for each shift at assembly, manufacturing and
warehousing facilities. The majority of fire situations occur when the site is
occupied. However, the fire brigade should be of sufficient size to respond to
emergency situations at any time.
The composition and level of training of the brigade will vary from location to
location. The basic nucleus of a volunteer brigade should include security
personnel, maintenance employees, and others as may be necessary. Brigades
may be composed of both primary and secondary members. Primary brigade
members are defined as being directly involved in fire suppression activities.
Secondary members are not directly involved in fire suppression activities. Their
duties may include traffic and crowd control, utilities control, manning of valves and
monitoring of fire pumps.
Training
All primary and secondary fire brigade members should receive training
commensurate with the functions that they are expected to perform. These
15
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
Composition
Each shift should include a minimum of five personnel trained as structural fire
brigade members. One of these designated personnel should be the leader. The
fire brigade members should perform security or other fire-related duties when not
responding to fires. Support personnel trained at the incipient level may be
required to perform non-structural fire fighting.
The personal protective equipment for structural fire brigade members should be in
accordance with the local fire fighting codes or regulations.
Equipment
Fire Ladders - Ladders intended solely for firefighting purposes, and so identified,
should be placed in suitable and readily accessible places throughout the site or
carried on the fire truck. Locks, seals or similar security devices should be used to
prevent the use of these ladders for purposes other than fire fighting.
In-plant fire trucks may be needed for use by fire brigade personnel. One or more
in-plant vehicles should be provided at large facilities
The following decision tree may be used to determine the appropriate level of fire
brigade for a given facility.
* NOTE: For the purpose of applying this decision tree, a large warehouse is
defined as any warehouse of greater than 500,000 ft2 (46,452 m2).
16
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
Decision Tree.docx
Fire and security patrols should be made on a frequent basis during non-
construction periods and when particular hazard areas are noted.
General Requirements
17
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
O. Sufficient quantities of fire hose, to easily reach all parts of the building,
field offices, storage sheds, or piles of stored material should be
provided.
18
Fire Prevention and Protection Section
Chapter 1- Safe Work Environment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 6 Jim Ellis 09/29/09
S. Legible signs should be placed above all job telephones listing the
emergency telephone numbers.
19
Fire
Emergency
Yes
Yes
Manufacturing, Test Sites or
Large Warehouses
(>500,000 ft2, or 46,452 m2) Type of Offices or CC&A
Occupancy? PDC’s
Legal or Union
Requirements for Yes
Structural Fire
Brigade?
Structural Fire Brigade
Recommended
Yes Yes
Yes
No
Incipient Fire Brigade
Recommended
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
1.0 PURPOSE
This chapter provides fire prevention and protection standards and additional
information for the most common occupancies found within General Motors
facilities.
2.0 SCOPE
3.0 STANDARDS
Table 3.0-a
Table 3.0-b
Table 3.0-c
1
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Install and protect fluid Filling Operations in accordance with Chapter 3, Section
3.4.
Provide sprinkler protection for pits, exhaust ductwork and enclosures associated
with DVT operations.
Protection information and details are available in the Global Paint & Polymers
Center Bill of Process – 34950.D.
34950D Fire
Protection GTR_3.pdf
Storage arrangements beyond the above stated parameters and in areas where
extensive screen guard is installed, require a sprinkler density of 0.60 gpm/ft2
(24.4 lpm/m2) over any and the most remote 3,000 ft2 (279 m2) area of
application.
2
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Additional information and details are available in the Global Paint & Polymers
Center Bill of Process - 34950.D.
3.2.1 General
Do not permit Hot Work, such as cutting or welding, in paint operation areas
unless approval is given by a security supervisor. If Hot Work is required, ensure
it complies with Chapter 1, Section 3.4 of this manual. Additional information is
available on the GM Global Security Fire Prevention & Protection website, Fire
Guidelines web page, FPG-28 Hot Work - Cutting, Welding, and the Allied
Processes.
Provide properly grounded drip pans under all faucets. Also provide static
bonding between containers during transfer operations.
Install static grounding devices on any floor or platform where drums or other
containers are filled or emptied.
Ensure Class I and II liquids used in cleaning operations are in listed safety
containers. Ensure the ventilation system and all fire protection systems for the
spray booth remain on during cleaning operations. Limit cleaning operations to
not more than one gallon of flammable or combustible liquid for each cleaning
operation. Properly ground all equipment and personnel used in pressurized
spray cleaning operations.
3.2.3.1 General
3
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Provide storage rooms for paint materials that cannot be safely contained in
circulating and mixing systems or that cannot be properly stored elsewhere in the
plant.
Isolate storage rooms from work or warehouse areas by firewalls with a minimum
three-hour rating. Ensure walls dividing paint storage from paint mix areas have
a minimum rating of two hours. Maintain the integrity of fire walls or fire barrier
partitions by airtight filling of any abandoned or partially used openings to the full
wall thickness with materials having the same fire resistance rating as the wall.
Prohibit power operated trucks within storage rooms, unless they are listed or
approved battery powered units for hazardous areas. Equivalent requirements
may be considered upon acceptance of the authority having jurisdiction.
Protect all storage rooms with a wet pipe hydraulically designed sprinkler system
that is capable of discharging 0.60 gpm/ft2 (24.4 L/min/m2) for any and the most
remote 3,000 ft2 (279 m2) area of application.
Provide manual pull fire alarm devices located outside of and adjacent to
pedestrian doorways of the storage room.
4
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
3.2.4.1 General
Isolate dispensing and mixing rooms from work or warehouse areas by firewalls
with a minimum three-hour rating.
Ensure walls dividing paint mix from paint storage areas have a minimum rating
of two hours.
Install damage limiting construction on the exposed wall between the dispensing
and main plant area on a minimum designed basis of 100 PSF (488-kg / m2)
blast resistances.
Maintain the integrity of the fire wall or fire barrier partitions by airtight filling of
any abandoned or partially used openings to the full wall thickness with materials
having the same fire resistance rating as the wall.
Prohibit power operated trucks within mixing and dispensing rooms, unless they
are listed or approved battery powered units for hazardous areas. Equivalent
requirements may be considered upon acceptance of the authority having
jurisdiction
Where automatic sprinklers are the only form of protection, provide drainage in
accordance with Global Paint & Polymers Center Bill of Process - 34950.D.
3.2.4.3 Electrical
3.2.4.4 Ventilation
5
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Protect all dispensing and mixing rooms with a wet pipe hydraulically designed
sprinkler system that is capable of discharging 0.60 gpm/ft2 (24.4 L/min/m2) for
any and the most remote 3,000 ft2 (279 m2) area of application..
Provide manual pull fire alarm devices located outside of and adjacent to
pedestrian doorways of the storage room.
Ensure sprinkler protection is part of the building system. Design the sprinkler
system to provide 0.30 gpm/ft2 (12.2 L/min/m2) over 3000 ft.2 (279 m2).
Protect all process enclosures with a wet pipe sprinkler system hydraulically
designed for 0.30 gpm /ft2 (12.2 L/min/m2) over 3,000 ft2 (279 m2) or the area of
the enclosure whichever is less.
3.2.7.1 General
6
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Provide door exits in tunnel type booths on each side of the conveyor line,
spaced not more than 75-ft. (15-m) apart. Provide exits at each end of the booth.
3.2.7.2 Electrical
Protect the powder spray booth, robot rail enclosures, equipment closets and
non-automated zones with a pre-action sprinkler system.
Design sprinklers to provide a density of 0.35 gpm/ ft2 (14.2 L/min/m2) for the
entire booth area.
Diagram 4.xls
Ensure the automatic sprinkler system for each spray booth, including its
connecting exhaust system, is controlled by an accessibly located, plainly
identified valve.
Protect the bell station side cabinets with an automatic wet sprinkler system.
Protect interior exhaust ducts subject to powder residue with wet pipe sprinklers.
Interior supply plenums do not require sprinkler protection unless combustible
filters are utilized. Design the sprinkler system for a maximum of 40 heads
flowing 30 gpm (113 L/m) per head. Install heads not more than 12-ft. (3.7-m)
apart. Provide openings for access to each sprinkler head.
7
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Use only open head manual systems for exterior exhaust plenums and ducts.
Design the sprinkler system for a maximum of 40 heads flowing 30 gpm (113
L/m) per head.
Protect the powder storage room with an automatic wet sprinkler system. Design
the sprinkler system to provide a density of 0.30 gpm/ ft2 (12.2 L/min/m2) for the
affected area.
3.2.8.1 General
Protect all spray booths; flash off areas, side cabinets, exhaust systems and cat-
trac enclosures with a wet pipe automatic sprinkler system.
Design the sprinkler systems to deliver a density of 0.35 gpm/ ft2 (14.2 L/min/m2)
for the most remote, 3,000 ft2 (279 -m2) or the entire booth, whichever is less.
8
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Ensure the automatic sprinkler system for each spray booth, including its
connecting exhaust system, is controlled by an accessibly located, plainly
identified valve.
Protect interior exhaust ducts, eliminators, plenums and tunnels with wet pipe
sprinklers. Design the sprinkler system for a maximum of 40 heads flowing 30
gpm (113 L/m) per head. Install heads not more than 12-ft. (3.7-m) apart.
Provide openings for access to each sprinkler head. Design the system to limit
the number of sprinklers controlled by sub-valves in order to meet water supply
capabilities.
For all new or renovated paint spray booths, ensure the pipe and hangers
exposed to the exhaust stream are stainless steel.
Provide open head manual systems for exterior exhaust plenums, stacks, and
ducts. Design the sprinkler system for a maximum of 40 heads flowing 30 gpm
(113 L/m) per head. For water wash type booths, perform a biannual inspection
of these systems. Replace obstructed sprinkler heads as needed.
Where exhaust air is re-circulated to booth supply, apply the provisions of the
Global Paint & Polymers Center Bill of Process 34950.D.
Depending upon the type of paint application and paints employed, Logic
Diagrams Nos. 1, 2, or 3 must be applied for the protection features and
associated interlocks.
Protect dosing pumps and color changer enclosures with sprinklers fed by the
booth system.
3.2.10.1 General
9
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Locate oven heaters, other than those of steam type, a minimum of 20-ft. (6.1-m)
away from spray booths and paint storage and mix rooms.
Design and locate ovens to provide adequate space for proper functioning of
explosion vents, fire fighting accessibility, inspection, and maintenance.
Thoroughly evaluate the need for proper explosion relief of the drying chamber
and/or heating source with respect to the style of firing (indirect versus direct)
and the liberation of flammable vapors that may accumulate and/or approach
25% of the lower explosive limit if ventilation within the unit fails.
Construct ovens to minimize the transmission of solvent vapors through the inner
shell and the subsequent condensation of these vapors in the insulation section
between the inner and outer shells.
Equip ovens with access doors or openings and lights in adequate number and
size to permit inspection, maintenance, and fire fighting access. Ensure
distances between access doors and/or openings do not exceed 100-ft. (33-m).
Ensure oven ducts, insulation and covering materials are constructed of non-
combustible materials.
Provide a purge cycle consisting of at least four complete air changes of the oven
and heating chamber(s) prior to light-off of the oven. Prove this air purge by fan
motor/starter interlocks and airflow or differential pressure switches.
10
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
or,
Classify heated flash zones as ovens, and install protection features accordingly.
11
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Do not connect exhaust ducts from heated flash zone and spray operations
unless they are sprinkler protected and approved for the specific application.
Ensure all manifolding of exhaust ducts is downstream of exhaust fans. Ninety-
degree connections are not permitted.
Provide a closed head, wet pipe sprinkler system throughout the heated flash
zone and silhouetted vestibules on a hydraulically designed basis of 0.35 gpm/ ft2
(14.2 L/min/m2).
See Global Paint & Polymers Center Bill of Process 34950.D for details with
respect to these installations.
Perform paint spraying only in booths provided for that purpose. See Global
Paint & Polymers Center Bill of Process 34950.D for details with respect to these
installations.
12
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
3.4 Machining
Many machine enclosures contain oil lubrication systems, oil coolants, and/or
hydraulic oil systems. The enclosure prevents the ceiling level sprinkler system
discharge from reaching these hazards. Provide protection within the machine
enclosure if any of the following conditions exist:
Operations using mineral oil coolant with an enclosure size greater than
50 ft2 (4.6 m2).
3.4.2 Protection
13
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Insulation Material
Guidance for the selection of insulation materials for machine enclosures can be
found in the Appendix.
3.5 Stamping
Install sprinkler protection for the first floor level of contiguous stamping
operations, if required, in accordance with the local Authority Having Jurisdiction.
3.6 Warehousing
3.6.1 Separation
14
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
3.6.2.2 Smoking
Protection requirements for storage facilities of less than 500,000 ft2 (46,452 m2)
may be less than those specified elsewhere in this manual. Use Table 3.6.3-a to
determine the appropriate reference table for protection requirements.
Table 3.6.3-a
Locate interior hose stations equipped with 100 ft. (30 m) of 1-1/2 inch
(38 mm) hose and a combination nozzle or acceptable equivalent so that any
point in the storage area can be reached by two hose streams. Add 750 gpm
(2,839 L/min) to the water demand for hose streams.
15
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Fixed-Rack Storage
It may be necessary to add one additional level of in-rack sprinklers for rack
storage of exposed Group A plastic between 10 ft (3.1 m) and 25 ft (7.6 m).
Consult Global Security.
Protect bulk, palletized and portable rack storage of expanded Group A plastics
in accordance with Table 3.6.3.3-a.
table 3.6.3.3.a.docx
table 3.6.3.3.b.docx
Where the ceiling sprinkler density is less than 0.30 gpm/ft2 (12.2 L/min/m2) over
any and the most remote 4,000 ft2 (372 m2) area of application, limit storage
heights to 5 ft (1.5 m) and pile sizes to 500 ft2 (46 m2).
16
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Include 250 gpm (946 Lpm) hose allowance in water supply calculations for
systems using specific application sprinklers.
Where quick response sprinklers are installed (such as ESFR), separate these
sprinkler systems from other sprinkler systems with a minimum 3 ft (1 m) draft
curtain and a minimum 8 ft (2.4 m) clear aisle.
Where specific application sprinklers are used, follow the maximum pile sizes
indicated in Table 3.6.3.3-c.
table 3.6.3.3.c.docx
3.7 Offices
17
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
7.0 DEFINITIONS
18
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
8.0 APPENDIX
Automatic sprinkler protection for the dynamic vehicle test exhaust system
should be designed based on 20 sprinkler heads operating @ 30 psi, minimum
start pressure.
Based on actual fire testing results, the following fire protection arrangements are
recommended for areas where screen guarding is present:
OR
Screen guard with no storage below, and minimum 0.30 gpm/ft2 sprinkler
system at the ceiling: No additional sprinkler protection required.
1 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
OR
Screen guard with >10 ft. high storage below: Provide sprinklers under
the screen guard in accordance with the policies established in this
manual.
In all cases the screen guard with at least a nominal 2 in. x. 4 in. (51 mm x
102 mm) opening should not be blocked by materials, cardboard, plastic
sheets, etc.
Storage and/or dispensing of paint materials within the plant, but outside paint
storage, mixing rooms or storage cabinets should be limited to the amount
prescribed in NFPA 33 - Spray Application Using Flammable and Combustible
2 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
The following should be considered with regard to containers and portable tanks:
Approved drum pumps are recommended for handling small quantities of paint
materials.
All containers and portable tanks, when being emptied or filled should be visibly
grounded and bonded. Racks used in storing paint materials should be
grounded.
3 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Waste liquids, dirty rags, and other disposable media should be placed in
approved safety containers. These materials should be removed daily and
disposed of in a safe manner.
After using or emptying containers, all bungs and shut-offs should be
immediately replaced or closed. Empty pails, cans, and barrels are dangerous
due to the presence of explosive vapors. After emptying, containers should be
removed immediately to an approved storage area. Drums that have been used
for transporting solvents should be identified when emptied and to be returned.
Explosion venting is not needed unless local code requires venting, there is
dispensing of flammable liquids or the mix room and storage rooms are not
adequately separated with normally closed fire doors.
Dispensing and mixing rooms should be provided for paint mixing and dispensing
operations that are not permitted to be located elsewhere in the plant due to size
of the room and quantity of paint material as prescribed by Chapter 8, NFPA 33 -
Spray Application Using Flammable and Combustible Materials.
4 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
An emergency shutoff switch, to stop the paint mix and circulation systems,
should be installed outside the pedestrian doors.
All equipment (including insulated devices such as agitator covers, etc.), paint
material lines, racks, and containers and portable tanks should be visibly
grounded.
Circulating thinners and paint lines should be of steel, or other material having
comparable properties of resistance to heat and physical damage.
This section includes enclosures for the following operations: Sanding, Prep,
Blow-off, Feather Dusters (EMU), and Solvent wipe
Production welding operations should not be permitted within spray booths and
spray finishing areas and should not be located within 35-ft. (10.7-m) of openings
to spray booths or spray finishing areas.
Cutting or welding (Hot Work) or open flame (e.g. soldering) should not be
permitted within spray booths or spray finishing areas. All alternative work
methods should be considered. Prior to any welding, the booth should be free of
5 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
residue, and a safe operating plan should be developed. See Chapter 1, Section
3.4 for further information.
8.3.2.7.2 Electrical
The spray booth and all equipment, such as piping, conduit, lighting, fixtures,
motors, and switches installed in conjunction with same should be grounded.
Lighting fixtures in the spray booth should not be located where they are
continually and directly exposed to air laden with paint powder. Flush mounted
fixtures should be listed or approved dust-tight type with a high stress or wire
glass lens.
If lighting fixtures are located entirely inside the spray booth, they should be of
the explosion-proof type.
Re-lamping of fixtures should be conducted from outside the booth unless the
fixtures are listed Class II Division 1 or 2 equipment. Maintenance operations in
the booths should utilize rated electrical equipment. Portable units, cabling, and
receptacles should be listed for Class II, Division 1, Group G locations and
should not remain in the booth during spraying operations.
Ventilating equipment should provide the volume and velocity of air necessary to
contain and remove powder overspray.
Ample access doors should be provided in all ducts, stacks, and exhaust tunnels
for the purpose of cleaning, repairing, inspection and replacing of sprinklers and
manual fire fighting,
6 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Air exhausted from the recovery system of a powder operation should not be re-
circulated as input air for that operation unless:
Existing booths having extra hazard sprinkler protection need not be revised.
The automatic zones of the powder spray booth should utilize single frequency
infrared flame detectors. The robot rail enclosures, equipment closets, and any
non-automated areas protected by the preaction should utilize rate-compensated
thermal detectors. These thermal detectors should be rated at 140 deg. F (60
C).
Stacks over 6-ft. (1.8-m) in diameter or width may require sprinklers installed on
an individually engineered basis with approval by the authority having jurisdiction.
Global Security should be contacted for review. The system should be designed
to limit the number of sprinklers controlled by sub-valves in order to meet water
supply capabilities.
A separate water flow alarm should be installed for each spray booth and
connected to the plant proprietary alarm console.
7 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Circulating thinner and paint lines located outside the booth enclosure should be
of steel or other material having comparable properties of resistance to heat and
physical damage.
Glass panels in booth walls are not recommended. If viewing windows are
necessary, they should be of wired glass and of limited dimensions.
Door exits should be provided in tunnel type booths on each side of the conveyor
line. Exits should be provided at each end and spaced along each side not more
than 75-ft. (23-m) apart.
Electrical
Electrical equipment in spray areas and spray booths should conform to NFPA
70 - National Electric Code for Class I, Division 1, (Zone 1) Group D locations, or
local/regional equivalent.
The spray booth and all equipment, such as piping, conduit, lighting, fixtures,
motors, and switches installed in conjunction with same should be grounded.
Lighting fixtures in the spray booth should not be located where they are
continually and directly exposed to air laden with paint solvents. Flush mounted
fixtures should be listed vapor-tight type with a high stress or wire glass lens. If
lighting fixtures are located entirely inside the spray booth, they should be of the
explosion-proof type.
Re-lamping of fixtures should be conducted from outside the booth unless the
fixtures are listed Class I Division 1 or 2 (Zone 1 or 2).
The use of portable hand lamps or fixtures on movable stands in spray booths
should be avoided except where necessary for cleaning and other maintenance
operations. Such portable units, cabling, and receptacles should be listed for
8 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Class I, Division 2 (Zone 2), Group D locations and should not remain in the
booth during spraying operations.
Ventilation
Ample access doors should be provided in all ducts, stacks, and exhaust
tunnels for the purpose of cleaning, repairing, inspection, replacing of
sprinklers and fire fighting.
9 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Existing booths having extra hazard sprinkler protection need not be revised.
Central exhaust stacks over 6-ft. (1.8-m) in diameter or width may require
sprinklers installed on an individually engineered basis with approval by the
authority having jurisdiction. Global Security should be contacted for review.
A separate water flow alarm should be installed for each spray booth line and
connected to the plant proprietary alarm console.
All paint and thinner supply circulating to the booth (including specialty and
satellite systems) should be shut down automatically on activation of the booth's
fire extinguishing system(s). For additional interlock details, see the appropriate
“Process Fire Protection Systems Logic Diagram”.
Emergency manual paint and thinner pump shut down stations should be
installed outside booths and arranged so that the unobstructed travel distance to
each stop switch is not over 75-ft. (23-m) from each booth exit. A local
visual/audible alarm should be provided at each stop station.
Where the circulating thinner lines are located above the booth's paint stations,
spring loaded check valves should be installed in the thinner supply line at the
drop point prior to any plastic tubing. In addition, a regular or spring-loaded check
10 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
valve should be installed in the return at the point that the tubing reconnects to
the hard piping.
Air supply, exhaust, and sludge water removal systems should remain
operational when the booth is in use, occupied for maintenance functions, or in
the event of a fire incident. Additionally, activation of the fire protection
equipment in the paint booth, ductwork, filter houses or adsorption equipment
should permit direct exhaust (to atmosphere) of the air in the paint process. Any
abatement equipment should be by-passed. The thermal oxidizer should remain
running.
Fire Protection Process Criteria for Existing Facilities with Approved Equipment
(Diagram No. 1):
The following are additional fire protection requirements for U.L. Listed and/or
F.M. approved robotic waterborne non-electrostatic, non-robotic, non-rotary
spray equipment installations, including: non-electrostatic (Manual and
Automatic); electrostatic (Manual and Automatic); and non-electrostatic approved
robotic (Waterborne/Solvent).
Additional Fire Protection Requirements for this section are intended for the on-
going maintenance and repair of systems currently in use outside of Europe (See
Diagram No.2).
11 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
If the color changer is exposed to the booth deluge system (i.e. open top)
carbon dioxide (CO2) is not required within the enclosure.
Carbon dioxide cylinders, deluge valves including trim and fire control
panels should be located outside the booth (same floor as booth operating
level).
The following are additional fire protection requirements for new robotic and
rotary spray equipment installations:
12 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
the cabinets should be directed to the flood sheet with the exception of
hose retractor cabinets.
The activation of any one booth flame detector should cause a localized
interruption of the paint flow and an intermittent discharge of carbon
dioxide (CO2) (as long as the detector sees flame) through the paint
applicator. It is intended that this is the initial automatic fire protection
system to be activated in the spray booth. For timing sequence refer to
Diagram No.3.
Deluge water spray sprinkler protection should be provided for the booth
interior of each zone (each zone individually controlled). Design density
should be 0.60 gpm/ ft2 (24 L/min/m2). Detection should be by single
frequency, infrared flame detectors. Existing installations with combination
ultra-violet/infrared flame detectors are satisfactory; however, when
replacement of the detectors is required, single frequency infrared flame
detectors should be used. Deluge actuation is by cross-zoned optical
detectors after a 15-second delay has elapsed. If protected zones are
adjacent to each other, it may be necessary to simultaneously discharge
systems for more than one zone.
If the color changer is exposed to the booth deluge system (i.e. open top)
carbon dioxide (CO2) is not required within the enclosure.
Carbon dioxide (CO2) cylinders, deluge valves including trim and fire
control panels should be located outside the booth (same floor as booth
operating level).
13 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
All oven areas should be well posted with "No Smoking" signs.
Cutting and welding should not be permitted within ovens. Cutting or welding
within ovens should be in accordance with Chapter 1, Section 3.4. Approval is
required from a security supervisor.
and
Replace the sprinkler heads one bay or 30-ft. (9-m) (whichever is greater)
beyond the perimeter of the oven(s).
The use of high temperature heads is not limited to the ceiling sprinkler
system. Additional areas for consideration may include under walkways,
ducts, adjacent to heater boxes, etc
14 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Convection zones should use sprinklers with a rating 50ºF (10ºC) above
maximum expected air temperatures.
15 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
Insulation Material
For prefabricated wall and ceiling panels, panels listed in any of the
following categories are acceptable:
16 Appendix
Fire Prevention and Protection - Chapter 2
Occupancy Specific Protection
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 5 Jim Ellis 09/29/09
o Plastic curtains used for enclosure entrance or exit openings less than
10 ft2 (0.93 m2) may be non-listed ordinary type materials.
8.3.7 Offices
17 Appendix
GENERAL MOTORS PAINT FIRE
GENERAL TECHNICAL REQUIREMENTS PROTECTION
GM BILL OF PROCESS
Document Number.Rev: 34950.D
Fire Protection Technical Requirements
Owner: Paint
Date: 15AU08
Manufacturing Partition Codes: 63.00.00
BOM Row Number(s):
APPLIES TO: ALL GM PAINT SHOPS
Sequence No.:
LID NO.: 5040, 5110, 8100, 8200, 8300
Table of Contents
Topic Page
1. SCOPE ...............................................................................................................................................3
2. GENERAL ..........................................................................................................................................3
2.1. BUILDING CONSTRUCTION .............................................................................................................3
2.2. CONTRACTOR REQUIREMENTS ......................................................................................................4
2.3 FIRE PROTECTION INSTALLATIONS AND EQUIPMENT ........................................................................4
3. SPECIFIC DESIGN DATA .................................................................................................................6
3.1. GENERAL .....................................................................................................................................6
3.2. BUILDING SPRINKLER PROTECTION ...............................................................................................6
3.3. PHOSPHATE AND ELPO MACHINES ................................................................................................7
3.4. PROCESS ENCLOSURES ...............................................................................................................7
3.5. SPRAY BOOTHS ............................................................................................................................7
3.6. ROTARY ATOMIZER (ESTA) SPRAY BOOTH ZONES – FLAMMABLE PAINTS ...........................................8
3.7. ROTARY ATOMIZER (ESTA) SPRAY BOOTH ZONES – NON-FLAMMABLE PAINTS AND PURGE MATERIALS ..... 8
3.8. ROBOTIC ELECTROSTATIC SPRAY BOOTH ZONES ..........................................................................8
3.9. ROBOTIC NON-ELECTROSTATIC AND ELECTROSTATIC USING NON-FLAMMABLE PAINT .....................9
3.10. HEATED FLASH ZONE ...................................................................................................................9
3.11. DOSING PUMPS AND COLOR CHANGERS .....................................................................................10
3.12. HOSE RETRACTOR CABINETS ......................................................................................................10
3.13. FLASH TUNNELS / OVEN EXITS ...................................................................................................10
3.14. OVENS ......................................................................................................................................10
3.15. SPRAY ROOM – REPROCESSING OPERATIONS ONLY ...................................................................11
3.16. PAINT HOSPITAL – SPOT REPROCESSING....................................................................................12
3.17. LIMITED FINISHING W ORKSTATION ..............................................................................................12
3.18. CANOPIES, ENCLOSURES AND TUNNELS......................................................................................13
1 of 38 © 2008 GENERAL MOTORS CORPORATION 34950D
All rights reserved
When printed, this copy is uncontrollable. GM users should verify latest revision at http://paint.gm.com/facility.
Revision Status
Date: Change Control No.: Revision: Reason/Need:
15AU08 003-08 D 2008 Update
1. SCOPE
This document shall apply to all new and renovated GM paint shops.
This document is based on General Motors and Insurers requirements. Local legal
requirements that are more stringent shall be applied.
Exceptions to this document must be submitted to and approved by the responsible GM
operating group (GPPC, GME, LAAM, GMAP) and GM Global Security.
It is the responsibility of the contractor to follow all referenced standards, since this document
cannot be all-inclusive. Where not specifically outlined, if deviations may occur, the installation
shall be in accordance with the GM Fire Prevention and Protection Section of GM Global
Security Manual. Deviations to the Manual and this document shall be reviewed by GM Global
Security, in cooperation with appropriate Regional Security and Facilities Engineering
personnel.
Definitions:
Shall = indicates a mandatory requirement
Should = indicates a recommendation or that which is advised but not required
2. GENERAL
2.1. Building construction
Noncombustible construction is required for all buildings.
Insulation of roof and walls shall be with noncombustible materials in accordance with the
provisions of Chapter 3 of the General Motors Fire Prevention and Protection of the GM
Security Global Manual.
The following material should not be used or only after separate review and acceptance
2
1. Material with a bituminous content of more than 0,7 kg/m² (0.143 lb/ft ) shall not be used in
roof construction as a vapor barrier.
2. Foam material such as Polyurethane shall not be used as insulation material on roof and
wall constructions.
3. The wall or roof insulating material shall be generally in compliance with a Class A material
according DIN 4201. Only FM or UL listed panels shall be used.
Foamed plastic filled wall construction, for interior panels, modular panels and exterior side wall
shall have pass a Factory Mutual Full Scale Corner Test and be FM approved (or equivalent)
for use in sprinkler-protected buildings (as specified in the GM Global Security Manual, Chapter
3). The ASTM E-84 Tunnel test is not considered a relative test.
Roofing system shall be rated by UL as a “fire classified“ assembly or FM class 1 (for interior
exposure) with a UL listed class A roof covering (for exterior exposure). Equivalent ratings by
other recognized testing laboratories may also be accepted.
Gravity type Heat & Smoke Vents are not required according to GM standards. However, local
codes and requirements of local authorities having jurisdiction shall be considered, clarified,
3
and variances received as necessary. In addition, smoke removal at the rate of 0,45 m /min
2
per square meter (1.5 cfm/ft ) of floor area shall be accomplished by mechanical ventilation.
(See Chapter 3 of the General Motors Fire Prevention and Protection Section of the GM
Security Manual.)
2.2. Contractor requirements
The contractor shall be well experienced in NFPA fire protection installations. In addition, the
contractor must demonstrate, as a minimum:
adequate engineering capacity
sufficient manpower for installation
sufficient ability to service
three years minimum experience in installing fire extinguishing systems
Registration and approval as required by local authorities (in Europe registered by
local fire protection associations and ISO 9001 certified.)
To exhibit adequate experience and technical reliability the contractor should be prepared to
provide references upon request.
The contractor must guarantee adequate qualified manpower with appropriate experience in
installation of extinguishing systems, and that these employees will be in place during the fire
protection construction period. In addition, the job must have with a sufficient number of
supervisors for the job size who have adequate written and verbal skills.
All drawings and documents shall be submitted to XL GAPS for review and acceptance before
installation begins.
2.3 Fire protection installations and equipment
All equipment shall be listed and/or approved for its intended purpose by a recognized testing
laboratory such as Underwriters Laboratories (UL) or Factory Mutual (FM). Listed means
equipment, materials, or services included in a list published by an organization acceptable to
the authority having jurisdiction and concerned with evaluation of products or services that
maintains periodic inspection of production of listed equipment or materials or periodic
evaluation of services and whose listing states either that the equipment, material, or service
meets appropriate identified standards or has been tested and found suitable for a specified
purpose.
Sprinkler installation shall be based on the most recent edition of NFPA 13 - Standard for the
Installation of Sprinkler Systems.
Fire protection systems shall be protected to prevent piping damage in earthquake zones.
Earthquake zones shall be defined by a registered professional institution.
Building sprinkler systems shall be in full operational service before combustible material and/or
equipment is moved into the building.
The integrity of the fire protection system remains the responsibility of the contractor until final
acceptance of the system has been obtained. Prior to final acceptance, systems may be placed
in temporary service to provide some level of fire protection. During this period, operation of the
fire protection system shall be coordinated with site Security. The guarantee for a fire protection
system begins when final acceptance without deficiencies has been obtained.
Automatic sprinkler protection shall be provided for the entire building, including inside
concealed spaces, below platforms and other obstructions.
Sprinklers are required below all obstructions (e.g. platforms, ducts, closed conveyer or piping,
stairs, underneath grillage (gratings) that exceed 1200 mm (48 inches) in width. For small
obstructions the sprinkler system shall be designed according pipe schedule OH or XH (see
paragraph 4.8). For large obstructions the sprinkler system shall match the ceiling sprinkler
design and be hydraulically calculated.
The maximum base of riser pressure demand shall not exceed 6,1 bars (90 psi). An exception
to exceed 6,1 bars (90 psi) is allowed on an individual riser basis when all of the following
conditions are met: 1) the maximum base of riser pressure demand shall be calculated back to
the water supply, 2) the calculated pressure at the water supply shall not exceed 90% of the
actual available water supply at that point, and 3) the actual available water supply shall be
based on the current water supply test.
Each sprinkler system shall have an individual lead-in from the fire loop with a separate post
indicator valve (PIV) in each line. The building installation starts with the floor flange unless
otherwise stated in the contract.
Provide portable fire extinguishers of the appropriate type and quantity per NFPA 10 throughout
the building.
Inside hose stations connected to the sprinkler system shall be installed so that two hose
streams will reach any point. For details refer to Material Requirements.
Roof hose stations or hydrants shall be provided and arranged to reach designated hazard
areas of the roofs. Roof hose stations or hydrants are not required on roofs where there are no
penthouses, heater houses, spray booth stacks, etc.. The distance between roof hydrants shall
not exceed 90 m (300 ft).
Roof hydrants or dry pipe risers to the roof areas where required by the authority having
jurisdiction shall be provided with hose couplings on both ends, preferably placed in the
proximity of a yard hydrant.
Fixed access ladders, stairs, bridges or ramps of steel or aluminum, shall be provided so that
any level or area of the roof may be reached unabated. For new construction, stairs shall be
installed for access from ground level to the roof.
All water flow alarms shall be transmitted as a supervised signal to the facility alarm system.
Hose allowance for inside hose stations is 380 L/min (100 gpm) at the area of application for all
systems per NFPA 13.
Total hose allowance for hydrants and inside hose requires 1900 L/min (500 gpm) for 4-14
2 2
L/min/m (0.1 -0.35 gpm/ft ) and 2840 L/min (750 gpm) for all others added at the lead in
connection to the fire loop. A separate hydrant system shall not be used unless required by the
authority having jurisdiction.
Manual fire alarm stations shall be located inside and adjacent to emergency exits with a
maximum travel distance of 61 m (200 ft.).
The location of the extinguishers, manual fire alarm stations and inside hose reels shall be
reviewed and accepted by plant security.
Spray booth deluge and closed head sprinklers shall each be supplied independently of plant
ceiling sprinklers. The supply should encompass a two-way feed arrangement from the yard
main with the risers and sectional control valves arranged to minimize impairment potential.
A separate water flow alarm shall be installed for each spray booth and connected to the facility
alarm console. The spray booth ends at the exit of the scrubber section.
If field joining of the paint circulation piping outside the paint mix room relies on nonmetal
gaskets to prevent leakage, all primer surfacer, topcoat and solvent pumps shall be interlocked
with the building fire protection system to shut down in the event of a sprinkler discharge in the
vicinity of the paint circulation lines.
Emergency manual paint and thinner pump shut down stations shall be installed outside spray
booths and arranged so that the unobstructed travel distance to each stop switch is not over 23
m (75 ft.) from each booth exit. This shut down station shall be interlocked to provide an alarm
on the plant proprietary console. (See Process Fire Protection Systems Logic Diagrams in
Appendix C for additional shut down function requirements).
The sprinkler piping shall be identified with legends consisting of white letters set against a red
background of appropriate size to provide the maximum contrast and legibility. Preprinted pipe
marking systems may be used, provided they are of durable materials, are securely attached,
and meet the size and color requirements of this standard and applicable local requirements.
The maximum and minimum distance between sprinkler heads / branch lines shall be 3,66m
(12 ft) and 2,44m (8 ft) respectively. Sprinkler spacing and area of application in this document
are the maximum allowed.
2
Area of protection 4831 m² / alarm valve 52,000 ft / alarm valve
Temperature rating Ordinary (57-77 °C ) Ordinary (135-170°F)
Temperature rating High (121-149 °C ) High (250-300 °F)
above and around ovens
Due to Emergency cool-down procedure used for the ovens and possible building ventilation
failures the sprinklers above and around ovens shall be High Temperature Classification. This
zone should extend one bay or 9 m (30 ft.) whichever is greater. This should include under
walkways, ducts and adjacent to heater boxes.
3.3. Phosphate and Elpo Machines
Sprinkler protection is not required inside the phosphate and Elpo machines. This includes the
tunnels between phosphate and Elpo, between stages and up to the Elpo oven.
Sprinklers are required below these machines if the height is enough to allow combustible
storage.
General: In addition to the general requirements for spray booths, the following additional
protection is required. Note: For further discussions of the additional fire protection required,
refer to Appendix B, Section 6.
a) Booth sprinkler protection shall to be extended to cover the inside of the side machines and
support cabinets of the roof machines if located outside of the spray booth enclosure.
b) Special CO2 and Deluge protection are required as described below:
A two shot liquid CO2 system shall be provided to protect the side cabinets (including
those for the roof machine). The roof machine shall be protected by a two shot liquid or
gaseous CO2 system. A 34% concentration of CO2 shall be achieved within one minute
after agent release. Once a concentration of 34% is achieved, it must be held for one
additional minute.
A deluge system shall be provided as the final protection for the affected zone. IR
detectors shall be installed to provide overlapping coverage of the entire spray zone
with or without a vehicle present and regardless of the position of the automation.
Any one IR detector in the zone will activate spray shutdown in the zone. If after a 10
second delay there are two detectors in alarm the deluge shall activate.
Means for manual electrically operated release of systems are to be available on both
sides of the booth. Mechanical means for release are to be available at the deluge
valve and the CO2 storage tanks.
Interlocking and all other features are required as per “Logic Diagram 3” in Appendix C.
3.7. Rotary Atomizer (Esta) Spray Booth Zones – Non-flammable Paints and Purge Materials
This section applies to Waterborne Paints and Purge Materials determined to be non-burning or
non-self-sustaining burning using the triangle diagram from the PTB Institution W-57 Test.
In addition to the general requirements for spray booths, booth sprinkler protection shall be
extended to cover the inside of the side machines and support cabinets of the roof machines if
located outside of the spray booth enclosure.
Special CO2 and Deluge protection are not required.
Interlocking and all other features are required as per “Logic Diagram 1” in Appendix C.
3.8. Robotic Electrostatic Spray Booth Zones
8 of 38 © 2008 GENERAL MOTORS CORPORATION 34950D
All rights reserved
When printed, this copy is uncontrollable. GM users should verify latest revision at http://paint.gm.com/facility.
This section applies to Solvent borne, Waterborne Paints and Purge Materials determined to be
self-sustaining burning using the triangle diagram from the PTB Institution W-57 Test. NOTE:
This section shall also apply to paints and solvents that have not been tested.
General: In addition to the general requirements for spray booths, the following additional
protection is required. Note: For further discussions of the additional fire protection required,
refer to Appendix B, Section 6.
a) Booth sprinkler protection shall be extended to cover the inside of robot rail enclosures or
covers. 7,5m (25 ft) is the maximum length of rail where a single head located in the center
can be used. Longer lengths will use standard spacing design
b) Special CO2 and Deluge protection are required as described below:
A liquid CO2 system is not required in the cat-trac (robot servo motor and electrostatic
power) if the power cables are listed.
A deluge system shall be provided as the final protection for the affected zone. IR
detectors shall be installed to provide overlapping coverage of the entire spray zone with
or without a vehicle present and regardless of the position of the automation.
Any one IR detector in the zone will activate spray shutdown in the zone. If after a 10
second delay there are two detectors in alarm the deluge shall activate.
Means for manual electrically operated release of systems are to be available on both
sides of the booth. Mechanical means for release are to be available at the deluge valve
Interlocking and all other features are required as per “Logic Diagram 3” in Appendix C.
c) Water deluge system for the rotary atomizer zones
2 2
Water density 24 L/min/m 0.60 gpm/ft
2 2
Sprinkler spacing 8,4 m 90 ft
2 2
Area of application Entire zone (max. 372 m ) Entire zone (max.4,000 ft )
Sprinkler protection
2 2
Water density 14 L/min/m 0.35 gpm/ft
2 2
Sprinkler spacing 8,4 m 90 ft
Temperature rating
Calming/Cooling Zones Ordinary (57-77 ºC) Ordinary (135-170 °F)
Inside Heat Zones 28 °C above maximum start- 50 F above maximum start-
up or operating temperature up or operating temperature
Sprinkler protection shall be provided within the exhaust duct up to and just beyond the first
filter bank.
Sprinkler protection
2 2
Water density 14 L/min/m 0.35 gpm/ft
2 2
Sprinkler spacing 8,4 m 90 ft
Temperature rating Ordinary (57-77 C) Ordinary (135-170 F)
Temperature rating at High (121-149 C) High (250 – 300 F)
entrance and exit
2 2
Area of application Entire zone (max. 372 m ) Entire zone (max.4,000 ft )
3.14. Ovens
Sprinkler protection inside ovens is not required for metal bodies or components. Ovens drying
combustible panels or parts including final repair ovens must be protected in accordance with
the table below.
Sprinkler protection
2 2
Water density 14 L/min/m 0.35 gpm/ft
2 2
Sprinkler spacing 8,4 m 90 ft
Temperature rating 28 C above maximum start- 50 F above maximum start-
inside Oven up or operating temperature up or operating temperature
2 2
Area of protection 3715 m / alarm valve 40,000 ft / alarm valve
2) 2
Area of Application Entire zone (max 280 m Entire zone (max 3,000 ft )
Sprinkler protection shall be a closed head dry system on a manual control basis.
b) Electrical equipment in spray rooms shall conform to NFPA 33 and NFPA 70 for Class 1,
Division 1 (Zone 1) Locations.
c) The curing and polishing enclosures shall be electrically classified as ordinary hazard except
as required by the 3-foot rule (according to NFPA 33) separated from Class 1, Division 1
(Zone 1) Locations.
e) Spraying equipment shall be interlocked with the heating apparatus to not allow spraying
during drying.
g) Any attached enclosure for baking and polishing shall be per paragraph 3.4 - Process
Enclosures. If it is an attached oven refer to Paragraph 3.14
c) Spray apparatus shall be interlocked to prove ventilation. The bake lamps do not need to be
interlocked with the ventilation.
FIGURE 1
If spray application equipment is not interlocked with the exhaust ventilation equipment, a 3,0
meter (10 ft.) Class 1 Division 2 (Zone 2) area shall extend from the curtain.
Sprinklers are required in the filter box and under the overhead filters.
Sprinkler protection:
2 2
Water density 14 L/min/m 0.35 gpm/ft
2 2
Sprinkler spacing 8,4 m 90 ft
o
Temperature rating Ordinary (57-77 C) Ordinary (135-170 F)
Area of application Entire station Entire station
In order to not require sprinkler protection below plastic canopies the polyethylene film used
for the ceiling of the canopy shall have a maximum thickness of 0,18 mm (7.0 mils) and be
adequately supported by a metal support frame or cables. The spacing for the metal
support for the plastic film shall not exceed 4,5 m (15 ft.).
Tacky mesh canopy shall be woven polyethylene coated with a high tack, residue-free,
VOC-free adhesive with a fire retardant additive and supported by a metal cable or frame.
Fire breaks are not required for tacky mesh due to its slow burning properties.
Manual operations may be performed below a canopy constructed of plastic film / tacky
mesh as long as egress for fire and safety is provided as required by code.
The plastic / tacky mesh enclosure or canopy may span multiple conveyor lines when the
vehicle is completely non-combustible. The plastic /tacky mesh enclosure or canopy is
limited to one conveyor line in width when the vehicle has combustible panels.
Flash tunnels between the spray booth and oven shall not be constructed of plastic film or
tacky mesh.
Egress for fire and safety shall be provided as required by Life Safety Guidelines when
manual operations are performed.
2 2
Water density 14 L/min/m 0.35 gpm/ft
2 2
Sprinkler spacing 8,4 m 90 ft
Area of application 40 heads in remote area 40 heads in remote area
2 2
Area of protection 4831 m / alarm valve 52,000 ft / alarm valve
o
Temperature rating Ordinary (57-77 C ) Ordinary (135-170 F)
Interior of exhaust tunnels up to the main stack shall be protected with sprinklers.
Sprinkler heads subject to paint over spray or similar shall be protected from spray residue by
lightweight paper or by polyethylene bags having a thickness of 0,075 mm that will (3 mils) or
less.
Sprinkler pipes and hanger assemblies including the hanger rods shall be made of stainless
steel grade 304 or owner approved alternate within booth scrubbers, exhaust plenums,
concrete tunnels and exhaust ducts up to the inlet of the exhaust fan.
Electrical equipment in the interior of booth scrubbers, exhaust plenums and concrete tunnels
shall conform to NFPA 33 and NFPA 70 for Class 1, Division 1, Group D (Zone 1) Locations
3.22. Ductwork
a) Spray Booths and Spray Rooms
Aluminum shall not be used for ventilation ductwork or ductwork structural support when
associated with a spray booth or spray room.
The exhaust ductwork from the spray booths and spray rooms must be provided with wet
sprinklers installed not more than 3,7 m (12 feet) apart in horizontal or vertical runs. The
means to remove and replace each individual sprinkler head shall be incorporated into the
design of the ductwork.
Ductwork from the air supply house to the booth plenum does not require sprinklers except
where exhaust air is recirculated to booth supply.
Electrical equipment in spray booth exhaust ducts shall conform to NFPA 33 and NFPA 70
for Class 1, Division 1, Group D Locations.
In addition a CH (hydrocarbon) detector shall be installed in the recirculated duct after the
filter house. A warning signal shall be sent at a 20% CH level. At a 25% CH level an alarm
signal shall be sent to the facility alarm system and the fire interlock is energized. The fire
interlock shall deactivate booth air recirculation and direct the exhaust air to atmosphere.
The sludge removal water, air supply, bearing air and exhaust shall remain on at all times.
The hydrocarbon detector should be calibrated with methane or propylene. Propane should
not be used because it is too sensitive.
Electrical equipment in the recirculated air ducts, filter house and booth plenum shall
conform to NFPA 33 and NFPA 70 for Class 1, Division 1, Group D (Zone 1) Locations.
c) Process Enclosures
Ductwork for process enclosures does not require sprinklers. (See paragraph 3.4 for
definition of a process enclosure.)
3.23. Exhaust stacks
a) Exhaust stacks from process enclosures and ovens do not require sprinklers.
d) Electrical equipment in spray booth exhaust stacks shall conform to NFPA 33 and NFPA 70
for Class 1, Division 1, Group D (Zone 1) Locations.
Sprinkler system shall be tested with air pressure to detect and correct any leakage prior to
testing the water fill.
b) Ductwork
The exhaust ductwork from the collector modules to and just beyond the final filter shall be
provided with wet sprinklers installed not more than 3,7 m (12 feet) apart in horizontal or
vertical runs. The means to remove and replace each individual sprinkler head shall be
incorporated into the design of the ductwork.
The supply ductwork from the air supply house to the plenum does not require sprinklers
Fire protection for the air supply house and booth plenum will not be required when Class 1
or 2 filters are installed.
c) Storage / Distribution Room
The powder storage room shall be protected by an automatic wet sprinkler system. The
sprinkler system shall be designed and located to provide an effective distribution of water
throughout the entire room.
2 2
Sprinkler design shall be 12 L/min/m (0.30 gpm/ ft ) for entire area affected.
This room shall be considered an unclassified / normal electrical hazard. Proper house
keeping shall be maintained.
d) Bell Cabinets
The bell station side cabinets shall have automatic wet sprinkler protection as an extension
of the booth sprinkler system. CO2 protection is not required.
Sprinkler protection shall be part of the building system (see paragraph 3.2).
Unless otherwise required by local code, the building sprinklers shall be the only fire
suppression system installed in the paint mix room. Containment for discharge of sprinklers
shall be provided with capacity to hold 20 minutes of sprinkler discharge for the mix room
2 2 2 2
area up to a maximum of 280 m (3,000 ft ). 20 mins * 24 L/min/m * 280 m ( 20 mins *
2 2
0.60 gpm/ft * 3,000 ft ).
The sprinkler discharge containment tank shall be designed to comply with WFG
specifications and satisfy applicable local codes and regulations.
17 of 38 © 2008 GENERAL MOTORS CORPORATION 34950D
All rights reserved
When printed, this copy is uncontrollable. GM users should verify latest revision at http://paint.gm.com/facility.
In addition, when building sprinklers are the primary means of fire protection:
Water flow shall shutdown all paint and solvent pumps.
The room ventilation equipment should stay operating in the event of a discharge.
Isolation dampers on supply and exhaust duct are not required.
For installations in which a carbon dioxide fire suppression system is required due to local
codes or regulations, an automatic two-shot carbon dioxide system shall be provided in
addition to the closed head sprinkler system. For interconnected rooms, the quantity of
carbon dioxide shall be based on two shots for the volume of the larger room. The carbon
dioxide system shall be designed to operate before the sprinklers. CO2 protection shall
provide a 34 % concentration in one minute and hold at that level for 3 minutes. Time delays
and audible warning devices shall also be pneumatically operated. Containment for the
building sprinklers is not required when carbon dioxide fire suppression is utilized.
Interlocks in conjunction with the detection system of the CO2 system shall be arranged
as follows:
Shut off all paint material supply lines, air supply and exhaust fans, pumps, agitators,
barrel roller, compressed air supply, etc.
Close fire doors and dampers.
c) Electrical equipment in paint mix rooms shall conform with NFPA 70 National Electric Code
for Class I, Division 1, Group D (Zone 1) locations. All equipment shall be visibly grounded.
Racks for paint materials shall be grounded. Grounding methods used shall be in
accordance with NFPA 77 - Static Electricity.
d) For explosion relief venting see paragraph 3.29
e) Miscellaneous Requirements
Mix tanks for both solvent based and water based paint shall be provided with adequate
combination flash arrestors that are vented to the room interior. Exception: Paints
containing isocyanate materials shall be vented to a safe location at the building
exterior. This vent shall have a combination conservation–flame arrestor discharge cap.
The combination storage and mix room shall be separated from other building areas by
a three hour rated firewall. Openings are to be protected by approved fire rated
(commensurate with the wall) fire dampers and fire doors.
Floors shall be concrete. If drains are installed, they shall gravity feed to a containment
tank sufficient to contain spillage from the largest container in the room.
Floors shall be liquid tight and have 100 mm (4 “) high curbs or ramps at door openings
to outside and 100 mm (4 “) to paint shop.
Room shall have at least two exits for emergency egress.
18 of 38 © 2008 GENERAL MOTORS CORPORATION 34950D
All rights reserved
When printed, this copy is uncontrollable. GM users should verify latest revision at http://paint.gm.com/facility.
Continuous fresh air mechanical ventilation system shall be provided on a basis of 6 air
changes per hour: The 6 air changes per hour are calculated only for the lower 3
meters (10 ft) of the room.
- 80% of the volume should be exhausted at floor level, 150 mm (6“) above floor
- 20% of the volume should be exhausted near the ceiling level
- Supply air will be delivered according to good engineering practice to prevent any
dead areas in the room.
Air supply systems may be direct fired natural gas if the air supply house is mounted
outside the paint mix room and UL listed Class 1 or 2 (DIN 4102 Class B1 or
equivalent) filters are used.
The supply air system shall be capable of supplying air at 50% RH at the winter design
conditions.
Ventilation failure alarm shall be provided. This should be a local alarm and signal to
plant proprietary system upon the loss of either supply or exhaust airflow. A ventilation
failure does not need to shutdown the paint mix pumps or agitators.
Exhaust fans shall be non-sparking type.
An emergency shut off button to stop the paint mix equipment shall be installed outside
the room.
CH-detection to be provided if required by local authorities and shall be interlocked as
follows:
20 % LEL - - Ventilation starts or continues to operate and local visual alarm
40% LEL - - Audio alarm, signal to plant proprietary system and shutdown paint and
solvent pumps.
The combination storage and mix room shall be separated from other building areas by
a three hour rated firewall. Openings are to be protected by approved fire dampers and
doors. If the paint mix and storage rooms are designed as separate hazards, the
dividing wall shall have a minimum rating of two hours. These walls shall conform to
the provisions of General Motors Fire Prevention and Protection Manual, Section 3.
The integrity of fire walls or fire barrier partitions must be maintained by airtight filling of
any abandoned or partially used openings to the full wall thickness with materials
having the same fire resistance rating as the wall.
Floors shall be concrete. If drains are installed, they shall gravity feed to a containment
tank sufficient to contain spillage from the largest container in the room.
Floors shall be liquid tight and have 100 mm (4 “) high curbs or ramps at door openings
to outside and 100 mm (4 “) to paint shop.
Room shall have at least two exits for emergency egress.
Continuous fresh air mechanical ventilation system shall be provided on a basis of 6 air
changes per hour. The 6 air changes per hour are calculated only for the lower 3
meters (10 ft) of the room.
- 80 % of the volume should be exhausted at floor level, 150 mm (6“) above floor.
- 20 % of the volume should be exhausted near the ceiling level.
- Supply air will be delivered according to good engineering practice to prevent any
dead areas in the room.
Air supply systems may be direct fired natural gas if the air supply house is mounted
outside the paint mix room and UL listed Class 1 or 2 (DIN 4102 Class B1 or
equivalent) filters are used.
The supply air system shall be capable of supplying air at 50% RH at the winter design
conditions.
Ventilation failure alarm shall be provided. This should be a local alarm and signal to
plant proprietary system upon the loss of either supply or exhaust airflow. A ventilation
failure does not need to shutdown the paint mix pumps or agitators.
Exhaust fans shall be non-sparking type
3.29. Explosion Venting
Explosion relief venting shall be provided in accordance with the provisions of General Motors
Fire Prevention & Protection Section of the Global Security Manual. If there is no dispensing in
the storage room explosion venting is not required.
4. MATERIAL REQUIREMENT
4.1. General
All equipment shall be listed and/or approved for its intended purpose by a recognized testing
laboratory such as Underwriters Laboratories (UL) or Factory Mutual (FM). Listed means
equipment, materials, or services included in a list published by an organization acceptable to
the authority having jurisdiction and concerned with evaluation of products or services that
maintains periodic inspection of production of listed equipment or materials or periodic
evaluation of services and whose listing states either that the equipment, material, or service
meets appropriate identified standards or has been tested and found suitable for a specified
purpose.
Sprinkler design shall be based on the most recent edition of NFPA 13 – Standard for the
Installation of Sprinkler Systems.
4.2. Pipework and Fittings
Sections of pipes greater than DN 65 (2 ½”) shall be joined by means of welded flanges or via
grooved pipe system. (ie. Victaulic, Gruvlok...) Piping equal to or less than DN 65 (2 ½”) shall
have threaded joints.
4.2.1 All pipe and fitting materials shall be based on NFPA 13 requirements. Schedule 10
light wall piping is permitted in those instances where the water supply is considered
potable.
4.2.2 For European Installations, welding inside buildings is strictly forbidden. All piping shall
be prefabricated outside the building.
4.2.3 For European installations, the pipe and fitting materials listed in the table below shall
be used.
Pipes Bends
welded steel pipe accorded to DIN 2458 / seamless steel bends accorded to DIN 2605
EN 10220 St 37 accord. To DIN 1626 for standard 3S, material St33 , according to DIN /
welding EN 10025
323,9 mm x 5,6 mm standard wall 323,9 mm x 7,1 mm wall thickness
thickness
273,5 mm x 5,0 mm " 273,1 mm x 6,3 mm "
Threaded-Pipes Fittings
steel pipes accorded to DIN 2440 material For DN 65: threaded malleable fittings
St 33 accord. DIN / EN 10025 for screw accorded to DIN 2950 / EN 10242.Connections
connection to large diameters by means of threadolet
76,1 mm x 3,65 mm (2 1/2") Tees: no prefabs. Forged fittings but directly
welded connections for equal and different
60,3 mm x 3,65 mm (2)
diameters, accorded NFPA No. 3.12.2.
48,3 mm x 3,25 mm (1 1/2")
Reducer: accord. DIN 2616
42,4 mm x 3,25 mm (1 1/4")
Flanges: accord. DIN 2633 (PN 16, welding
33,7 mm x 3,25 mm (1) neck).
26,9 mm x 2,65 mm (3/4“) Grooved-style joints are also acceptable. Max.
21,3 mm x 2,65 mm (1/2“) length of pipework between flanges : 7m (23 ft)
No jointing compound except steam-sealing quality shall be permitted and all joints shall be
wiped clean externally upon completion. For sprinkler head thread TPF packing shall be used.
4.3. Hangers
Hanger design shall be in accordance with NFPA No. 13 with the following exceptions:
- Pipes up to DN 40 (1 ½ in) diameter can be supported on the metal panel ceiling using
trapeze hangers.
- Pipes with DN 50 (2 in) diameter – support on metal panel ceiling with trapeze hangers
and every third hanger shall be supported on steel structure.
- The distance between hangers on pipes of DN 80 can be up to 6 m (20 ft) if double
hangers on beams are utilized (VdS rule)
The hangers shall be designed to support five times the weight of the water-filled pipe plus 125
kg (275 Ibs) at each point of piping support.
All necessary supports for pipe work shall be supplied and fitted by the contractor.
All pipe supports must be allowed to swing freely to permit expansion and contraction of the
pipe work and shall ensure correct alignment of the services at all times.
When determining the position, design and type of brackets, care should be exercised to
ensure that ample clearance is allowed from walls and steelwork.
All brackets must be securely clamped to building structural steel. Welding to or cutting the
structural steelwork will not be permitted under any circumstances.
Where water based fire protection systems are required to be protected against damage from
earthquakes, the requirements of NFPA 13 shall be applied.
Installations that exceed the maximum quantities listed in the above table shall be hydraulically
designed. Working drawings for all pipe schedule sprinkler modifications shall be submitted to
XLGAPS for field review at the subsequent Loss Prevention Survey.
NOTE: 20 sprinkler for OH and 15 sprinkler for XH as given in the above table
represent the total area that can be covered on a pipe schedule basis. If the number of
sprinkler heads under platforms, obstruction, etc. exceeds those given in the table, the
proposed extension of the sprinkler system needs to be hydraulically designed.
Grated metal mezzanines and solid noncombustible platforms that exceeds1,2 m (4 ft):
The following active and passive fire protection measurements are subject to review and comment by
XLGAPS prior to installation and respective documentation shall be submitted:
1. Sprinkler and deluge systems 9. Underground piping and equipment
2. Inside hose connections 10. All fuel-fired equipment
3. CO2 extinguishing systems 11. Dryer and incinerator air flow system
4. Fire alarm systems 12. Filter material specification
5. Fire walls and partitions 13. Paint repair operations
6. Roof and wall construction 14. Flammable and combustible liquids in
7. Detection systems mixing, dispensing and storage
8. Connection of sprinkler systems 15. Chemicals
to the fire main
24 of 38 © 2008 GENERAL MOTORS CORPORATION 34950D
All rights reserved
When printed, this copy is uncontrollable. GM users should verify latest revision at http://paint.gm.com/facility.
For 1,3,8,9 :
Complete bill of materials
A. Plan layout of the piping showing
pipe diameters sprinkler/CO2 head location with type of head used
pipe hanger location with type of hanger used at each location
hydraulically most remote area for calculations must be outlined
location of inspectors test connection
B. Plan showing one or more section views of the building
C. Plan showing isometrics in order to follow up on hydraulic calculation
It is also acceptable to show calculation reference points on the
installation drawing.
D. One set of hydraulic calculation for each sprinkler/CO2 system
Reference points used in the hydraulic calculation must be either shown on an isometric drawing or the
installation drawing.
For 2 Drawing with the location and connection points to sprinkler systems
For 5,6 Drawing with location and facility operation, cross section and construction,
exposures around, interior and exterior construction materials.
For 10,11 Mechanical equipment drawings, Hard wire diagram, air flow diagram, purge
time, heat source, material list, PLC logic.
The paint shop building areas, outside of classified processes, are considered to be
unclassified.
Application of Class IIIB combustible liquid (Flashpoint > 93°C) can be performed in
unclassified locations.
5.2. Connection of paint lines to the spray booth
The use of plastic paint lines for all types of paints outside of the spray booth, color changers
located external to the booth, cat track, or hose cabinets is not permitted. Exception: PTFE
flexible pipe covered by one layer wire braid, stainless steel has been accepted for the use in
waterborne paint supply lines. Flexible pipe shall be no larger than 12 mm (0.5 inch) diameter,
properly supported and protected from damage by the use of cable trays or equivalent.
5.3. Rotary Atomizer (Esta) Machine Cabinets
The cabinets for the side machines and the supports for the roof machines shall be arranged as
follows:
a) Electrical classification shall be as shown in the following table:
b) If the cabinets meet the requirements of NFPA 496 “Purged and Pressurized Enclosures
For Electrical Equipment”, classification within the cabinets may be reduced to unclassified.
c) The bottom of the cabinets shall be closed liquid tight.
d) For liquid paints, the cabinets shall overflow to the spray booth water wash system. The
ventilation openings at the bottom may be used for this purpose. For powder paints, a drain
to a safe location shall be provided.
e) For liquid paints, the paint lines shall be rigid tubing up to the bottom of the cabinets (see
paragraph 5.2 for exception for use of flexible tubing). For powder paint, the powder hose
shall be supported and protected from damage by the use of cable trays or equivalent.
5.6. Paint Mix and Storage Rooms – Tote and Mix Container Venting
Paint mix tanks and connected supply totes are considered process vessels when referring to
NFPA 30.
Containers shall be vented directly to the room atmosphere with a flame arrestor. A
combination flame arrestor/conservation vent may be used dependent upon process
requirements.
Exception: Containers holding isocyanate materials shall be vented to atmosphere exterior of
the building. A flame arrestor or a combination flame arrestor/conservation vent shall be used
Ventilation shall be provided per the requirements of paragraphs 3.27 and 3.28.
Ventilation shall be supervised with an audible and visual local alarm to assure its continuous
operation. Supervision must be accomplished by the use of a pressure differential switch(s) or
airflow device(s).
5.7. Rotary atomizer (ESTA) stations
Door exits from the rotary atomizer (ESTA) station shall be spaced not more than 23 m (75 ft)
apart from each side of the conveyor. Travel through a door in a silhouette is acceptable if the
doors swing out from the inside the rotary atomizer zone. In the case where two or more
stations are located back to back, doors on each side shall be provided between overhead
machines to allow path to safety when both overhead machines are lowered. Doors shall be a
minimum of 810 mm (32 in).
5.8. Paint line flushing
An inert gas, such as nitrogen, shall be used for the blow back of all paint (solvent borne and
waterborne) and solvent lines. The inert gas supply pressure shall not exceed the maximum
recommended pressure for the circulation system piping. For initial cleaning, all operations in
the paint shop shall be shutdown due to the possibility of leaks. Initial flushing of paint lines
using materials with a flash point greater than 93 C (200F) may be accomplished with air.
5.9. Twin tank systems for colored primer coat (waterborne primer)
If paints are classified as non-burning or non self-sustaining burning (according PTB triangle
test), the following protection features are needed:
enclosed by sheet metal
provide spill containment
mechanical ventilation to remove vapors on the basis of 6 air changes per hour
classified electrical equipment - Zone 2 or class I, division 2
(Electrical classification shall be Zone 1or class I division 1 for solvent based paints)
sprinkler protection designed for 24 L/min/m² (0.60 gpm/ft ) over entire area
2
proper housekeeping
maximum paint storage 82 L/m² (2 gal/ ft )
2
b) Inside storage rooms - Class I, II, III A liquids (more than 450 liters (120 gal).)
2 2
Water density 24 L/min/m 0.60 gpm/ft
2 2
Sprinkler spacing 9,3 m 100 ft
Temperature rating Ordinary (57-77 C ) Ordinary (135-170 F)
2 2
Area of application Entire room (max. 372 m ) Entire room (4,000 ft )
2
Storage limitations for room 14 m² to 45 m² (150-485 ft )= 385 L/m²
c) Attached or cut-off rooms - Class I, II and IIIA liquids (more than 450 liters (120 gal)).
2 2
Water density 24 L/min/m 0.60 gpm/ft
2 2
Sprinkler spacing 9.3 m 100 ft
Temperature rating Ordinary (57-77 C ) Ordinary (135-170 F)
2 2
Area of application Entire (max. 372 m ) Entire (max 4,000 ft )
2
room size more than 93 m² (1000 ft )- F-120 rated walls needed
Provision shall be made for explosion venting in all areas designated as catastrophic hazards and in
other areas where combustible or explosive atmospheres of vapor or dust may develop. Venting shall
be provided by means of roof ventilators, side wall panels or sach attached with dead soft copper clips
or other means approved by the fire underwriters. These methods are recommended in lieu of glass
scoring. Panels or sash may be arranged to swing or fall open due to explosion pressures in the range
of 96 Kpa (20 psf).
2 2 3 3
Generally, the minimum vent area shall be 0,09 m (1 ft ) of effective vent area to 0,28 m (10 ft ) of
room volume for very small rooms up to 1 to 50 for large rooms such as paint mixing or similar areas
3 3
over 710 m (25.000 ft ) in volume.
if required vent area is available vent area, the entire outside wall should provide
means of explosion relief
Documentation for explosion venting, including calculation and means of explosion venting,
shall be submitted to XLGAPS for review.
6. APPENDIX B
THIS SECTION PROVIDES ADDITIONAL FIRE PROTECTION INFORMATION FOR
ROTARY ATOMIZER AND ELECTROSTATIC ROBOTIC STATIONS
Refer to Appendix C - Logic Diagram 3 for System Operation
6.1 Overhead Machine CO2 system
GMNA Facilities
CO2 supply shall be liquid from CO2 supply container with capacity supervision.
A 34% concentration of CO2 shall be achieved within one minute after agent release.
Once a concentration of 34% is achieved, it must be held for one additional minute. A
minimum of two shots must be available.
Actuation is by optical flame detectors or linear heat detection inside the roof bar.
GME Facilities
CO2 supply shall be gaseous from CO2 supply container using a solenoid valve and
with capacity supervision.
A 34% concentration of CO2 shall be achieved within one minute after agent release.
Once a concentration of 34% is achieved, it must be held for one additional minute. A
minimum of two shots must be available.
Actuation is by optical flame detectors inside the roof bar and by detectors inside the
booth, which are directed to supervise the rotary atomizers (bells) of the roof machine.
6.2 Cabinet CO2 system
CO2 supply is liquid
A 34% concentration of CO2 shall be achieved within one minute after agent release.
Once a concentration of 34% is achieved, it shall be held for one additional minute. A
minimum of two shots shall be available.
Actuation is by the cabinet optical flame detectors or linear heat detection.
Rotary atomizer stations with the color changer located on the extension arm shall have
an optical flame detector or linear detection placed in the arm. A CO2 nozzle is not
required in the arm if it is open to the side cabinet.
CO2 is not required for cat-trac enclosure area of current GMNA approved robotic systems
when the cables for servomotors and electrostatic power are listed for use with solvents
normally used in painting operations.
6.4 Deluge System
A flame detected by one optical flame detector will result in shutting down the spray
process. If after a 10 second delay, a flame is detected by two booth optical flame
detectors the deluge valve for the affected zone shall be operated.
If spray shutdown capability is not provided, the deluge shall be discharged immediately
after a flame is detected by two booth optical flame detectors.
6.5 Sprinkler System
2
The general booth shall be protected by sprinklers with a design density of 14 L/min/m
2
(0.35 gpm/ft ).
The electrostatic zones shall be protected with a deluge system with a design density of
2 2
24 L/min/m (0.60 gpm/ft ).
Manual operation of CO2 and deluge systems shall be from booth operating level.
Booth sprinkler protection shall be extended to cover all side and overhead support
cabinets.
For rail mounted robots, the booth sprinkler protection shall be extended to cover all
rail, color changer and cat-trac enclosures.
GENERAL MONITORING
OFF 1)CONVEYERS, 2)AUTOMATIC DENSITY OF 0.35
PAINT SYSTEM EQUIPMENT AND GPM/SQ.FT. FOR
FIRE INTERLOCK
3)HIGH VOLTAGE ENTIRE BOOTH AREA
SHUT DOWNS
AFFECTED. (EXISTING
BOOTHS WITH EXTRA
HAZARD SPRINKLER
PROTECTION ARE
ACCEPTABLE)
SPECIALTY/SATELLITE
FIRE ALARM SYSTEM
TROUBLE SIGNAL TO
(SEE NOTE A)
(INCLUDES
SYSTEMS)
SYSTEM
DEVICE EVENT
SPRINKLER PROTECTION 1 ST SPRINKLER OPERATED X X X
7.2. DIAGRAM 2
This diagram is for reference only. It shall not apply to new installations unless prior approved is
given by the responsible GM operating group and GM Security.
7.3. DIAGRAM 3
7.4. DIAGRAM 4
7.5. DIAGRAM 5
8. REVISION HISTORY
Date: Change Control No.: Revision: Reason/Need:
15 AU08 003-08 D 2008 Update
- Commonized units of measure with Global Security Fire Protection and Prevention
Specification.
- Modified sprinkler spacings and araeas of application to conform to revised Global
Security Fire Protection Specification.
- 3.6 Eliminated the provisions for CO2 to shaping air supply for fire supression.
- 3.16 clarified that the bake lamps are not required to be interlocked with ventilation.
- 3.18 added tacky mesh to plastic tunnels
- 3.27, 3-28 clarified paint mix room ventilation alarm /Allows use of direct fired gas
burner if certain conditions are met. / Revised the design air changes per hour from 12
to 6/ Provides option to use wet sprinkler with containment in lieue of CO2 fire
supression system for paint mix rooms.
- 3.8 Clarified the use of a single sprinkler to protect robot cat trak
- 5.1 add Class IIIB liquid clarification
- 3.5 add laminated glass as a option
- 3.22 hydrocarbon calibration gas
- Modified diagram 3 to remove CO2 discharge through shaping air .
Diagram 1
GENERAL MONITORING
OFF 1)CONVEYERS, 2)AUTOMATIC DENSITY OF 0.35
PAINT SYSTEM EQUIPMENT AND GPM/SQ.FT. FOR
FIRE INTERLOCK
3)HIGH VOLTAGE ENTIRE BOOTH AREA
SHUT DOWNS
AFFECTED. (EXISTING
BOOTHS WITH EXTRA
HAZARD SPRINKLER
PROTECTION ARE
ACCEPTABLE)
PROPRIETARY FIRE ALARM
SPECIALTY/SATELLITE
FIRE ALARM SYSTEM
TROUBLE SIGNAL TO
(SEE NOTE A)
(INCLUDES
SYSTEMS)
SYSTEM
DEVICE EVENT
SPRINKLER PROTECTION 1 ST SPRINKLER OPERATED X X X
Diagram 2
FIRE PROTECTION
FIRE INTERLOCK
NOTE A: FIRE INTERLOCK
SHUT DOWNS
SHUTS OFF 1)CONVEYORS,
2)ROBOT UNITS, 3)AUTOMATIC
PAINT SYSTEM EQUIPMENT,
4)HIGH VOLTAGE AND
5)CONTROL AIR
BOOTH
PANEL
ONLY
DEVICE EVENT
DETECTION SYSTEM
TUBING
RUPTURE BREAK X X X X X X X X
LOW PRESSURE
CO2 DETECTION SYSTEM
LOW LIGHT LEVEL
X X X
1 ST DETECTOR OPERATED X X X
FIRE CONTROL
OTHER
PANEL
AC FAILURE X X
Audible trouble to
fire alarm system
CO2 Discharge to
alarm system
control panel
Fire interlock
for 1 minute
mix room
panel
Device Event
Flame detection Detect flame on applicator (identical with
system first line deluge system)
X X X X X X
Detect flame in side and roof machine
(single line arrangement)
X X X X X X X
2)
Flame detector supervision X X
Fire control panel 3) Power failure X X X
Door open X X
CO2 system Manual trip at each booth door X X X X X X X
CO2 pressure switch (auto & man) X X X X X X
Container quantity supervision X X
Paint & thinner stop
relay
Emergency manual trip X X X X X X
Audible trouble to
fire alarm system
thinner supply @
affected booth
affected booth
alarm system
control panel
Fire interlock
mix room
panel
Device Event
4)
Flame detection 1st. line detection X X X X
system 2nd. line detection X X X X X X X X
2)
Flame detector supervision X X X
Fire control panel 3) Power failure X X X
Door open X X
Deluge system Gate valve closed X X
Manual trip at each booth door X X X X X X X X
Mechanical actuation at deluge valve X X X X X X X X
Alarm pressure, switch / deluge valve X
Paint & thinner stop
relay (process)
Emergency manual trip X X X X X X
Wet Sprinklers Operated x x x x x
Sludge removal water, air supply, bearing air 1) to be seen inside booth
and exhaust shall remain on all times, except 2) cable break and flame eye supervision
as noted in text (entire circuit from flame detector lens
to local alarm panel)
Fire Interlock Shuts Down 3) no release if local panel door is open
- high voltage 4) time delay < or = 15 sec. (see below)
- conveyor
- control- and drive air 2. Detector Deluge
- robot units 1. Detector Discharge
- automatic paint system equipment
0 3 6 9 12 15 sec.
FIRE INTERLOCK
NOTE A: FIRE INTERLOCK
SHUTS OFF 1)CONVEYERS,
2)AIR SUPPLY UNITS,
3)EXHAUST FANS, 4)PAINT
SUPPLY, 5)AUTOMATIC PAINT
SYSTEM EQUIPMENT, 6)HIGH
VOLTAGE AND 7)CONTROL AIR
PANEL
PANEL
2 ND DETECTOR OPERATED X X X X X X
FLAME DETECTOR
DETECTOR
SUPERVISION
X X X
FIRE CONTROL
PANEL
AC FAILURE X
FIRE CONTROL TROUBLE INSIDE
PANEL PANEL
X X X
DETECTOR OPERATED X X X X X
SUPPRESSION
SYSTEM CONTROL AC FAILURE X X X
PANEL
SUPPRESSION
TROUBLE INSIDE
SYSTEM CONTROL
PANEL
X X X
PANEL
40,000 750
General Assembly 15 0.40 (16) 4,000 (372) 100 (9.3)
(3,716) (2,840)
40,000 750
General Assembly 26 0.60 (24) 3,000 (279) 100 (9.3)
(3,716) (2,840)
Production Paint Spray Booths
750
& Ovens where protection is 0.35 (14.3) N/A 90 (8.4) N/A
(2,840)
needed
Notes:
1 In open office areas that are cut off from adjacent occupancies by a minimum 1 hour fire partition AND have a smooth ceiling;
2 2 2 2
maximum spacing of 225 ft (21 m ) is acceptable. Head spacing in excess of 225 ft (21 m ) requires advance approval from Global
2 2
Security. Under no circumstances may the head spacing exceed 400 ft (37.2 m ).
2 Sprinkler protection for the operating floor of the press shop may be waived, subject to the approval of the authority having jurisdiction.
3 An increase in the required density and area of application may be warranted in areas where storage is such that the given density
and area of application would be considered insufficient.
2 2
4 Storage in these areas must be limited to 10 ft. (3 m) high, 500 ft (45 m ) piles. If this combustible loading is exceeded, sprinkler
2 2 2 2
densities should be increased to 0.60 gpm/ft (24 L/min/m ) over any including the hydraulically most remote 4,000 ft (372 m ).
2 2
5 Storage must be limited to 15 ft. (4.6 m) high, 1000 ft (93 m ) piles. In addition, screenguarding must be limited and protection
provided beneath where required.
6 These requirements apply where the storage limitations of Note 5 cannot be met, or where extensive screenguarding is present or
expected.
Table 3.0-b GM Owned or Leased Facilities
100,001-350,000 ft2 (9300-32550m2)
Office occupancies 0.10/3,000 100 gpm (400 L/min) Maximum sprinkler spacing 130 ft2
hose stream demand (11.9 m2) per NFPA for type of
sprinkler
Occupancies, i.e., manufacturing, 0.30/4,000; 500 gpm (1890 L/min) Maximum sprinkler spacing 130 ft2
assembly hose stream demand (11.9 m2), Ordinary combustible
storage @ 12 ft (3.4 m) maximum.
Plastic storage @ 10 ft (3 m) max-
2 2
AUTOMATIC imum with 500 ft (45 m ) piles
SPRINKLERS Occupancies, i.e., Heat treat, 0.45/4,000; 750 gpm (2839 Maximum sprinkler spacing 130 ft2
plastics, painting L/min) hose stream demand (11.9 m2)
Fixed rack storage associated GMFP&P Chapter 3 , Standard 3.6 Exposed, expanded plastic per NFPA
with manufacturing 13 + 1 additional level of in-rack
sprinklers
Warehousing, rack and bulk GMFP&P Chapter 2, Standard 3.6 Use of ELO and ESFR sprinklers
acceptable
Flammable liquids storage NFPA 30 flammable and 0.60/3,000 may be needed.
combustible liquids Deviation-Global Security
Inside hose connections NFPA 13 and 14 as appropriate Maximum spacing 1:10,000 ft2 (930
m2), two point attack for storage
Alarm system NFPA 72 & GMFP&P Chapter 5, Approved/listed central station or
BUILDING Standard 3.4 proprietary
FEATURES Fire extinguishers NFPA 10 Spacing as appropriate
Draft curtains May be required, see GMFP&P Floor openings, elevation changes,
Chapter 4, Standard 3.3 special hazards
Venting May be required, see GMFP&P Over special hazards
Firewalls, partitions May be required, see GMFP&P As required by AHJ
Chapter 4, Standard 3.3
One fire pump ( sized according NFPA 20 Public supply may be acceptable
to hydraulic demand) alternative
WATER
SUPPLIES Duration of water supply 60 minutes Each source
Water distribution “L” shaped fire main with hydrants at Sprinkler hydraulic demand may
two corners Exception: Office require larger than 6-inch (150 mm)
occupancy minimum
Office occupancies NFPA 13, light hazard 100 gpm Maximum sprinkler spacing per NFPA
(400 L/min) hose stream demand for type of sprinkler head
Occupancies, i.e., 0.30/3,000; 250 gpm (1000 L/min) Maximum sprinkler spacing 130 ft2
manufacturing, assembly hose stream demand (11.9 m2), Ordinary combustible
storage @ 12 ft. (3.4 m) maximum.
Plastic storage @ 10 ft (3 m) max-
2 2
AUTOMATIC imum with 500 ft (45 m ) piles
SPRINKLERS Occupancies, i.e., Heat treat, 0.38/3,000; 500 gpm (1890 L/min) Maximum sprinkler spacing 130 ft2
plastics, painting hose stream demand (11.9 m2)
Fixed rack storage associated NFPA 13 Exposed, expanded plastic per NFPA
with manufacturing 13 + 1 additional level of in-rack
sprinklers
Warehousing, rack and bulk NFPA 13, Use of ELO and ESFR sprinklers
GMFP&P Chapter 2, Standard 3.6 acceptable
Flammable liquids storage NFPA 30 flammable and 0.60/3,000 may be needed. Deviation-
combustible liquids Global Security
Inside hose connections NFPA 13 and 14 as appropriate Maximum spacing 1:10,000 ft2 (930
m2), two point attack for storage
Alarm system NFPA 72 & GMFP&P Chapter 5, Approved/listed central station or
Standard 3.4 proprietary
BUILDING Fire extinguishers NFPA 10 Spacing as appropriate
FEATURES Draft curtains May be required, see GMFP&P Floor openings, elevation changes,
Chapter 4, Standard 3.3 special hazards
Venting May be required, see GMFP&P Over special hazards
10 {3} 0.3 {12.2} 4,000 {372} 500 {46.5} 500 {46.5} 10 {3}
Class I-IV
commodities, Cartoned Cartoned Exposed Exposed
Sprinkler and Group B, C Expanded Non-Expanded Expanded Non-Expanded
Type Plastics Plastics Group A Plastics Plastics Group A
& Tires Plastics
All sprinklers in this category must be strictly installed in accordance with their
Listing/Approval and in accordance with current NFPA standards (e.g., building height,
storage height, clearance). No deviations allowed.
Note: Pile sizes in areas protected with specific application sprinklers not listed
above are subject to review by Global Security.
Table 3.6.3-a Fire Protection for Small Warehouse Facilities Based on Facility Size,
Inventory Values, Lease Agreements and Business Continuity
Water supply One source calculated to highest Additional source may be required (if
sprinkler/hose stream demand exposure warrants)
One fire pump 2,500 GPM Fire Pump (9464 L/min) Public supply may be acceptable
WATER alternative
SUPPLIES
Duration of water supply 120 minutes (250,000 gal tank) Each source
(946000 l)
Water distribution Looped fire main of ductile iron, 12” 10” (250 mm) PVC Class 200 FM approved
(300mm) minimum diameter may be acceptable alternative
2 2
Office occupancies 0.1 gpm/ft (4.1 L/min/m ) over most Head spacing may be extended to 225ft2
remote 3000ft2 (280 m2) – 130ft2 (12 (21 m2) if wall between warehouse and
2
m ) maximum head spacing office has minimum 2 hr fire rating
Computer Room 0.12 gpm/ft2 (4.9 L/min/m2) over most Same maximum head spacing as office
2 2
AUTOMATIC remote 3000ft (280 m ) occupancies
SPRINKLERS
Warehousing, rack and bulk Design to supply 12 K-25 ESFR As an alternative, K-17 heads may be used
sprinklers operating at minimum end at a density of .8 gpm/ft2 (32.6 L/min/m2)
2 2
head pressure of 20 psi (1.4 bar) over 2,000 ft (186 m )
2 2
(or as required per the listing) 90 ft (8.4 m ) head spacing
If obstructions cannot be avoided,
design to 14 heads at 20 psi (1.4 bar)
2
80-100ft head spacing
Below walkway/mezzanine 0.4 gpm/ft2 (16.3 L/min/m2) over Feed from adjacent ceiling system
2 2
2,500 ft (232 m )
Inside hose connections NFPA 13 as appropriate Sufficient number and spacing for two point
attack. Feed from adjacent ceiling system
Firewalls, partitions Minimum 1 hour fire rated masonry Fire rated glass in windows, or line of
wall between warehouse and office sprinklers above
1.0 PURPOSE
2.0 SCOPE
3.0 STANDARDS
This section provides guidelines on the construction and fire protection of main
computer rooms and remote data processing operations.
3.1.1 Construction
Separate computer rooms from adjacent areas by a minimum one hour fire rated
barrier extending from the structural floor to the structural ceiling. Separate the
media storage area by a two hour fire rated barrier.
All finishing materials for the computer room including walls, floors, partitions,
acoustical treatment, raised floors, raised floor supports, suspended ceilings and
others, must have a flame spread rating of 25 or less.
1
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Use only listed plenum rated cable in the subfloor, or fully house all cables in
conduit.
Restrict paper stock and other combustibles to the minimum necessary for
efficient operations. Store this material in enclosed metal cases or cabinets, or
restrict these combustibles to the supplies storage area.
3.2.1 Engine Hot Test Areas, Chassis Dynamometer Areas and Fuel Flow
Operations
3.2.1.1 Construction
Isolate engine hot test areas from other occupancies, including control rooms, by
a one hour rated fire barrier, or at a minimum, a deep draft curtain as defined in
Chapter 4, Section 3.3.1.3 of this manual.
2
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Isolate fuel flow operations from other occupancies by a minimum one hour rated
fire barrier.
Avoid the use of pits, trenches or basements where possible. If pits or basements
are required, provide appropriate exits from at least two points. All operations
necessary for employee entrance into pits or basements must be in accordance
with Local or Facility Confined Space Entry Procedures.
Provide floor drains wherever fuel spillage is possible in test rooms in which
liquid fuel is used.
Provide at least two means of egress from 1) any test enclosure where fuel is
used and 2) in all enclosures adjoining a hazardous area in order to minimize the
possible entrapment of personnel.
Piping
Maintain the fuel system at the lowest pressure at which the system will operate.
Pitch fuel distribution piping to drain to the outside, with a valved connection to a
receiving tank.
Clearly identify all piping used in the transfer of hazardous flammable materials in
accordance with applicable local regulations.
Pressure test all fuel piping systems in accordance with ANSI B 31.3 or an
equivalent standard.
3
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Sleeve all fuel lines passing through walls or foundations. Pack sleeves with
non-hardening caulking compound.
Flexible piping must be approved by a recognized testing laboratory for the fuel
used.
Fuel Delivery
Limit inside compressed natural gas storage to six 1.5 ft3 (42.5 L) cylinders,
arranged in a manifold, with no more than one bottle in use at any one time.
Locate the fuel measurement system in the test cell or in a room specifically
designed for handling fuel. Arrange the equipment to prevent physical damage
from other equipment.
4
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Design and install fuel cooling and conditioning equipment to prevent fuel from
mixing with any other substance.
Provide a one hour fire rated enclosure for the pumps when located within the
building.
3.2.1.3 Ventilation
Provide a minimum ventilation rate of one cfm per ft2 (28.3 L per 0.09 m2) of floor
area, exclusive of recirculated air.
Locate room exhaust pickups at a maximum of six inches (15.2 cm) above floor
level.
Provide interlocks to automatically terminate testing and shut off appropriate fuel
systems upon loss of ventilation.
Equip the following with an exhaust system mechanically vented to the outdoor
atmosphere:
5
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
3.2.1.4 Electrical
Electrical equipment and wiring must conform to Article 500 and other applicable
provisions of NFPA 70, or an equivalent standard.
Install equipment and wiring in accordance with General Motors Standards El-1
Electrical Installation Standard for Buildings and Facilities and ES-1 Electrical
Standard for Industrial Equipment.
Ensure all electrical equipment located within 18 inches (0.5 m) of grade level is:
rated as Class I, Group D, Division 2 or Zone 2; or rated as non-classified in
accordance with Article 501 of NFPA 70, or equivalent.
Do not locate Test Area power supplies, including batteries or terminals for
engines, in close proximity to fuel supply couplings.
Provide a wet pipe sprinkler system throughout the facilities, including exhaust
hoods, hydraulically designed to deliver a density of 0.30 gpm per ft2 (12
L/min/m2) over any and including the most remote 3,000 ft2 (280 m2) area of
application. Protect duct systems with sprinklers controlled by a readily
accessible valve.
6
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Protect each test stand or group of test stands in engine hot test operations or
fuel flow rooms with one of the following, activated by heat detection:
Protect control rooms utilized to monitor test operations with automatic sprinklers
installed in accordance with applicable sections of this manual.
Shut off electrical power, engine ignition, air systems, ventilation fans,
dampers, cranes and hoists
Provide grounding and bonding of fuel handling and/or fuel piping systems.
Locate test cells adjacent to an outside wall in a one story building with no
unrelated facilities or normally occupied spaces above or below.
Provide explosion relief venting for each cell. As a minimum, use the entire
outside wall for explosion relief.
7
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Isolate test cells from other occupancies, including control rooms and adjacent
test cells, by walls having a fire resistance rating of two hours and blast
resistance rating of 100 pounds per ft2 (4.8 kpa). Prohibit the installation of
viewing windows that reduce these ratings.
3.2.2.3 Ventilation
3.2.2.4 Electrical
Locate vapor detection at the floor when vapors from fuel are heavier than
air.
Locate vapor detection at the ceiling when vapors from fuel are lighter
than air.
8
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Locate heaters as close as possible to the engine or test fixture, within the test
cell, or in a room specifically designed for handling fuel.
3.2.3.2 Equipment
Use equipment, including seals, gaskets and all materials of construction that is
rated above the maximum operating temperature. All wetted materials must be
compatible with the specific fuel being used.
Meet or exceed the requirements of the previous sections for all piping and
electrical equipment.
Provide appropriate monitoring and control for high temperature and high/low
pressure and level limits.
Provide methods to ensure that the media do not mix. Stainless steel heat
exchangers and conditioned water are recommended to reduce component
failure. Provide steam at the lowest possible pressure required to perform the
test.
Steam to Fuel
Provide methods to ensure that the media do not mix. Provide steam at the
lowest possible pressure required to perform the test.
Use electric heaters with caution, and only if the following conditions are met:
9
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Ensure the heater and installation meet the requirements of the General
Motors Standards ES-1, EI-1 and all electrical requirements set forth in
this document.
Ensure the heater, when continuously energized with 110 percent rated
voltage, does not have an internal or external temperature exceeding the
ignition temperature of the fuel and/or oil being used. Ensure oils meet the
operating and safety requirements of the fuel conditioning equipment and
the test specifications.
Use direct electric heaters only if the following conditions are met:
Ensure electrical safety devices are sized to reflect the actual operating
currents to protect equipment, buildings and personnel.
Ensure the heater, when continuously energized with 110 percent of the
rated voltage does not have an internal or external temperature exceeding
the ignition temperature of the fuel being used.
Provide explosion relief venting for the compressed gas bottle storage room.
Isolate bottle rooms from other occupancies with walls of a minimum of one hour
fire resistance rating.
10
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Ensure the distribution system design pressure exceeds the maximum container
storage pressure.
Provide manual service shut-off valves and lock-out provisions at the user
locations.
Provide properly sized flow limiters on each distribution line, as close as possible
to the gas source.
3.2.4.3 Ventilation
Monitor ventilation for failure with alarms that sound locally and at a constantly
attended location.
Locate room exhaust ducts no more than 6 inches (15.2 cm) from the floor level,
and at ceiling level to eliminate the pocketing of harmful vapors.
3.2.4.4 Electrical
11
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Provide interlocks to shut off all equipment, with the exception of ventilation,
upon detection of a vapor concentration of 40 percent of the lower explosive limit.
Provide a wet pipe sprinkler system throughout the facilities, including exhaust
hoods and storage cabinets, hydraulically designed to deliver a density of 0.30
gpm per ft2 (12 L/min/m2) over any including the most remote 3,000 ft2 (280 m2)
area of application. Protect duct systems with open-head sprinklers controlled by
a readily accessible valve.
3.2.5 Operations
Do not store or use unrelated combustible materials within the storage room.
Conduct leak tests at least annually to ensure the integrity of the entire supply
piping system.
Provide Emergency Stop stations within each fire area in case of failure or
damage to the supply piping.
Arrange the system to sound an alarm locally and at the facility proprietary
alarm console in the event of Emergency Stop operation.
This standard applies to the outside storage of liquefied petroleum gas (LPG),
flammable and combustible liquids and associated equipment.
table 3.3.a.doc
12
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
table 3.3.b.docx
Locate unprotected fuel unloading stations at least 100 ft. (33 m) from the
nearest buildings or at a distance prescribed by applicable codes or regulations,
whichever is greater.
Provide protection for fuel unloading stations located within 100 ft. (33 m) of any
building.
Locate and/or protect above ground storage tanks per Table 3.3.a.
13
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Surround tank vents, filler pipes and pumps with dikes of sufficient capacity to
contain any overflow.
This standard applies to all new and existing fluid fill operations.
Use minimum Schedule 40 welded carbon steel pipe for fuels and 100%
windshield washer solvent.
Use minimum Schedule 40, 304 stainless steel pipe for water/windshield washer
solvent mixtures.
Use either double pass socket welded, gasketed flange with 150 PSI (10.34 bar)
welded type flanges or mechanically attached fittings for all piping connections.
Mechanically Attached Fittings (MAF) must not rely on O-rings, elastomeric, or
rubber seals to provide a leak-free joint. MAF must be permanent compression
style fittings which cannot be disassembled and reused. Avoid threaded piping
due to increased leakage potential.
If the floor grating or plating in the dispensing area is to be covered with matting,
use only conductive materials. If located over grating, use only matting with
openings representing at least 40% of the surface area.
14
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Provide a fuel/water separator for the recovery of flammable fluids for all pit
installations that have an automatic water wash system.
Provide spill containment and/or a special drainage system for dispensing areas
without pits. Provide spill containment drainage that will allow the fluid to flow to
a common collection point. Provide an accessible collection point for clean-up,
recovery, or maintenance by qualified personnel.
Ensure tubing used for processing, transferring, or dispensing of fluids meets the
following requirements:
Use carbon steel tubing for fuels and 100% windshield washer solvent.
Use minimum 304 stainless steel tubing for windshield washer solvent
mixtures.
Determine tubing wall thickness for each diameter based on 3000 psi
working pressure after de-rating factors are applied.
Ensure all tubing connections meet the same conditions as piping specifications
as per 3.4.1.
Install a noncombustible vapor barrier along the traffic aisles on either side of the
classified area to limit the extent of the electrical classification boundary for
above grade areas. The installation of this barrier will eliminate the need for
rated electrical equipment in the aisle. Extend the barrier 25 feet (7.62 m)
15
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
beyond the fluid dispensing area.. Install self-sealing exit doors in the barrier
walls as required.
3.4.2.4 Ventilation
Equip each exhaust ventilation fan with a dedicated differential airflow switch.
Prove airflow before the dispensing equipment can be activated and other
interlocks enabled.
Automatic Sprinklers
Provide automatic sprinkler protection over, and for 20 ft (6.1 m) beyond, the
classified fuel dispensing area on a designed density of 0.60 gpm/ft2 (24.5
lpm/m2). Include protection under any overhead obstructions such as ductwork,
mezzanines, stairways, piping assemblies, etc.
Where drip pans are provided in pits or trenches and the area beneath the
pans are part of the exhaust system
Provide any pit areas deeper than 3 ft. (.91m) with automatic sprinkler protection.
16
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Maintain the floor around the windshield washer test area free of accumulations
of the windshield washer fluid.
Provide flammable gas detectors in adjacent pit areas where the potential for
vapor accumulation exists.
Refer to Table 3.4.3.4 for required fluid fill process and alarm interlocks.
table 3.4.3.4.xls
The fire alarm control panel must be placed outside the classified area, visible to
operators, and easily accessible.
3.4.3.5 Operations
To minimize sources of ignition, do not start the vehicles within the vapor barrier.
Do not connect the battery or conduct other electrical tests within the vapor
barrier.
Clearly label the dispensing area and floor as "No Smoking" and "Restricted
Ignition Source".
After fueling, install fuel filler cap within the fluid fill area.
17
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Arrange all automatic and manual dispensing equipment to automatically shut off
after the delivery of the preset quantity of fluid.
Chill fuel (if required) through an indirect method such as shell and tube or
brazed plate heat exchangers.
Perform a field acceptance test, per a site-specific test matrix, for new
installations and major renovations. Complete acceptance testing prior to
introduction of fluids.
Properly trained personnel must perform annual fire protection systems and
interlock testing per a site-specific test matrix.
Description: Protection requirements for exhaust air ductwork and collectors are
based on type of coolant used in the operation, physical dimensions, and
accumulation and combustibility of residues.
Ensure at least one of the following conditions is met for all ductwork having a
cross sectional area greater than 100 in.2 (0.0645 m2):
If the residue is combustible, provide sprinkler protection for the collectors and/or
filters.
18
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Provide sprinkler protection in all ductwork having a cross sectional area greater
than 100 in.2 (0.0645 m2).
Locate combustible yard storage at least 100 ft {30.5m} from all important
buildings, pipe racks, flammable liquids storage areas and electrical substations.
Maintain non-combustible yard storage a minimum of 50 ft. {15m} from the
buildings for manual firefighting access.
Limit pile sizes to 2,500 ft2 {232.5m2}. Long, narrow storage piles are preferred
to square blocks.
The following sections outline basic requirements for fire prevention and
protection when using hydrogen as a fuel for vehicles. Due to the many
variables that could affect the requirements, an engineering review is required
19
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Arrange room ventilation to maintain the vapor concentration below 25% of the
Lower Flammable Limit (LFL). Base calculations on the largest probable release
aside from a full tank rupture.
For fixed piping hydrogen delivery systems into a room, interlock the ventilation
with the hydrogen gas valve so the valve will not open if the ventilation is not
operating.
The following are required for rooms using both hydrocarbons and hydrogen:
3.7.1.2 Electrical
Intrinsically safe
20
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
3.7.1.3 Protection
Interlock all process equipment, including the fuel supply, to automatically shut
off In the event the vapor concentration reaches 40 percent of the LFL. Ensure
exhaust ventilation remains on at all times.
Provide an audible alarm and a strobe mounted on the outside of each entrance
to the test cell and in the control room. The alarm and strobe must be activated
upon 20% LFL detection. Ensure the audible alarm is distinguishable from the
“Employee Evacuation” notification and sounds at the security proprietary control
console.
Provide clearly marked emergency manual shut off valves for fuel lines.
Do not permit smoking or the use of open flame in areas where flammable gas
vapors may be present.
Test cell operations include any small rooms such as engine or vehicle
dynamometer cells, noise and vibrations rooms, etc. where normally only one
21
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
vehicle would be undergoing tests. Due to the many variables that could affect
fire protection requirements, an engineering review is required. The
requirements below present the most restrictive approach based on large
volumes of hydrogen gas usage or release potential.
3.7.2.1 Location
Locate the test chamber(s) in which hydrogen fuel will be used adjacent to an
outside wall in a one-story building with no unrelated facilities or normally
occupied spaces installed above or below.
3.7.2.2 Construction
Isolate test chamber(s) from other occupancies, including control rooms and
adjacent test cells, by walls and ceiling having a fire resistance rating of two
hours and minimum blast resistance rating of 100 pounds per ft2 (4.8 kPa).
Construct exterior walls of lightweight materials or panels designed to relieve at a
maximum internal pressure of 20 lb/ft2 (13.3 kPa/m2).
Do not install viewing windows without prior approval from Global Security. If
approved, install viewing windows having explosion and/or impact resistance
commensurate with the test cell wall construction.
Provide appropriate exits from at least two points of basements or pits. Ensure
employee entrance into basements is in accordance with local or facility confined
space entry procedures.
3.7.2.4 Electrical
3.7.2.5 Protection
22
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Locate the hydrogen fuel source outside the test cell, and pipe the gas to the test
cell for use as needed.
Provide a valve (powered open, fail closed) on the hydrogen fuel source.
Interlock the valve to the hydrogen detection in the test cell such that a detected
level of 20% LFL will shut off the fuel supply.
3.7.3.1 Construction
Isolate lab hood operations from adjacent test operations by walls having a
minimum fire resistance rating of one hour.
Provide a secondary means of egress from a lab hood operations work area if
any of the following apply:
23
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Provide emergency lighting for any lab hood operation areas requiring a
secondary means of access to an exit.
3.7.3.2 Ventilation
Design ventilation to ensure that chemical vapors which originate from within the
laboratory hood systems are not re-circulated. Control the release of chemicals
into the laboratory through the use of enclosures or a method of capture to
prevent hydrogen or other flammable and/or combustible concentrations of
vapors from reaching any source of ignition.
Ensure laboratory hood face velocities and exhaust volumes are sufficient to
contain contaminants generated within the hood and exhaust them outside of the
laboratory building. Ensure the hood provides containment of the possible
hazards (or exhausts to the outdoors as in the case of hydrogen) and protection
for personnel at all times when chemicals are present in the hood.
Discharge air exhausted from the laboratory hoods above the roof at a location,
height and velocity sufficient to prevent re-entry of chemicals into the building
through ventilation air intakes.
In laboratories where single (or multiple) cylinders of hydrogen are used, ensure
the cylinders are kept in a cabinet and the cabinet has mechanical ventilation to
the outside. Provide sprinklers within the cabinet.
3.7.3.3 Electrical
24
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Provide Class I, Division 2 (Zone 2), Group B electrical equipment inside lab
hoods due to the potential for hydrogen vapors.
Where receptacles are located inside a lab hood, locate additional accessible
and clearly marked electrical disconnects within 50 ft (15m).
Locate controls for lab hood services (e.g. gas, air and water) external to the
hood.
3.7.3.4 Protection
Provide rooms containing Lab Hood Operations with a wet pipe automatic
sprinkler system capable of providing a density of 0.30 gpm/ ft2 (12.2 L/min/m2)
over the lesser of 3,000 ft2 (280 m2) or the entire area of application.
Ensure the following occurs in the event the vapor concentration increases to 40
percent of the LFL:
The high level vapor alarm sounds at the security proprietary alarm
console.
25
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
General
Prohibit the placement of the vehicle in a non-ambient area such as a paint booth
oven, climatic chamber, etc., without prior engineering review.
Do not involve the vehicle in crash testing without prior engineering review.
3.7.4.1 Location
Locate any area housing hydrogen fueled vehicles on which fuel system work will
be performed, adjacent to an outside wall in a one-story building with no
unrelated facilities or normally occupied spaces installed above or below.
Designate specific vehicle stalls for hydrogen fuel system operations, and
prohibit fuel system work outside these areas.
3.7.4.2 Construction
Isolate the garage operations from other occupancies by walls having a minimum
fire resistance rating of two hours.
3.7.4.3 Ventilation
Ensure the air handling system is capable of 6 air changes per hour in open
garage areas.
Place a hood over the stall(s) designated for fuel system work. Vent the hood
directly to the outdoors using mechanical ventilation capable of at least 1 cfm per
ft2 (28.32 L per 0.09 m2) of hood area.
3.7.4.4 Electrical
26
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Ensure any electrical equipment within the hood over the fuel system work area,
and 18 inches below the hood, is classified a minimum Class I Division 2 (Zone
2).
3.7.4.5 Protection
Install automatic sprinklers under the hood, over the fuel system work area.
Install hydrogen detection in the hood, arranged to sound an alarm when 20% of
the LFL is detected. Also ensure the hood ventilation is engaged, regardless of
its previous on/off position.
If the other portions of the building will be used for hydrogen vehicle storage or
non fuel system work, refer to the requirements of 3.7.5.
The following are general requirements for hydrogen fueled vehicles inside
buildings:
27
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Ensure any parked vehicle has the fuel shut off at the supply tank.
Flow Chart
3.7.5.docx
3.7.5.1 Location
3.7.5.2 Construction
3.6.5.3 Ventilation
Ensure air handling systems in open garage areas are capable of 6 air changes
per hour.
Provide the following for rooms where hydrogen fueled vehicles are kept within a
larger garage area:
A ventilation rate of 1 cfm per ft2 (28.32 L per 0.09 m2) of floor area.
28
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Perform air flow tests (with smoke) to verify that there is air movement
throughout the entire room and that there are no dead spaces where
hydrogen could be trapped. Refer to 3.7.1.1 General Conditions – Room
Ventilation.
3.7.5.4 Electrical
3.7.5.5 Protection
Install a hydrogen detection system at the ceiling to provide an alert in the event
of a leak. Arrange the system to alarm at 20% of the LFL.
Note: In very large garage areas, it may not be practical to install a detection
system in the entire building. It may be acceptable to designate an area
where hydrogen vehicles will be located and provide detection in this area.
5.0 REFERENCES
29
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
NFPA 55 – Standard for the Storage, Use and Handling of Compressed Gases
and Cryogenic Fluids in Portable and Stationary containers, Cylinders and Tanks
NFPA 58 – Liquefied Petroleum Gas Code
NFPA 70 – National Electrical Code
NFPA 72 – National Fire Alarm Code
NFPA 77 – Recommended Practice on Static Electricity
NFPA 80 – Standard for Fire Doors and Fire Windows
NFPA 255 – Standard Method of Test of Surface Burning Characteristics of
Building Materials
NFPA 496 – Standard for Purged and Pressurized Enclosures for Electrical
Equipment
GM NAO Piping Systems Identification Standards
7.0 DEFINITIONS
Chassis Dynamometer Operations are generally utilized for operating the total
vehicle on roll test beds and dynamometers to evaluate such items as emissions;
vibration; drive train; heating, ventilation and air conditioning (HVAC) and other
systems verification at normal atmospheric conditions. These operations may
also include allied repair facilities.
Engine Hot Test Operations are those in which production engines are cycled
with a fixed fuel piping system to determine operational characteristics prior to
delivery of engine to point of use.
Engine Test Cell Operations consist of severe structural and system testing for
development and durability. The hazards created by this type of testing require
additional protection both for life safety and property conservation. Examples
include high revolutions per minute (rpm), high load, elevated temperatures,
maximum power curve, and experimental components.
30
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Hydrogen Fuel Cell Test Operations are those in which fuel cells are cycled
with a fixed fuel system to determine operational characteristics. Fuel cell test
chambers are used to determine power curves and durability at high RPM and
load.
Hydrogen Fuel Fill Areas are approved locations, inside or outside of buildings,
where the process of refilling hydrogen cylinders (outside only) or the changing of
portable hydrogen cylinders is conducted.
Fuel Flow Operations consist of any conditioning carts, tanks, fueling systems,
flow conditions of carburetion, fuel injection, pumps, regulators, related
components and test equipment. These operations are generally conducted
within properly ventilated rooms, enclosures or booths rated for flammable or
combustible liquids with fixed or portable fuel piping systems.
Lab Hood Operations are those in which testing is conducted on a small scale
inside an approved laboratory hood. The lab test hoods are ventilated
enclosures designed to contain and exhaust fumes, gases, vapors, mists and
particulate matter generated within the hood interior. Lab hoods are used for the
experimental handling of open containers with small amounts of fuels.
31
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
sensors, and an automatic filling system. This reservoir and pump allow for more
consistent fuel delivery during testing.
Storage Garages are those areas strictly for the storage of vehicles and
equipment.
Vehicle Test Operations are those in which fuel cells and other engines are
cycled with a fixed fuel system (gasoline, hydrogen, compressed natural gas,
diesel fuels) to determine operational characteristics. Vehicle test operations are
used to determine power curves and durability under temperature extremes,
various atmospheric pressures, high RPM, and load.
32
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
8.0 APPENDIX
Separation
Points of access through roof areas over computer rooms should be secured to
prevent unauthorized entry.
Access to the computer room via tunnels, storm or sanitary sewers or other
means should be secured to prevent unauthorized entry.
Automatic Sprinklers
Additional Protection
If the subfloor is protected by CO2, the system should be designed on the basis
of a 50% concentration with a 20 minute hold time and interlocked as necessary
with air handling equipment and computer power. The need for a connected
reserve should be based on risk considerations, such as the critical nature of the
operations and the timeliness (less than 24 hours) of recharge services.
1 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
rooms, data storage rooms or in any surrounding support areas where infiltration
of the dry chemical powder is likely.
8.3.2.1 Engine Hot Test Areas, Chassis Dynamometer Areas and Fuel Flow
Operations
Drains
Size drains sufficiently to handle 1) the maximum possible rate of spillage and 2)
any agent which may be used for the removal of the spilled fuel or the discharge
from fire protection equipment.
Locate drains close to potential points of fuel spillage. The drains should direct
the spilled fuels and other liquids to a safe approved location.
2 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Arrange the drains so that liquid in the vertical riser of the drain will remain as
close to the floor level as possible, thereby preventing a major vapor volume. If
this is accomplished by traps, each trap should be vented through a flame
arrestor.
Piping
Fuel accumulated in an outside receiving tank may be pumped back to the main
supply tank or disposed of under controlled conditions.
Compressed natural gas piping should be clean internally and free of chips, scale
or other foreign matter.
Fuel lines should utilize a positive shut off valve and be capped or plugged
whenever disconnected. Abandoned or unnecessary fuel piping not in service
should be purged or removed.
Where piping in a building is exposed and under pressure, and a safety device
shuts off a fuel pump or pumps, a solenoid valve or valves should open to
provide pressure relief and drainage of fuel back to storage or outside receiving
tanks.
Piping should be designed to avoid the use of sealants and gaskets. When
required, sealants and gaskets should be compatible with the fuel within the
system.
Prohibit fuel lines to run through basements, tunnels, trenches or pits without
adequate ventilation and drain lines to interceptor tanks.
Proper hose routing and installation methods should be in accordance with the
manufacturers recommendations.
3 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Fuel Delivery
Liquid fuel should not flow by gravity from the tank farm to the test area, except
from day or header tanks, unless interceptors are sized to accept the maximum
possible leakage.
Where pump relief valves are employed for liquid fuels, they should be piped to
the fuel supply tank to which the pump is connected. Relief valves for
compressed natural gas systems should be vented to the atmosphere at a height
greater than adjacent buildings.
Design pumps and associated piping to be compatible with the fuels used.
Provide a remote emergency means, exterior to the pump rooms or test cells, to
shut off the flow of fuel from the distribution pumps.
8.3.2.1.3 Ventilation
Room Ventilation
4 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
If a mechanical system of air supply is required, the air supply should be placed
near the periphery of the area. Depending on the fuel characteristics, i.e., fuels
lighter than air, room ventilation systems may need to be modified to exhaust
near the ceiling as well as near the floor.
Monitor the ventilation through the use of contactors, motor starter interlocks and
air flow monitoring devices.
Engine Exhaust
Exhaust ducts should be connected to the engine or chassis exhaust outlet at all
times during engine and chassis operations to prevent discharge of carbon
monoxide into the room atmosphere.
Since exhaust ducts become hot during engine operation, fuel lines should be
effectively segregated from the ducts by suitable distance, adequate thermal
insulation or a combination of distance and insulation.
Determine the rate of engine exhaust ventilation for the largest engine on test
and operating at maximum speed. The vehicle exhaust evacuation system
should maintain a negative pressure with respect to room ventilation. Branch
ducts should be well designed with proper angle of entry.
Where diesel engines are tested, care should be taken to mitigate fires in the
engine exhaust ducts. This may require the addition of outside air to dilute the
residues to a safe level.
8.3.2.1.4 Electrical
5 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Where there is a critical need to protect the control equipment associated with
test functions, the control room concealed floor space should be arranged or
protected as indicated in 3.1.
Welding, open flame and sparks should be avoided. If these operations are
necessary, the applicable provisions of Chapter 1, Section 3.4 of this manual
should be followed.
Where test conditions require that both the fuel and the chassis/engine should be
conditioned with respect to changes in temperature, portable fuel systems may
be employed.
Portable containers should be of the type approved for flammable liquid storage
and handling.
The amount of liquid fuel to be kept in the environmental test cell for conducting
engine tests should not exceed five gallons (18.9L).
The amount of liquid fuel in the chassis gas tank should be kept to a minimum
consistent with the test program.
6 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
The following operations are included for storage and distribution of compressed
gases:
Regardless of the inherent safety designed and built into an installation, fire
prevention and safety depend on thorough training of personnel combined with
scheduled follow-up and refresher programs, constant supervision, continuous
maintenance and inspection, and good housekeeping programs in all phases of
the operations.
7 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
All rooms should have a grounded, non-sparking conductive floor coating and a
perimeter grounding bar.
Installation and labeling methods should comply with ANSI B31.3, A13.1,
General Motors NAO Piping Systems Identification Standards SD 3-95 and
applicable building codes.
At no time should smoking or the use of open flame be permitted in areas where
flammable gas vapors are present.
Welding, open flame and sparks should be avoided. If these operations are
necessary, the applicable provisions of the Chapter 1, Section 3.4 of this manual
should be followed.
Continuous monitoring for gas leaks should be provided for combustible and/or
toxic gases stored within the facility.
8 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Ventilation
Equations
1. Buried or Mounded
9 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
3. No Special Protection
Groups of tanks totaling over 60,000 gallons (227,100 L) should not be installed
without some form of special protection.
Spill Control
A high fluid level alarm should be provided for the sump collection point and
storage tank to prevent overflow into adjacent areas.
Fluid portable tanks that are not located adjacent to the fluid-fill area water wash
system should have spill containment. A means for detecting fluid leakage
should be present and should initiate an alarm within the spill containment area.
All hoses used for the transferring or dispensing of fluids should be chemically
compatible and have the capability of dissipating static electricity.
Fluids should be drawn from portable tanks through an opening in the top using
an anti-siphon valve.
Electrical
10 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
The vapor barrier will normally extend 15 ft (4.57 m) beyond the mechanical
ventilation. However, in instances where the mechanical ventilation extends
more than 10 ft (3.05 m) beyond the dispensing area, the vapor barrier need not
extend the full 15 ft (4.57 m) beyond the mechanical ventilation. The vapor
barrier must extend 25 ft (7.62 m) beyond the dispensing area.
Automatic Sprinklers
Water flow supervision should be provided for the dedicated sprinkler protection
in the dispensing area.
Detection
At least one detector should be provided outside of each fluid-fill area pit barrier
opening, and in accordance with the manufacturer's specifications for the
application. The detectors should initiate a trouble signal locally, and to the
proprietary alarm console, at 20% of Lower Flammable Limit (LFL). The
detectors should initiate an alarm signal locally and to the proprietary alarm
console, and initiate an emergency shutdown at 40% of the LFL.
Pull stations should be located a bay away up line, and a bay away down line, of
the fuel-fill operation.
The emergency stop buttons should be interlocked to close “fail safe” electrically
supervised shut off valves located as follows:
11 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
Each plant should have a specific matrix developed to cover the individual
operation.
The fluid dispensing area fire protection alarm system should be listed/approved
by a nationally recognized testing lab as “Automatic Extinguishing and Releasing
Equipment”.
Operations
The restricted ignition sources should include, but are not limited to, cell phones,
portable electronic devices, cutting, burning or welding.
Any proposals for use of specially designed fuel-fill nozzles for On-Board Vapor
Recovery Systems require additional review.
Yard Storage
Empty metal racks without dunnage or combustibles of any type can be used as
fire breaks in order to exceed the 2,500ft2 {232.5m2} pile size limitation. The
12 Appendix
Fire Prevention and Protection - Chapter 3
Protection of Special Hazards
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 3 Jim Ellis 09/29/09
General Conditions
8.3.7.1.3 Protection
Additionally, the test cell audible alarms and strobes can be actuated manually at
a local control panel or by activation of the E-stop.
Avoid welding, open flame and sparks. If these operations are necessary, the
applicable provisions of Chapter 1, Section 3.4 should be followed.
The typical laboratory hood should operate under negative pressure with face
velocities ranging from 80-120 linear ft/min (0.41-0.61 m/sec), with 100 linear
ft/min (0.5 m/sec) being most common.
Exhaust stacks should extend at least 10 ft (3 m) above the highest point of the
roof.
8.3.7.3.3 Electrical
13 Appendix
3.7 - Operations Involving Hydrogen Fuels
Yes
Will the hydrogen
Requirements as outlined in
be used in a lab?
Section 3.7.3
No
No
No
No Is this a hydrogen
fueled vehicle?
Yes
Requirements as outlined in
Section 3.7.5
No No
No
Yes
No
Yes
Yes
Yes No
ABOVEGROUND TANK STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS
CLASS I LIQUIDS
TABLE 3.3.a
NOTES
1. Diking may be required to protect buildings, access roads or for environmental purposes.
2. Intermediate diking which is at least 18 inches (0.5 meters) high is required within diked areas for each group of two or more tanks of Class I liquids or for
each group of four or more tanks of Class II and III liquids.
3. Portable foam application as minimum.
4. In no case less than 50 ft. (15 m) with consideration for prevailing wind.
5. Includes open vaults which have the tanks below or above grade. In no case less than 25 ft. (7.5 m) with consideration for prevailing wind.
6. Tank unloading station shall be protected if distance to important buildings is less than required for the tank farm.
ADDITIONAL REQUIREMENTS
1. The requirements for Class I liquids should be followed for combined tank farms.
2. Where Class I is segregated from Class II and III by barrier wall to top of tank heights within the same tank farm, fixed AFFF/water spray may
be omitted for Class II and III.
LIQUEFIED PETROLEUM GAS INSTALLATIONS
MINIMUM SPACING FOR LPG TANKS BASED ON PROTECTION LEVEL
TABLE 3.3.b
Major Buildings, Tank Farms, Etc.
FIELD DEVICE
INTERLOCK PROCESS EQUIPMENT INTERLOCKS SIGNALS TO BUILDING PROPRIETARY SYSTEM
Windshield Washer
General Trouble to
Air Supply House
General Alarm to
Valve Close
Valve Close
Fluid Panel
Sprinkler Flow to
Interlock
Building
Building
Panel
to Building
to Building
Building
Building
BLDG
INPUT DEVICE
Pit X
Stack X
Duct X
Water Flow X
Pull Station X
Smoke Detector X
LEL Detector X
Ventilation X
table 3.4.3.4
FLUID FILL PROCESS AND ALARM INTERLOCKS
Table 3.4.3.4
Control Panel General Trouble (process fault,
communications fault, etc) X
table 3.4.3.4
EQUATIONS FOR USE IN DETERMINING VENTILATION RATES IN
ENGINE TEST CELLS OR FUEL HANDLING AREAS
In determining the necessary ventilation required for safe operation of engine test cells
and other areas where fuel spills are possible, it is beneficial to look at the potential
situations quantitatively. The amount of air required will depend in a large part on the
possible amount of fuel spilled and the speed at which the fuel would evaporate. The
equations in this section will help in estimating the amount of air needed to dilute vapors
from a potential fuel spill to a mixture that will not ignite. (NOTE! These calculations are
approximate). The safety factors used when applying these equations should vary
relative to the potential for an accident.
The following values, used in the calculations, are at pressure = 29.92” Hg and
temperature = 70º F (P = 0.76 m HG, T = 21º C):
air density = 0.075 pounds per ft3 (1.2 kg/m3) 1.199 kg/m3
air equivalent molecular weight = 28.97
air vapor density = 1.0
1 gallon water = 8.35 pounds of water (1 Liter = 1 kg)
water specific gravity = 1.0
The example calculations are for gasoline, using the following average values as those
for gasoline vary widely.
gasoline (API = 60) specific gravity = 0.739
gasoline molecular weight approximately = 111
gasoline vapor density approximately = 3.8
lower explosive limit of gas in air (approximate) = 1.4 percent
Note: Values used in actual calculations should be those obtained from the Material
Safety Data Sheets for the fuels to be used in the test cells.
The following steps should be followed in order to calculate the approximate minimum
rate of ventilation required to maintain fuel vapor concentrations below minimum safe
levels:
Step 1. If the vapor density of the fuel is not known, it can be determined from the
molecular weight using the following formula:
Dv = MWfuel / MWair
Example:
Step 3. Determine the volume of air required to bring the air/vapor mixture to the
LEL using the following formula:
Step 4. Determine the volume of air required to bring the air/vapor mixture to 20%
of the LEL, the typical first warning level, as follows:
Step 5. Approximate the ventilation rate required to maintain the air volume
mixture below the LEL.
This may seem an inordinately small amount of dilution air, but that may be because all
of this ventilation must be directed at the area of spill in order to be effective. The
ventilation rate for the room as a whole would need to be higher to ensure that the
minimum rate is available at anticipated spill locations. Other major factors to consider
when designing safety ventilation are possible rate of fuel spill, possible rate of
vaporization, locations of possible spills, and exhaust ducting proximity to the expected
level of fuel vapor accumulation.
Fire Prevention and Protection - Chapter 4
Building Construction
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
1.0 PURPOSE
2.0 SCOPE
The following standards assist in ensuring GM facilities are constructed with
materials that will support the level of safety and property conservation needed.
3.0 STANDARDS
See also the Worldwide Facilities Group, Capital Projects, GM One Spec Facility
Construction Specification for details regarding construction.
3.2 Roofs
Ensure all roof assemblies have a Class “A” exterior fire exposure rating as
defined by the Underwriters Laboratories, Inc., Factory Mutual Research
Corporation or other recognized testing laboratories.
3.3 Walls/Barriers/Separation
1
Fire Prevention and Protection - Chapter 4
Building Construction
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
Protection requirements and other guidelines for warehousing and storage can
be found in Chapter 2, 3.6, Warehousing.
2
Fire Prevention and Protection - Chapter 4
Building Construction
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
3.4 Exposures
5.0 REFERENCES
3
Fire Prevention and Protection - Chapter 4
Building Construction
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
8.0 APPENDIX
There will be limitations as to the degree to which a building code can be applied
to existing structures. However, in the case of existing buildings, there may be
certain improvements that are necessary to achieve overall fire safety.
8.3.2 Roofs
All joints should be sealed to prevent hot bitumen from dripping in the event of
fire. All joints are covered with strips of asphalt-coated organic felt set in roof
cement. An underlayment of two plies of asphalt glass felt is applied to the deck
in hot asphalt. Board type insulation made of glass fiber, polyisocyanurate, wood
fiber, mineral products, or other material is applied directly to the underlayment in
a full mopping of hot asphalt. A second layer of insulation may be applied to the
first in a full mopping of hot asphalt. A Class “A” roofing membrane is then
applied to the insulation.
Standard Metal Roof Decks Covered with a Non-combustible Type of Vapor Seal
Membrane
1 Appendix
Fire Prevention and Protection - Chapter 4
Building Construction
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
Board type insulation made of materials listed above is applied over the metal
deck, with mechanical fasteners at a rate of one per two sq. ft. of insulation area.
A second layer of insulation may be applied to the first in a full mopping of hot
asphalt. A Class “A” roofing membrane is applied to the insulation. Metal deck
roof construction and all materials used therein should meet the requirements for
metal deck constructions in the Underwriters Laboratories, Inc. Roofing Materials
and Systems Directory and the Factory Mutual Approval Guide that are classified
as to spread of fire on the underside of the deck and/or resistance to uplift forces.
Equivalent ratings by other recognized testing laboratories may also be
considered upon acceptance of Global Security.
In multiple story structures such as office and engineering buildings, the HVAC
system should be utilized to accomplish venting through pressurization,
shutdown, exhaust, zoning or other specific smoke control features.
In certain high hazard manufacturing occupancies such as heat treat and engine
hot test operations, venting and deep draft curtains should be installed. Draft
curtains and closely spaced sprinklers should be installed around conveyor or
other large floor openings. Draft curtains may also be required at points where
there are substantial changes in roof elevations and between sprinkler systems
with different response factors (e.g. ESFR and standard sprinklers).
In areas where vents and /or draft curtains are required, the following conditions
should be met:
2 Appendix
Fire Prevention and Protection - Chapter 4
Building Construction
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
Roof vents should be located at or near the center of small rooms or draft
curtained areas less than three bays. In larger areas, vents should be located
symmetrically, in regular patterns and spacing.
Certain extra hazard areas such as flammable liquid storage, paint mix and
storage rooms, polyurethane storage and tire storage, should preferably be
located in separate buildings. If placement is necessary in the main structure,
these rooms should be located in accordance with the applicable chapters of the
General Motors Global Security Manual, Fire Prevention and Protection Section,
and model building codes.
3 Appendix
Fire Prevention and Protection - Chapter 4
Building Construction
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
Extra hazard areas should not be located adjacent to, under or over cafeterias,
toilet rooms and other enclosed areas where employees might be trapped in
case of fire.
The size of any single building area should be determined by referring to local
standards and considering the following factors:
Egress of building occupants
Occupancy, i.e., manufacturing, warehousing, assembly, etc.
Isolation of high hazards
Business continuity
These areas do not need to be subdivided into fire areas, except as determined
by the Authority Having Jurisdiction or management with regard to single source
plants or other critical or unique processes with substantial business interruption
potential.
4 Appendix
Fire Prevention and Protection - Chapter 5
Fire Protection Systems and Equipment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
1.0 PURPOSE
This chapter provides standards and additional information with regard to fire
protection systems and equipment.
2.0 SCOPE
3.0 STANDARDS
General Requirements
Provide at least one independent and reliable source of water supply for sprinkler
systems and all other fire-fighting equipment.
The water source must be both adequate and reliable in duration, volume, pressure
and rate of flow to meet the highest fire challenge on the property.
Depending upon the size, hazard, values and criticality of the facility, a second
water source may be required. Size this source to match the primary source to
ensure the necessary redundancy.
Duration
For facilities of 100,000 ft2 (9,300 m2) or less, the duration of each required
water supply must be at least 60 minutes.
For facilities of greater than 100,000 ft2 (9,300 m2), the duration of each
required water supply must be at least 120 minutes.
Factors such as plant size, hazard, value, and availability of municipal services may
dictate water supplies of greater duration.
1
Fire Prevention and Protection - Chapter 5
Fire Protection Systems and Equipment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
Where the public water system alone cannot be considered an adequate and
reliable water source, appropriately sized ground level tanks, reservoirs or other
sources of supply are required.
General Requirements
Fire pumps are required anywhere the public water system cannot satisfy the sum
total of the following:
Depending upon the size, hazard, values and criticality of the facility, a second
pump and supply may be required. The pump must be sized to match the primary
pump to ensure the necessary redundancy.
Provide dual discharge lines into the fire protection underground system where
multiple fire pump installations are arranged within a single pump house.
General Requirements
The water supply facilities must discharge into an underground piping system of
sufficient size to supply the highest anticipated water demand for the hazards
involved.
Depending upon the size, hazard, values and criticality of the facility, it may be
necessary to loop the underground piping, or ring main, around each major
building.
Loop piping where any dead end portion of the underground supplies more than a
combined total of five sprinkler risers and/or hydrants.
2
Fire Prevention and Protection - Chapter 5
Fire Protection Systems and Equipment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
Valves
Provide sectional control valves on the underground distribution piping such that
there are no more than a combined total of five sprinkler risers and/or hydrants
between valves.
Provide a control valve for each sprinkler system. This may be either a post
indicator valve (PIV) on the lead-in piping or a valve on the sprinkler system riser.
Lead-Ins
Size sprinkler system lead-in piping based on the maximum hydraulic demand of
the system, but no smaller than 6” (150 mm) in diameter.
Hydrants
Supply a sufficient number of yard hydrants for hose stream protection for exterior
areas of all buildings.
Locate hydrants so that the required hose streams can provide an adequate
concentration of water for any building or group of buildings, with spacing not to
exceed 500 ft. (152 m).
Use only ordinary temperature rated 135º F – 170º F (57º C - 77º C) sprinklers,
except in those areas where the ambient temperature dictates the use of higher
temperature heads.
3
Fire Prevention and Protection - Chapter 5
Fire Protection Systems and Equipment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
Connect 100 ft (30.5 m) maximum lengths of fire hose with combination hose
nozzles to hose drops with suitable racks, reels or in boxes throughout all buildings.
Ensure the number and placement of hoses is such that all areas of the building
can be reached by at least one hose stream.
Install hose reels in high piled warehousing and other catastrophic hazard areas so
that any point in the storage can be reached by two hose streams.
Provide and arrange fire hose connections and cabinets such that hose streams
can reach designated hazard areas of the roofs.
Ensure a sufficient amount of fire hose and combination nozzles are available for
use with the roof hose connections.
Design special extinguishing systems for a full discharge into the largest hazard
area. Design and install these systems in accordance with local codes and
manufacturers’ instructions.
4
Fire Prevention and Protection - Chapter 5
Fire Protection Systems and Equipment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
Ensure all components used in special extinguishing systems are listed and/or
approved for their intended purpose by a recognized testing laboratory.
Place a sufficient number of portable fire extinguishers of the proper type and size
throughout all facilities. Distribute the units in accordance with local code
requirements.
Water flow (both wet and dry pipe) for each sprinkler riser
Multiple story buildings must have a water flow device for each feed from the
main riser
Excess and low air pressure for dry pipe and pre-action systems
Manual fire alarm boxes
Post indicator, sectional control, OS&Y and indicator butterfly valves where
valves are exposed to the public
As an alternative to monitoring, valves may be locked open with hard shank
locks.
Fixed fire extinguishing equipment (gaseous systems, wet and dry chemical,
water spray, etc.)
Heat detection equipment (rate of rise, fixed temperature, etc.)
Smoke detection equipment (ionization, photoelectric, etc.)
Building temperature (critical areas or warehouses, truck centers or
training centers which do not have 24-hour security)
5
Fire Prevention and Protection - Chapter 5
Fire Protection Systems and Equipment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
7.0 DEFINITIONS
Highest Fire Challenge: The highest fire challenge is based on sprinkler demand,
including a 10% allowance for hydraulic imbalance, and simultaneous hose stream
demand.
Source: The actual origin of, or facility containing, the water supply, such as: a
lagoon, lake, reservoir or other body of water; a series of wells; city water system;
or a man-made facility such as an underground reservoir, ground level (suction)
tank, etc.
6
Fire Prevention and Protection - Chapter 5
Fire Protection Systems and Equipment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
Supply: The quantity of water of known volume, pressure and rate of flow
immediately available for fire automatic and manual fire suppression.
7
Fire Prevention and Protection - Chapter 5
Fire Protection Systems and Equipment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
8.0 APPENDIX
For limited areas (20 sprinklers for ordinary hazard occupancies and 15
sprinklers for extra hazard occupancies) under obstructions such as platforms
and conveyor screen guards, sprinklers may be installed on a pipe schedule
basis. To ensure adequate protection, the point of connection for the above
sprinklers should be at least two pipe sizes larger than the pipe schedule.
The maximum base of riser pressure demand should not exceed 90 psi (6.1
bars). Additional hydraulic calculations to the discharge side of the pump(s) are
required to verify that the hose and sprinkler system water demands can be met.
1 Appendix
Fire Prevention and Protection - Chapter 5
Fire Protection Systems and Equipment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
Exceptions for higher base of riser pressure demand may be made on a case-by-
case basis if the facility has fire pumps in excess of 125 psi (8.6 bars) net rated
pressure. Also, excess of 90 psi (6.1 bars) is permitted if ESFR sprinkler
systems are employed.
Hose outlets should utilize the same thread standard as the local fire service. In
situations where different thread standards exist, adapters should be available.
Examples of designated hazard areas on roofs include paint shops, heat treat
areas, oven enclosures, combustible cooling towers, and dust collectors.
It is preferred that hose be kept in the roof hose cabinets, pre-connected to the
water supply. However, it is acceptable to have hose packs available at nearby
roof entrances.
Hose outlets should utilize the same thread standard as the local fire service. In
situations where different thread standards exist, adapters should be available.
Special extinguishing systems generally include fixed fire protection other than
automatic sprinkler systems. Specific examples are local application or total
flooding gaseous, wet or dry chemical, foam and water spray systems.
2 Appendix
Fire Prevention and Protection - Chapter 5
Fire Protection Systems and Equipment
Author Technical Contact Revision Approver Name Effective Date
Level
Global Security Tim Sullivan 2 Jim Ellis 09/29/09
An adequate number of personnel, located such that any local alarm can
be readily detected and investigated, and proper response initiated
In addition to those items listed in the standard, the following are recommended:
3 Appendix
Fire Prevention & Protection - Chapter 6
Fire Alarm System Standard
Author Technical Revision Approver Name Effective Date
Contact Level
Global Security Tim Sullivan 1 Jim Ellis 11/04/10
1.0 PURPOSE
This chapter provides standards and additional information with regard to fire
alarm systems and equipment.
2.0 SCOPE
3.0 STANDARDS
Install and maintain a fire alarm system to provide detection of a fire or other
emergency conditions and initiate occupant notification appliances.
An initiating device must activate a signal to a fire alarm control unit. The fire
alarm control unit must indicate, alphanumerically, the specific information about
the signal including the type of signal (alarm, trouble, reset), device type and
exact device location.
Monitor the system for events using a constantly attended monitoring station.
3.2 System
A complete fire alarm system consists of initiating devices, fire alarm control
units, and notification appliances. Connect all fire alarm control units to create a
single networked system per building or group of buildings. Control the entire fire
alarm system with a single head end control unit.
The facility may subscribe to a service providing remote alarm monitoring. This
service may supplement a locally monitored system. Use a service that is
approved by an independent authority or testing laboratory.
The facility may subscribe to a service providing a central monitoring station and
also monitor the proprietary system locally as needed. In addition to the central
monitoring service requirements above (section 3.3.1), provide local staff with a
software application designed to provide a user interface to manage and monitor
the complete system. The proprietary system does not need to be constantly
attended when combined with a central monitoring service.
Fire Prevention & Protection - Chapter 6
Fire Alarm System Standard
Author Technical Revision Approver Name Effective Date
Contact Level
Global Security Tim Sullivan 1 Jim Ellis 11/04/10
4.0 RECORDS
Record the results of a complete system test and inspection annually or more
frequently as required by local regulations.
5.0 REFERENCES
7.0 DEFINITIONS
Head End
A control unit which sends and receives signals from the other control units on
the system network.
Initiating Device
A system component that originates transmission of a change-of-state condition,
such as in a smoke detector, manual fire alarm box, or supervisory switch.
Notification Appliance
A fire alarm system component such as a bell, horn, speaker, light, or text display
that provides audible, tactile, or visible outputs, or any combination thereof.
Notification System
A system for the protection of life by indicating the existence of an emergency
situation and communicating information necessary to facilitate an appropriate
response and action.
Proprietary System
A supervising station under the same ownership as the protected premises fire
alarm system(s) that it supervises (monitors) and to which alarm, supervisory, or
trouble signals are received and where personnel are in attendance at all times
to supervise operation and investigate signals.
8.0 APPENDIX
Design the system to provide clear intelligible messages to the entire occupied
premises. Use the voice communication system for the intended purpose only.
Non life safety usage of the system (i.e., shift break tones) must not hinder
emergency notification messages. Emergency notification must take priority over
any other use of the system.