30RBP 360A
Air-cooled scroll chiller with Greenspeed® Intelligence
Performance Information
Mode Cooling
Cooling Capacity (1) ton 82.10
Cooling Efficiency (COPR) (1) kW/kW 1.894
Energy Efficiency Ratio (EER)
(1) Btu/(W.h) 6.463
(1) All
performances are compliant with AHRI Standard 550/590 (IP). Sound Power level according to
ISO9614-1.
Due to the minimum flow rate allowable, a lower inlet water temperature might have to be specified to Non contractual picture
(2) achieve this performance.
Seasonal Efficiency
Operating Conditions
IPLV.IP Btu/(W-hr) 17.07
System element Cooling
Water heat exchanger
Fluid Type Fresh Water Unit Information
Fouling Factor(3) (hr-sqft-F)/BTU 0.000250 Manufacturing Source Montluel
Leaving Temperature °F 44.00 Refrigerant type R410A
Fluid
Refrigerant Weight lb 90
Entering Temperature °F 54.00
Tonnes CO2 Equivalent Tonnes 85.1
Fluid Flow gpm 186.2
Number of Refrigerant Circuit 2
Total Pressure Drop ft-H₂O 4.65 Number of Passes (Evaporator) 1
Air heat exchanger Number of Compressor 6
Entering Air Temperature °F 118.4
Air
Number of Fan 6
Altitude ft 0 Fan Power Input kW 8.34
(3) The impact of fouling factor is calculated as per AHRI 550/590-551/591 method Operating / Shipping Weight lb 4784/4712
Unit Dimensions (LxWxH) in 142x89x91
Unit Configuration
149 Bacnet over IP Electric Information
15 Low noise level Unit Voltage V-Ph-Hz 400-3-50
20A IP54 control box Standby Power kW 0.397
23A Enclosure panels Power Factor 0.883
331 Plastic tarp Electrical Circuit Supply 1
92A Compressor suction and discharge valves Maximum Current A 287
EMB_SKID Packing specially designed for 40’ high cube loading units Startup Current A 498
CONTAINER Current at AHRI Conditions A 215
Documentation
PSD
IOM
Technical drawing
Revit file
Outside the scope of AHRI Air-Cooled Water-Chilling Packages Certification Program, but is rated in accordance with AHRI Standard 550/590
(I-P) and AHRI Standard 551/591 (SI).
Page 1/1