You are on page 1of 1

Standard report Project

ATE Camp Project-Kuwait


Tag
Gaurav Vispute (3/24/2022 10:41:01 AM) CH-1A

30RBP 360A
Air-cooled scroll chiller with Greenspeed® Intelligence

Performance Information
Mode Cooling
Cooling Capacity (1) ton 82.10
Cooling Efficiency (COPR) (1) kW/kW 1.894
Energy Efficiency Ratio (EER)
(1) Btu/(W.h) 6.463

Unit Power Input (1) kW 152.4


Sound power level (LwA) (1) dB(A) 92.0
Sound Pressure Level at 32.8ft
dB(A) 59.8
(LpA) (1)
Minimum Capacity (2) ton 14.51
Maximum Capacity ton 82.10

(1) All
performances are compliant with AHRI Standard 550/590 (IP). Sound Power level according to
ISO9614-1.
Due to the minimum flow rate allowable, a lower inlet water temperature might have to be specified to Non contractual picture
(2) achieve this performance.

Seasonal Efficiency
Operating Conditions
IPLV.IP Btu/(W-hr) 17.07
System element Cooling
Water heat exchanger
Fluid Type Fresh Water Unit Information
Fouling Factor(3) (hr-sqft-F)/BTU 0.000250 Manufacturing Source Montluel
Leaving Temperature °F 44.00 Refrigerant type R410A
Fluid

Refrigerant Weight lb 90
Entering Temperature °F 54.00
Tonnes CO2 Equivalent Tonnes 85.1
Fluid Flow gpm 186.2
Number of Refrigerant Circuit 2
Total Pressure Drop ft-H₂O 4.65 Number of Passes (Evaporator) 1
Air heat exchanger Number of Compressor 6
Entering Air Temperature °F 118.4
Air

Number of Fan 6
Altitude ft 0 Fan Power Input kW 8.34
(3) The impact of fouling factor is calculated as per AHRI 550/590-551/591 method Operating / Shipping Weight lb 4784/4712
Unit Dimensions (LxWxH) in 142x89x91

Unit Configuration
149 Bacnet over IP Electric Information
15 Low noise level Unit Voltage V-Ph-Hz 400-3-50
20A IP54 control box Standby Power kW 0.397
23A Enclosure panels Power Factor 0.883
331 Plastic tarp Electrical Circuit Supply 1
92A Compressor suction and discharge valves Maximum Current A 287
EMB_SKID Packing specially designed for 40’ high cube loading units Startup Current A 498
CONTAINER Current at AHRI Conditions A 215

Documentation
PSD
IOM
Technical drawing
Revit file

Outside the scope of AHRI Air-Cooled Water-Chilling Packages Certification Program, but is rated in accordance with AHRI Standard 550/590
(I-P) and AHRI Standard 551/591 (SI).
Page 1/1

Package Chiller Builder-EMEA v4.28.0.0 (date 2/28/2022)

You might also like