S.No Description
.
2) Repeater Panel with 960 Character LCD Display, repeater Panel CPU should have the same intelligence and capability
of panel CPU. UL Listed & FM approved
3) Intelligent Addressable self decsion making ,microprocessor based Multi-Sensor smoke and Heat detector, optical
type having 20 pre alarm senstivity settings and 5 alarm senstivity settings, Wide Sensitivity 0.5 to 4.36 %/ft. (1.6
to 13.6 %/m) smoke obscuration with Bicolor (green/red) status LED indicator on each detector and being capable of
addressed electronically. The microprocessor’s non-volatile memory shall permanently store the detector’s serial
number, device type and system address. Manual Addressing (Dip/ Rotary Switches) not preferred)Detector should
have its own memory.Swapping same type of detectors to different base should not call for reprogramming.
UL 268 7th edition and FM approved
3) Intelligent Addressable microprocessor based heat detectors with operating temperature of 57 deg C & 8.3 deg
C/min rate of rise of temperature, Bicolor (green/red) status LED indicator on each detector and being capable of
addressed electronically. The microprocessor’s non-volatile memory shall permanently store the detector’s serial
number, device type and system address. Manual Addressing (Dip/ Rotary Switches) not preferred .Detector should
have its own memory.UL Listed and FM approved
4) Intelligent Self decision making Addressable microprocessor based Smoke detector, optical type having 20 pre
alarm senstivity settings and 5 alarm senstivity settings, Wide Sensitivity 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m)
smoke obscuration with Bicolor (green/red) status LED indicator on each detector and being capable of addressed
electronically. The microprocessor’s non-volatile memory shall permanently store the detector’s serial number,
device type and system address. Manual Addressing (Dip/ Rotary Switches) not preferred.The detector should have
its own memory. UL 268 7th edition and FM approved.
586190106.xls 04/06/2022
Page 2
5) Intelligent Addressable Self decisoon making microprocessor based Smoke detector with Sounder Base, optical type
having 20 pre alarm senstivity settings and 5 alarm senstivity settings, Wide Sensitivity 0.5 to 4.36 %/ft. (1.6 to
13.6 %/m) smoke obscuration with Bicolor (green/red) status LED indicator on each detector and being capable of
addressed electronically. The microprocessor’s non-volatile memory shall permanently store the detector’s serial
number, device type and system address. Manual Addressing (Dip/ Rotary Switches) not preferred.The detector must
have its own memory.Swapping same type of detectors to different base should not call for reprogramming.UL 268
7th edition and FM approved.
6) Intelligent Addressable microprocessor based Duct detector capable of being addressed electronically with duct
piping. The microprocessor’s non-volatile memory shall permanently store the detector’s serial number, device type
and system address Manual Addressing (Dip/ Rotary Switches) not preferred ..Swapping same type of detectors to
diffrent base should not call for reprogramming. UL Listed & FM approved
7) Intelligent Addressable Double action manual pull station, capable of being addressed electronically. Manual
Addressing (Dip/ Rotary Switches) not acceptable, complete as required.and as per specifications. UL Listed & FM
approved
8) Fire Alarm LED Hooter cum Strobe (sound output of minimum 85 dB, Light output: 15, 30, or 75 candela ) made
Addressable with the help of Intelligent Addressable Signal Module, with seperate power supply arrangement
complete as required and suitable for wall/ceiling mounting and as per specifications. UL Listed
9) Addressable Signal control module complete as required for Hooter cum strobe Notification devices, capable of being
addressed electronically. Manual Addressing (Dip/ Rotary Switches) not preferred, complete as required.and as per
specifications. UL Listed & FM approved
10) Addressable control module complete as required for switching ON of smoke extraction fans / Pressurisation Fans
etc. and switching off AHU' s, capable of being addressed electronically. Manual Addressing (Dip/ Rotary Switches)
not preferred, complete as required.and as per specifications. UL Listed & FM approved
11) Addressable Monitor module complete as required for monitoring flow switches/ interface with any third party
equipment capable of being addressed electronically. Manual Addressing (Dip/ Rotary Switches) not preferred,
complete as required.and as per specifications. UL Listed & FM approved
12) Addressable Fault Isolator module complete as required for determining the short in a circuit and separating the
segment having the short capable of being addressed electronically. Manual Addressing (Dip/ Rotary Switches) not
preferred, complete as required.and as per specifications. UL Listed & FM approved
13) Speaker ceiling / wall mounting arrangement (0-2 watts) with multiple taping 1/4,1/2,1 and 2 watt tapping,
complete as per specification and should be UL listed and the same make of Integrated Fire Alarm System.
14) 15 W Wall Mounted Type Horn Type Speaker with Multi Tapping Feature complete as per specification and should be
UL listed and the same make of Integrated Fire Alarm System
15) Response indicator with LED display for all detectors located above false ceiling.Response Indicator should be of the
same make as panel & detectors and UL Listed & FM approved. Other make brand is not approved,
16) Intelligent Addressable 20 watts/40 Watts/ 95 Watts amplifier as required, shall be mounted on the rail chasis of Fire
Alarm Panel enclosures or inside remote closet cabinet with the requisite Intelligent Addressable power supply to
drive these amplifiers, capable of being addressed electronically. Manual Addressing (Dip/ Rotary Switches) not
acceptable, complete as required. The amplifier and Powers upply shall be same make of the panel. UL Listed & FM
approved
17) Supply, Installation, Testing and Commissioning of Graphical software ( same make as of panel) with compatible PC
system along with Printer & UPS ,complete in all respect as required and as per specifications. The system should be
capable of establishing IP connectivity in Graphics software to take multiple system inputs from multiple panels .
Highlighting an event in the “Event List Viewport” shall automatically cause the display of the map viewport and
other configured viewports to display information relative to the highlighted event. UL listed
586190106.xls 04/06/2022
Page 3
18) 2 x 1.5 sq mm PVC sheathed copper conductor 1100 volts grade flexible FRLS wires of approved make in concealed
or surface mounted existing 25 mm dia MS conduit including fixing, supporting, saddling & flexible conduit etc
complete in all respect.
19) 4 x 1.5 sq mm PVC sheathed copper conductor 1100 volts grade flexible FRLS wires of approved make in concealed
or surface mounted existing 25 mm dia MS conduit including fixing, supporting, saddling & flexible conduit etc
complete in all respect.
20) 2 x 1.5 sq mm twisted shielded PVC sheathed copper conductor 1100 volts grade flexible FRLS cable of approved
make in concealed or surface mounted existing 25 mm dia MS conduit including fixing, supporting, saddling &
flexible conduit etc complete in all respect.
21) Supply Installation testing and commissioning of the following 16 guage 25 mm MS rigid conduits recessed in RCC
walls or clamped on surface in ceilings including clamps hardwares etc. complete as per specifications. Quoted price
shall include GI flexible conduits to connect from ceiling to false ceiling.
TOTAL
APPENDIX - I
S. Details of Materials
No.
2) Detectors/Hooters/Manual Call
5) Monitor
6) Cables
7) Conduits
586190106.xls 04/06/2022
Page 4
Edwards FSB-PC2
+FSB-BRKT2
586190106.xls 04/06/2022
Page 5
Edwards SIGA-CC1
Edwards HPSA15R257
0
Edwards SIGA-LED
586190106.xls 04/06/2022
Page 6
RM
RM
RM
RM
TAL Rs. 0
APPENDIX - I
Manufacturer's Name
586190106.xls 04/06/2022