UL & FM INTELLIGENT ADDRESSABLE FIRE ALARM AND EVACUATION SYSTEM WITH FIRE FIGHTER TELEPHONE INTEGRATED

Description

INTELLIGENT ADDRESSABLE FIRE ALARM AND EVACUATION SYSTEM

Supply, Installtion, Testing and Commissioning of the following:


UL 864 ( 10 EDITION) listed and FM approved micro processor based 2 wire fault tolerant loop, 10 loop (each loop accessing minimum 125
detectors and 125 modules ) with Peer to Peer network communication system with additional 20 % Spare capacity in each loop fire
alarm/detection with Integrated voice evacuation control panel of same make.
The panel shall support 100 audio channels , 250 audio messages, upto 750 minutes of stored pre-recorded voice messages capacity, LARGE FULL
COLOUR LCD TOUCH SCREEN WITH CONTROL BUTTONS, Multiple command station feature for One way Voice Evacuation and Two way Fire
Fighter Telephone communication, Browser based remote connectivity, graphic software and compatible computer with sufficient panel enclosure
and cabinet size to accomodate Integrated voice evacuation unit for automated messaging with suitable Wattage amplifier and Fire Fighter
Telephone unit.
The panel must have minimum 20,000 event history out of which 10,000 events should be preserved events should not be overwritten .
The panel network must be hot swappable with no downtime from copper to fibre,
The panel shall have control and display switches for 24 speaker zones with one-way and two-way emergency audio communications facility.
The panel should be modular snap fit type and should operate on the broadcast polling . The system should have automatic mapping feature.
The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes and shall have zone indication
display LEDs on the main panel using the mountable LED strips on the panel. Further, the panel must be able to automatically switch ON /OFF
respective control module when ever any alarm is triggered.
The panel shall have rectifier, Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, external/inbuilt printer to log all
fire or fault events complete in all respects.
The panel shall have a built in power supply and battery charger along with maintenance free 24 AH, 2 x 12 volt SMF Lead acid batteries capable
of running for a minimum of 24 hours standby operation and 30 minutes in Alarm.
Panel shall have Bacnet/Modbus card for BMS integration .
The system should offer fail safe degraded mode making the life safety system working in any given set of conditions.
Latest cybersecurity standards to be adopted by the panel complying to AES,NIST &FIPS PUB197. The panel shall have Flexible IPV6 network
design which Can operate in Class B, A, X, N or full mesh using fiber, Ethernet or copper wiring with On-board Webserver. The Panel should have
Built-in E-mail and E-mail-to-SMS Messaging supporting Five-color LED Indicators. The FCAP should support Network data, audio data, and
telephone data share a single twisted pair or single fiber strand

UL listed and FM approved Repeater Panel with color Touch screen LCD Display with control buttons for quick intuitive access to key system status
and control functions,
The Repeater panel shall be capable of receiving the same event information and issuing the same system commands as the FACP to which it is
connected.
The Repeater panel shall have common indicators for Power, System Trouble, and Signal Silenced LEDs; System Reset, Silence, Panel Silence,
Drill push buttons and support local Lamp Test.

Intelligent Addressable self decsion making ,microprocessor based Multi-Sensor smoke and Heat detector, optical type having 20 pre alarm
senstivity settings and 5 alarm senstivity settings, Wide Sensitivity 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m) smoke obscuration with Bicolor
(green/red) status LED indicator on each detector and being capable of being addressed electronically.The microprocessor’s non-volatile memory
shall permanently store the detector’s serial number, device type and system address. Manual Addressing (Dip/ Rotary Switches) not
preferred)Detector should have its own memory.Swapping same type of detectors to diffrent base should not call for reprogramming.
UL 268 7th edition and FM approved

Intelligent Addressable microprocessor based heat detectors with operating temperature of 57 deg C & 8.3 deg C/min rate of rise of temperature,
Bicolor (green/red) status LED indicator on each detector and being capable of being addressed electronically. The microprocessor’s non-volatile
memory shall permanently store the detector’s serial number, device type and system address. Manual Addressing (Dip/ Rotary Switches) not
preferred .Detector should have its own memory.UL Listed.

Intelligent Self decision making Addressable microprocessor based Smoke detector, optical type having 20 pre alarm senstivity settings and 5
alarm senstivity settings, Wide Sensitivity 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m) smoke obscuration with Bicolor (green/red) status LED indicator
on each detector and being capable of being addressed electronically. The microprocessor’s non-volatile memory shall permanently store the
detector’s serial number, device type and system address. Manual Addressing (Dip/ Rotary Switches) not preferred.The detector should have its
own memory. UL 268 7th edition and FM approved.

Intelligent Addressable Self decisoon making microprocessor based Smoke detector with Sounder Base, optical type having 20 pre alarm
senstivity settings and 5 alarm senstivity settings, Wide Sensitivity 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m) smoke obscuration with Bicolor
(green/red) status LED indicator on each detector and being capable of being addressed electronically. The microprocessor’s non-volatile memory
shall permanently store the detector’s serial number, device type and system address. Manual Addressing (Dip/ Rotary Switches) not
preferred.The detector must have its own memory.Swapping same type of detectors to diffrent base should not call for reprogramming.UL 268
7th edition and FM approved.

586190105.xls 04/06/2022
Page 5

Intelligent Addressable microprocessor based Duct detector capable of being addressed electronically with duct piping. The microprocessor’s non-
volatile memory shall permanently store the detector’s serial number, device type and system address Manual Addressing (Dip/ Rotary Switches)
not preferred ..Swapping same type of detectors to diffrent base should not call for reprogramming. UL Listed & FM approved

Intelligent Addressable Double action manual pull station, capable of being addressed electronically. Manual Addressing (Dip/ Rotary Switches)
not acceptable, complete as required.and as per specifications. UL Listed & FM approved

Fire Alarm LED Hooter cum Strobe (sound output of minimum 85 dB, Light output: 15, 30, or 75 candela ) made Addressable with the help of
Intelligent Addressable Signal Module, with seperate power supply arrangement complete as required and suitable for wall/ceiling mounting and
as per specifications. UL Listed.

Addressable Signal control module complete as required for Hooter cum strobe Notification devices, capable of being addressed electronically.
Manual Addressing (Dip/ Rotary Switches) not preferred, complete as required.and as per specifications. UL Listed & FM approved

Addressable control module complete as required for switching ON of smoke extraction fans / Pressurisation Fans etc. and switching off AHU' s,
capable of being addressed electronically. Manual Addressing (Dip/ Rotary Switches) not preferred, complete as required.and as per specifications.
UL Listed & FM approved

Addressable Monitor module complete as required for monitoring flow switches/ interface with any third party equipment capable of being
addressed electronically. Manual Addressing (Dip/ Rotary Switches) not preferred, complete as required.and as per specifications. UL Listed & FM
approved

Addressable Fault Isolator module complete as required for determining the short in a circuit and separating the segment having the short capable
of being addressed electronically. Manual Addressing (Dip/ Rotary Switches) not preferred, complete as required.and as per specifications. UL
Listed & FM approved

Speaker ceiling / wall mounting arrangement (0-2 watts) with multiple taping 1/4,1/2,1 and 2 watt tapping, complete as per specification and
should be UL listed and the same make of Integrated Fire Alarm System.

15 W Wall Mounted Type Horn Type Speaker with Multi Tapping Feature complete as per specification and should be UL listed and the same make
of Integrated Fire Alarm System

Response indicator with LED display for all detectors located above false ceiling. Response indicator branding should be of the same make as
Panel & detectors and UL Listed & FM approved. Other brand Response Indicator is not acceptable

Intelligent Addressable 20 watts/40 Watts/ 95 Watts amplifier as required, shall be mounted on the rail chasis of Fire Alarm Panel enclosures or
inside remote closet cabinet with the requisite intelligent addressable power supply to drive these amplifiers, Manual Addressing (Dip/ Rotary
Switches) not acceptable, complete as required. The amplifier and Powers upply shall be same make of the panel. UL Listed & FM approved

Fire Fighting Telephone Jacks with Addressable control Module, UL Listed & FM approved

Fire Fighting Telephone Handset, UL Listed & FM approved

Supply, Installation, Testing and Commissioning of Graphical software (same make of the panel) along with comaptible PC system/Printer/UPS tec
,complete in all respect as required and as per specifications. The system should be capable of establishing IP connectivity in Graphics software to
take multiple system inputs from multiple panels. Highlighting an event in the “Event List Viewport” shall automatically cause the display of the
map viewport and other configured viewports to display information relative to the highlighted event. UL listed

2 x 1.5 sq mm PVC sheathed copper conductor 1100 volts grade flexible FRLS wires of approved make in concealed or surface mounted existing
25 mm dia MS conduit including fixing, supporting, saddling & flexible conduit etc complete in all respect.

4 x 1.5 sq mm PVC sheathed copper conductor 1100 volts grade flexible FRLS wires of approved make in concealed or surface mounted existing
25 mm dia MS conduit including fixing, supporting, saddling & flexible conduit etc complete in all respect.

2 x 1.5 sq mm twisted shielded PVC sheathed copper conductor 1100 volts grade flexible FRLS cable of approved make in concealed or surface
mounted existing 25 mm dia MS conduit including fixing, supporting, saddling & flexible conduit etc complete in all respect.

Supply Installation testing and commissioning of the following 16 guage 25 mm MS rigid conduits recessed in RCC walls or clamped on surface in
ceilings including clamps hardwares etc. complete as per specifications. Quoted price shall include GI flexible conduits to connect from ceiling to
false ceiling.

TOTAL

586190105.xls 04/06/2022
Page 6

APPENDIX - I

List of approved makes for Equipment and materials.

Details of Materials

Fire Detection & Alarm System

Detectors/Hooters/Manual Call

Fire Alarm Panel

Voice Evacuation, Speakers and Amplifiers

Monitor

Cables

Conduits

586190105.xls 04/06/2022
Page 7

Unit Make Model Remaks Qty U. Amount


Rate

No. Edwards EST-4 Batteies and Battery Enclosure


by others

Edwards FSB-PC4 + FSB-BRKT2

Set EDWARDS 4-2ANN + 4-


2ANNMT + 4-
NET-TP/SM

Nos Edwards SGA-


OSHD+SIGA-SB

Nos Edwards SIGA-


HRD+SIGA-SB

Nos Edwards SIGA-


OSD+SIGA-SB

Nos Edwards SIGA-


OSD+SIGA-AB4G

586190105.xls 04/06/2022
Page 8

Nos Edwards SIGA-SD + SD-


T24

Nos Edwards SIGA-278

Nos Edwards G1AVRF 24 VDC External

Edwards SIGA-CC1

Nos Edwards SIGA-CR

Nos Edwards SIGA-CT1

Nos Edwards SIGA-IM

Nos Edwards GCSWN/G4SWN

Edwards HPSA15R2570

Edwards SIGA-LED

Nos Edwards 3-ZAA20B/3-


ZA40B/3-ZA95B

Nos Edwards 6833-4

Edwards 6830-3

Nos Edwards FW-CGSUL Graphic Software only, other


required hardware &
accessories in SI Scope

RM

RM

RM

RM

Rs. 0

586190105.xls 04/06/2022