Operation
Maintenance
ODYSSEY
Light Commercial
Split System 5-20 Tons
TTH Model 50 Hz / 60 Hz
TTH 060 B D 0 0 B A
Electrical Characteristics
D = 380-415/3/50
3 = 230/3/60
TTH-IOM01-EN
Contents
Model Nomenclature 2
General Information 4
Unit Installation 5
General Data 7
Electrical Wiring 9
Dimensional Data 10
Operation and Start-up 13
Maintenance 14
Trouble Shooting 15
TTH-IOM01-EN 3
General Information
Foreword Note
These instructions do not attempt “Warnings” and “Cautions” appear
to cover all variations in systems, at appropriate places in this manual.
nor to provide for every possible Your personal safety and the proper
contingency to be met in connection operation of this machine require
with installation. Should further that you follow them carefully. The
information be desired or should manufacturer assumes no liability for
particular problems arise which are installations or servicing performed by
not sufficiently covered for the unqualified personnel.
purchaser’s purpose, the matter
should be referred to the Handling
manufacturer. The unit will be supplied with a
shipping base and protective
Reception packaging over the unit casing. The
On arrival, inspect the unit before packaging should be kept on the unit
signing the delivery note. Specify any during handling or storage on site.
damage on the delivery note, and
send a registered letter of protest to If it is necessary to remove the
the last carrier of the goods within 72 packaging for inspection prior to
hours of delivery. Notify the local Trane completion of on site handling, retain
Sales Office at the same time. The unit packaging parts and reapply them by
should be totally inspected within 15 tapping in position to prevent damage
days of delivery. If any concealed to the casing. The unit as supplied has
damage is discovered, stop unpacking a shipping base which is suitable for
the shipment. Take photos of the handling by a fork lift truck. If it is
damage material if possible. Notify the necessary to sling the unit, use
carrier immediately by phone and spreader bars under the shipping
registered mail. Notify the local Trane base.
Sales Office. Concealed damage must
be reported within 15 days of delivery. Ensure that ropes do not cause
Check the unit nameplate to confirm abrasion to the surface of the unit.
that the proper unit was shipped.
Available power supply must be Warning
compatible with electrical Open and lock unit disconnect to
characteristics specified on prevent injury or death from electric
component nameplates. shock or contact with moving parts
before attempting any installation or
General Information maintenance.
This manual covers the Installation,
Operation, and Maintenance of the Inspection
TTH060B, TTH075B, TTH100B, and Inspect material carefully for any
TTH120B single circuit air handlers. shipping damage. If damaged, it must
These new air handler models are be reported to, and claims made
completely redesigned to incorporate against the transportation company.
a single slab coil assembly, improved Replace damaged parts with autho-
application flexibility, servicing and rized parts only. Check the unit
maintenance accessibility, and an nameplate to confirm that the proper
improved accessory line. They are unit was shipped. Available power
horizontal type with special drain pan supply must be compatible with
(for TTH model). electrical characteristics specified on
component nameplates.
4 TTH-IOM01-EN
Unit Installation
Warning W3
On site Lifting Equipment must be
capable of lifting the weight of the unit m.
M 0m W1
IN
.8 85
N.
with an adequate safety factor. The 50
mm MI
.
use of under-capacity lifting devices
Figure 2
may result in personal injury ordeath Figure 1a
Position of corner weight
and cause damage to the unit.
TTH model
TTH-IOM01-EN 5
Unit Installation
6 TTH-IOM01-EN
General Data
TTH-IOM01-EN 7
General Data
8 TTH-IOM01-EN
Electrical Wiring
CONTROL BOX
PT TB
3M-1
L1
3M-2 I.D.
L2 MOTOR
3M-3
L3
O.L.
EXTERNAL CONTROL C1 95 96
POWER SUPPLY
220-230V./1PH./50Hz./60Hz.
C2
2M/3M
TO TERMINAL BLOCK C3
TTA MODELS TTA 075, 100, 120RD TTA 150, 200, 240RD
13 23
2M1/3M1/A1 2M1, 2M2 TTA 075, 100, 120RD00
TH 13
3M1, 3M2 TTA 150, 200, 240RD00
A1, A2 TTA 150, 200, 240RD0G
2M2/3M2/A2
TO PUSH BUTTON “2PB”
LEGEND
DEVICE
DESCRIPTION
DESIGNATION
1M CONTACTOR BLOWER MOTOR. NOTES
TB TERMINAL BLOCK
1. ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRIC
2M1, 2M2, 3M1 AUXILIARY N.O. CONTACT CODE (N.E.C.) CANADIAN ELECTRIC CODE AND/OR LOCAL STATE AND
3M2, A1, A2 AUXILIARY N.O. CONTACT CITY CODES, PROVIDE DISCONNECTS FOR ALL POWER SUPPLIES.
TH THERMOSTAT 2. DRAWING PRACTICES AND SYMBOLS ARE IN ACCORDANCE WITH AIR
2PB SWITCH PUSH BUTTON CONDITIONING & REFRIGERATION INSTITUTE (ARI) GRAPHIC
FACTORY WIRING & DEVICE BY MFR. ELECTRICAL STANDARDS.
FIELD WIRING 3. COMPONENT TERMINAL MARKINGS ARE INDICATED BY ENCIRCLED
ID. MOTOR INDUCTION MOTOR NUMBERS AND/OR LETTERS.
PT POWER TERMINAL 4. NUMBERS ON VERTICAL & HORIZONTAL LINE ARE CIRCUIT IDENTIFICATION.
FUSE 5. THIS UNIT TO BE USED WITH EVAPORATORS OPERATING WITH IN
A TEMPERATURE RANGE OF 32º F TO 53.5º F.
TB
L1
I.D.
L2 MOTOR
L3
N
LEGEND
DEVICE
DESCRIPTION
DESIGNATION
TB TERMINAL BLOCK
FACTORY WIRING & DEVICE BY MFR.
FIELD WIRING
ID. MOTOR INDUCTION MOTOR 380V. 3PH. 50Hz.
Caution: Disconnect the power supply before opening the control box or servicing.
TTH-IOM01-EN 9
Dimensional Data
10 TTH-IOM01-EN
Dimensional Data
TTH-IOM01-EN 11
Dimensional Data
TTH 060-120
With Plenum (Option)
12 TTH-IOM01-EN
Operation and Start-up
TTH-IOM01-EN 13
Maintenance
14 TTH-IOM01-EN
TTH-IOM01-EN.indd
T 14
Trouble Shooting
Refrig. Undercharge
High Voltage Wiring
Refrig. Overcharge
Restriction LD Coil
Low Voltage Fuse
System
Curcuit Breaker
Thermal Cutout
Capacitor (Fan)
Power Supply
Faults
Thermostat
Relay (Fan)
Refrigerant Circuit
Electrical
TTH-IOM01-EN 15
Trouble Shooting