Fan Selection
Fan Type BSB
Unit BSB1000/TM (I)
Fan Quantity 1
Operating Conditions Ducted
Required Volume 8,275 l/s
Required Static Pressure 500 Pa
Air Volume 8,275 l/s
Static Pressure 500 Pa
Velocity Pressure 57 Pa
Total Pressure 557 Pa
Outlet Velocity 9.86 m/s
Fan Total Efficiency 73.6 %
Fan Static Efficiency 66.1 %
Fan Speed 695 rpm
Air Temperature 30 °C
Altitude 1m
Fan Absorbed Power 6.26 kW
Motor Selection
Recommended Motor D160 6p (7.50 kW)
Motor Speed 1150 rpm
Service Factor 5%
Operating Limits
Max. Absorbed Power 16.00 kW
Max. Fan Speed 950 rpm
Temperature (Min-Max) -20° to 100°C
0DL A B C D E F F1 G H
55 1810 1540 1066 1266 663 500 200 656 1450
J K L M N P R S t t1
713 763 974 141 719 90 9 1322 16 10
UxS V v1 v2 w X Y z
17x22 1000 1043 1086 90 691 1294 53.5