Professional Documents
Culture Documents
Type Test Report Final 2319-17 V1
Type Test Report Final 2319-17 V1
The object, constructed in accordance with the description, drawings and photographs incorporated in
this Certificate, has been subjected to the series of proving tests in accordance with the complete type
test requirements of
The results are shown in the record of proving tests and the oscillograms attached hereto. The values
obtained and the general performance are considered to comply with the above standard and to
justify the ratings assigned by the manufacturer as listed on page 5 and the dynamic ability to
withstand short-circuits.
This Certificate applies only to the object tested. The responsibility for
conformity of any object having the same type references as that tested
rests with the Manufacturer.
*) as declared by the manufacturer
J.P. Fonteijne
Executive Vice President
KEMA Laboratories
Copyright: Only integral reproduction of this Certificate is permitted without written permission from DNV GL. Electronic copies as PDF or scan of this
Certificate may be available and have the status “for information only”. The sealed and bound version of the Certificate is the only valid version.
-2- 2319-17
INFORMATION SHEET
1 KEMA Type Test Certificate
A KEMA Type Test Certificate contains a record of a series of (type) tests carried out in accordance
with a recognized standard. The object tested has fulfilled the requirements of this standard and the
relevant ratings assigned by the manufacturer are endorsed by DNV GL. In addition, the object’s
technical drawings have been verified and the condition of the object after the tests is assessed and
recorded. The Certificate contains the essential drawings and a description of the object tested. A
KEMA Type Test Certificate signifies that the object meets all the requirements of the named
subclauses of the standard. It can be identified by gold-embossed lettering on the cover and a gold
seal on its front sheet.
The Certificate is applicable to the object tested only. DNV GL is responsible for the validity and the
contents of the Certificate. The responsibility for conformity of any object having the same type
references as the one tested rests with the manufacturer.
Detailed rules on types of certification are given in DNV GL’s Certification procedure applicable to
KEMA Laboratories.
TABLE OF CONTENTS
3 Legend ...................................................................................................................... 8
6 Summary of tests...................................................................................................... 11
22 Drawings.................................................................................................................. 67
Version: 1
-5- 2319-17
Rated voltage
HV side 33 kV X
LV side 400 V X
Tapping range HV ± 2 x 2,5 %
Rated power HV
ONAN 2500 kVA X
Rated power LV
ONAN 2500 kVA X
Short-circuit impedance at principal tapping
(measured by KEMA Laboratories)
HV-LV winding 7,66 % X
Short-circuit impedance at principal tapping
(guaranteed value)
HV-LV winding 7,5 %
Connection and phase displacement symbol Dyn11 X
Rated frequency 60 Hz X
Category I X
Maximum system short-circuit power 1000 MVA X
Guaranteed maximum temperature rise
top liquid 45 K X
HV windings 50 K X
LV windings 50 K X
Insulation levels HV
LI 170 kV X
AC 70 kV X
Insulation levels LV
AC 3 kV X
Insulation levels Neutral
AC 3 kV X
On request of the manufacturer the following drawings and/or documents have been included in this
report.
KEMA Laboratories has not verified these drawings and/or documents.
Drawing no./document no. Revision
P207/S058_A 0
0777/002A 0
The following drawings and/or documents are only listed for reference.
KEMA Laboratories has not verified these drawings and/or documents.
Drawing no./document no. Revision
3175 0
0211/850 2
T2-E25341_A 0
T2-E25341_B 0
T2-E25341_C 0
T2-E25341_D 0
T2-E25341_E 1
T2-E25341_F 0
T2-E25341_FA 0
ASP 21725 0
Version: 1
-7- 2319-17
2 GENERAL INFORMATION
Name Company
Alawneh, R. The Saudi Transformers Co. Ltd.,
Alshowaikhaf, A. Dammam, Saudi Arabia
Name Company
Keet, J.C. DNV GL Netherlands B.V.,
Arnhem, the Netherlands
The guaranteed uncertainty for the measured voltages and currents taking into account the total
measuring system, is less than 5%, unless mentioned otherwise.
Version: 1
-8- 2319-17
3 LEGEND
Phase indications
If more than one phase is recorded on oscillogram, the phases are indicated by the digits 1, 2 and 3.
These phases 1, 2 and 3 correspond to the phase values in the columns of the accompanying table,
respectively from left to right.
Tap position 1
Test number Reactance
Measured between the Calculated per leg Change per leg
phases
%
1U-1V 1V-1W 1U-1W 1U 1V 1W 1U 1V 1W
Before tests 74,27 72,61 74,04 112,35 107,43 111,66 - - -
AT 171201-6004 75,40 73,14 74,79 114,57 107,84 112,69 2,0 0,4 0,9
AT 171201-6005 75,78 73,59 75,10 115,14 108,62 113,03 2,5 1,1 1,2
AT 171201-6006 76,15 73,66 75,13 116,05 108,61 112,89 3,3 1,1 1,1
After tests 76,49 74,49 76,11 115,94 110,01 114,78 3,2 2,4 2,8
Tap position 3
Test number Reactance
Measured between the Calculated per leg Change per leg
phases
%
1U-1V 1V-1W 1U-1W 1U 1V 1W 1U 1V 1W
Before tests 68,27 66,84 68,05 103,25 98,99 102,55 - - -
AT 171201-6008 70,08 68,20 69,25 106,53 100,88 103,97 3,2 1,9 1,4
AT 171201-6009 70,12 68,35 69,29 106,52 101,21 103,97 3,2 2,2 1,4
AT 171201-6010 70,12 68,46 69,37 106,42 101,45 104,11 3,1 2,5 1,5
After tests 70,31 68,57 69,86 106,58 101,42 105,18 3,2 2,4 2,6
Tap position 5
Test number Reactance
Measured between the Calculated per leg Change per leg
phases
%
1U-1V 1V-1W 1U-1W 1U 1V 1W 1U 1V 1W
Before tests 61,56 60,43 61,56 92,91 89,56 92,91 - - -
AT 171201-6012 63,52 61,98 63,00 96,35 91,73 94,72 3,7 2,4 1,9
AT 171201-6013 63,56 62,01 63,15 96,34 91,74 95,06 3,7 2,4 2,3
AT 171201-6014 63,60 62,05 63,22 96,38 91,78 95,21 3,7 2,5 2,5
After tests 63,60 62,05 63,22 96,38 91,78 95,21 3,7 2,5 2,5
Maximum deviation
The maximum deviation in reactance per leg was 3,7%.
The maximum deviation allowed in accordance with the IEC 60076-5 is 7,5%.
Version: 1
-10- 2319-17
6 SUMMARY OF TESTS
Short-circuit tests
171201 171201 171201 171201 171201 171201
Test no.
6004 6005 6006 6008 6009 6010
Tap position 1 1 1 3 3 3
Observations
171201-6004 No visible disturbance.
171201-6005 No visible disturbance.
171201-6006 No visible disturbance.
171201-6008 No visible disturbance.
171201-6009 No visible disturbance.
171201-6010 No visible disturbance.
Version: 1
-13- 2319-17
Observations
171201-6012 No visible disturbance.
171201-6013 No visible disturbance.
171201-6014 No visible disturbance.
Version: 1
-15- 2319-17
Transformer new.
Environmental conditions
Ambient temperature 20 °C Ambient air pressure 1002 hPa
Humidity 9 g/m3
Requirement
None.
Result
The results are for information only.
Version: 1
-16- 2319-17
Requirement
IEC 60076-1, table 1: for the principal tapping: ± 0,5% of declared ratio or ± 1/10 of actual
percentage impedance on the principal tapping, whichever is smaller.
Result
The measured average voltage ratio on the principal tapping is within the tolerances.
Vector group has been verified and determined Dyn11.
Version: 1
-17- 2319-17
Requirement
None.
Result
The results are used for further calculations and are for information only.
Version: 1
-18- 2319-17
U 'U RMS
P0 P 1
Note: The no-load losses are calculated with the formula U ' where U' = 1,11 x Umean
Requirement
None.
Result
The results are for information only.
Version: 1
-19- 2319-17
Requirement
No collapse of the test voltage shall occur.
Result
The object passed the tests.
Requirement
No collapse of the test voltage shall occur.
Result
The object passed the test.
Version: 1
-20- 2319-17
Environmental conditions
Ambient temperature 20,3 °C
Temperature of test object 18,3 °C
(average oil)
Requirements
The client specified no requirements.
Result
Results to be analysed by the customer, as there are no passing criteria.
For information only.
Version: 1
-21- 2319-17
9 SHORT-CIRCUIT TESTS
TO
G MB MS L PT R1C1
U
U
U
Load
Short-circuit point earthed
Remarks: -
Version: 1
-24- 2319-17
Remarks
-
Version: 1
-26- 2319-17
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Environmental conditions
Ambient temperature 20 °C Ambient air pressure 1028 hPa
Humidity 8 g/m3
Requirement
None.
Result
The results are used for further calculations and are for information only.
Version: 1
-38- 2319-17
Requirement
IEC 60076-1, table 1: for the principal tapping: ± 0,5% of declared ratio or ± 1/10 of actual
percentage impedance on the principal tapping, whichever is smaller.
Result
The measured average voltage ratio on the principal tapping is within the tolerances.
Version: 1
-39- 2319-17
Requirement
None.
Result
The results are for information only.
Version: 1
-40- 2319-17
U 'U RMS
P0 P 1
Note: The no-load losses are calculated with the formula U ' where U' = 1,11 x Umean
Requirement
None.
Result
The results are for information only.
Version: 1
-41- 2319-17
Requirement
No collapse of the test voltage shall occur.
Result
The object passed the tests.
Requirement
No collapse of the test voltage shall occur.
Result
The object passed the test.
Version: 1
-42- 2319-17
Environmental conditions
Ambient temperature 20 °C Ambient air pressure 1029 hPa
Temperature of test object 20 °C Humidity 8 g/m3
Requirement
None.
Result
The results are for information only.
Version: 1
-43- 2319-17
Environmental conditions
Ambient temperature 20 °C Ambient air pressure 1019 hPa
Temperature of test object 20 °C Humidity 8 g/m3
Test voltage
Ucrest (full wave, 100%) 170 kV
Test connections
HV terminal under test Test voltage LV terminal under test Detection
HV terminals not under test Earthed LV terminals not under test Shunted
Tank Earthed LV neutral Earthed
Requirement
no breakdown
no significant difference in applied voltage and detection before and after test.
Result
The object passed the test.
Version: 1
-44- 2319-17
Version: 1
-45- 2319-17
Version: 1
-46- 2319-17
Version: 1
-47- 2319-17
Version: 1
-48- 2319-17
Version: 1
-49- 2319-17
Version: 1
-50- 2319-17
Environmental conditions
Ambient temperature 20 °C Humidity 8,7 g/m3
Temperature of test object 1032 °C
Requirement
The measured value shall not be higher than 0,5% at ≥ 2 kV.
Result
The object passed the tests.
Version: 1
-51- 2319-17
Environmental conditions
Ambient temperature 20 °C Ambient air pressure 1032 hPa
Humidity 8,7 g/m3
The zero sequence impedance Z0 of the transformer was determined by measurement of voltage and
current. For this purpose a single-phase current was induced through the low voltage windings of the
transformer, with the three-phase terminals interconnected.
Requirement
None.
Result
The results are for information only.
Version: 1
-52- 2319-17
Environmental conditions
Ambient temperature 20 °C
Temperature of test object 20 °C
(average oil)
Requirements
The client specified no requirements.
Result
Results to be analysed by the customer, as there are no passing criteria. For information only.
Version: 1
-53- 2319-17
Environmental conditions
Ambient temperature 20 °C Ambient air pressure 1011 hPa
Temperature of test object 24 °C Humidity 8 g/m3
Test conditions
Applied voltage (LV winding) 400
Frequency 60 Hz
Tap position 3
Test room surface Sv 1250 m2
Acoustic absorption coefficient α 0,15
Measurement distance X 0,30 m
Length of prescribed contour lm 13,00 m
Transformer height h 1,90 m
Area of effective surface S 30,88 m2
10 log S/S0 14,90 dB [A]
Microphone height 0,95 m
No. of measuring locations 13
Correction on measuring equipment 0,0 dB
Environmental correction K 2,20 dB
Version: 1
-55- 2319-17
Requirement
None.
Result
The results are for information only.
Version: 1
-56- 2319-17
Environmental conditions
Ambient temperature 20,3 °C Ambient air pressure 1019 hPa
Temperature of test object 20,3 °C Humidity 8 g/m3
Requirement
The pressure should be maintained for the agreed duration as specified by the customer.
No gas leakage shall occur (no drop in pressure shall be observed).
Result
The object passed the tests.
Version: 1
-57- 2319-17
18 TEMPERATURE-RISE TEST
Result
The top-liquid temperature-rise and the average winding temperature-rises are in compliance with the
requirements.
Version: 1
-60- 2319-17
Environmental conditions
Ambient temperature 20,3 °C Ambient air pressure 1019 hPa
Temperature of test object 20,3 °C Humidity 8 g/m3
Requirement
None.
Result
The results are for information only.
Version: 1
-61- 2319-17
Sample Description Before Dielectric After Dielectric Before Temprature After Temprature
Tests Tests Rise Test Rise Test
Hydrogen μl/l 4,9 4 4,9 4,3
Methane μl/l 1,26 2 <0,5 1,37
Ethane μl/l 1,65 5,1 1,25 2,03
Ethylene μl/l 0,49 0,3 0,46 0,48
Acetylene μl/l 0,31 0,28 0,3 0,32
Propane μl/l 0,77 2,2 0,56 1,29
Propylene μl/l 0,5 0,53 0,51 0,58
Carbon monoxide μl/l 66 66 64 68
Carbon dioxide μl/l 290 300 280 330
Oxygen ml/l 15,9 14 14,8 17,1
Nitrogen ml/l 42 41 39 49
Iso-butane μl/l <0,5 <0,5 <0,5 <0,5
N-butane μl/l 1,2 1,5 <1 1,5
Hydrogen μl/l 4,9 4 4,9 4,3
Methane μl/l 1,26 2 <0,5 1,37
Requirement
None.
Result
The results are for information only.
Version: 1
-62- 2319-17
On 8 December 2017 the transformer was untanked and the active part was inspected at KEMA
Laboratories.
The out-of-tank inspection with respect to displacements, deformations of core and windings,
connections and supporting structures or traces of discharges did not reveal any apparent defects.
Version: 1
-63- 2319-17
22 DRAWINGS
Version: 1
-68- 2319-17
Version: 1