Test specification The tests have been carried out in accordance with IEC 60255-1:2009.
Summary and The object has complied with the relevant requirements of the standard.
conclusion
This report applies only to the object tested. The responsibility for
conformity of any object having the same type references as that tested
rests with the Manufacturer.
*) as declared by the manufacturer
J.P. Fonteijne
Executive Vice President
KEMA Laboratories
Copyright: Only integral reproduction of this report is permitted without written permission from DNV GL. Electronic copies as PDF or scan of this report
may be available and have the status “for information only”. The sealed and bound version of the report is the only valid version.
-2- 1416-18
INFORMATION SHEET
1 KEMA Type Test Certificate
A KEMA Type Test Certificate contains a record of a series of (type) tests carried out in accordance
with a recognized standard. The object tested has fulfilled the requirements of this standard and the
relevant ratings assigned by the manufacturer are endorsed by DNV GL. In addition, the object’s
technical drawings have been verified and the condition of the object after the tests is assessed and
recorded. The Certificate contains the essential drawings and a description of the object tested. A
KEMA Type Test Certificate signifies that the object meets all the requirements of the named
subclauses of the standard. It can be identified by gold-embossed lettering on the cover and a gold
seal on its front sheet.
The Certificate is applicable to the object tested only. DNV GL is responsible for the validity and the
contents of the Certificate. The responsibility for conformity of any object having the same type
references as the one tested rests with the manufacturer.
Detailed rules on types of certification are given in DNV GL’s Certification procedure applicable to
KEMA Laboratories.
TABLE OF CONTENTS
1 Summary ................................................................................................................... 5
4 Test arrangement...................................................................................................... 11
9.1.1 Pre-inspection 35
9.1.2 Visual and functional inspection 35
9.2 Mechanical endurance 36
9.3 Continuous contact current 37
9.4 Short duration contact current 38
9.5 Limiting making capacity 39
9.6 Limiting breaking capacity 40
1 SUMMARY
By order of the client type tests according to IEC 60255-1 have been performed on the test object.
The test object REQ670 belongs to the Relion 670 and 650 series, version 2.2. The tests performed on
REQ670 are part of a type test programme to certify the Relion 670 and 650 series, version 2.2.
The type test programme has also been performed on other types of Relion 670 and 650 series,
version 2.2. The results of these tests are described in the following reports:
The test results obtained during the tests were compared with the relevant standards and with the
manufacturers specifications, given in the following documents:
Classification
IP-class front side (with sealing strip) IP 54
IP-class front side (without sealing strip) IP 40
IP-class sides IP 40
IP-class rear side (compression terminal) IP 20
IP-class ring lug terminal IP 10
Mechanical class 1
EMC emission class A
EMC immunity zone A
Overvoltage category II & III
Pollution degree 2
Version: 1
-7- 1416-18
The client has submitted files containing drawings and documents of the IEDs and their modules.
These files are kept in the KEMA Laboratories project file.
KEMA Laboratories has made use of these drawings / documents during the execution of the tests.
KEMA Laboratories has not verified in detail that these drawings and documents represent the object
tested.
Version: 1
-9- 1416-18
3 GENERAL INFORMATION
The tests were carried out without a representative of the client present.
Name Company
Martijn Dallinga DNV GL Netherlands B.V.,
Herman Koerts Arnhem, the Netherlands
Mihai Bivolaru
3.4 Subcontracting
The following tests were subcontracted to DEKRA Certification B.V., Arnhem, the Netherlands:
• measurement of radiated emission in accordance with IEC 60255-26 and CISPR22.
• measurement of conducted emission in accordance with IEC 60255-26 and CISPR22.
• contact performance in accordance with IEC 61810-1.
Purpose of the tests was to verify whether the material complies with the specified requirements.
A table with measurement uncertainties is enclosed in this report. Unless otherwise stated, the
measurement uncertainties of the results presented in this report are as indicated in that table.
4 TEST ARRANGEMENT
A general test set-up is made by connecting the protective relay to a relay test set. The protective
relay is powered with rated auxiliary voltage. Currents and/or voltages are applied to the analogue
input module(s). If required status signals are applied to the binary input module(s). The operation
and resetting is monitored with the binary output modules operated with 24 VDC. The protective relay
is parameterized and monitored by means of the human machine interface and interface on the
display and LED's. Settings of the IED under test and information from the IED is handled by PCM600
software from ABB. Communication between IED and parameterizing and monitoring device is via
Ethernet communication.
Protective relay
Parameterizing and
Analog Binary monitoring device
input I/O
Current/voltage
amplifier
Analog Binary
output I/O
Monitoring device
Relay test set
Version: 1
-12- 1416-18
5 RISK ASSESSMENT
Clause 7.3 in IEC 60255-1 describes that testing a product which is part of a product family shall be
considered sufficient to cover the entire product family provided a documented risk assessment is
carried out to determine which type tests are valid and which tests need to be repeated on the rest of
the product family. The risk assessment is present in the Type test certificate 1418-18.
Version: 1
-13- 1416-18
6 ENCLOSURE PROTECTION
Environmental conditions
Ambient temperature 21 °C
Requirement
• The requirements for accessible parts test according to IEC 60255-27 is IP2X, the requirement
for wiring terminals is IP1X (see IEC 60255-27, subclause 5.1.5.2.6).
Result
The object passed the test.
Version: 1
-14- 1416-18
Test on rear side, IP20, compression terminals. The test probe does not touch the metal parts of the
connector.
Version: 1
-15- 1416-18
Test on rear side, IP20. The test finger does not penetrate the housing.
Version: 1
-16- 1416-18
Test at side, IP40. The test finger does not penetrate the housing.
Version: 1
-17- 1416-18
7 PRODUCT SAFETY
7.1 Inspection
7.1.1 Pre-inspection
The pre-inspection is performed to verify that the test object is in operating state as described in
IEC 60255-1, Annex A 2.5. The pre-inspection is carried out prior to the test procedure.
The communication with the maintenance computer is verified. Signals are simulated to verify the
functioning and operation with the specified performance specification for the following inputs and
outputs:
• analogue inputs.
• digital inputs.
• contact outputs.
• data communication ports.
After each test a visual and functional inspection is carried out as described in this chapter.
The visual inspection is carried out to verify that there is no visual mechanical damage.
There shall be no:
• burning of any components.
• paint blisters on any components.
• discolouration on components.
• deformation of modules or components.
• interruptions or damage on interconnecting cables, wires and connectors.
Functional inspection is carried out to verify the correct operation of the test object.
The measurements of analogue input data shall not exceed twice the class index for the measurement.
There shall be no:
• alarm indications on display and LED’s.
• error messages reported in the maintenance computer.
• unintentional change of contact outputs.
• unintentional change of digital input status.
Unless otherwise stated the visual and functional inspection was carried out successfully after each
test.
Version: 1
-18- 1416-18
Environmental conditions
Ambient temperature 20 °C
Humidity 49 %
Note
The test has been performed after completion of the climatic tests.
Version: 1
-19- 1416-18
Requirement
• no disruptive discharges or flashovers shall occur.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-20- 1416-18
Environmental conditions
Ambient temperature 20 °C
Note
The test has been performed after completion of the climatic tests.
Requirement
• no disruptive discharges or flashovers shall occur.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-23- 1416-18
Environmental conditions
Ambient temperature 20 °C
Requirement
• the resistance between the test point and the protective conductor terminal shall not
exceed 0,1 Ω.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-25- 1416-18
Test points
Version: 1
-26- 1416-18
Environmental conditions
Ambient temperature 21 and 20 °C
Observations
1. No damage of the test object.
2. Correct operation of the test object after the test.
Observations
1. Operating within the stated accuracy.
2. Capable of operating.
Results are re-used from report 1029-16: tests on 670-series v2.0 in 2015.
Requirement
• The equipment CT input circuits shall withstand overcurrents declared by the manufacturer,
both continuously and for 1 s duration, without creating a fire or electric shock risk.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-28- 1416-18
Environmental conditions
Ambient temperature 20 °C
Observations
1. No damage of the test object.
2. Correct operation of the test object after the test.
3. Capable of operation (outside of accuracy range)
Results are re-used from report 1029-16: tests on 670-series v2.0 in 2015.
Requirement
• The equipment VT input circuits shall withstand overvoltages declared by the manufacturer,
without damage, both continuously and for 10 s duration.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-29- 1416-18
Requirement
• the markings on the test object shall comply with the requirements of IEC 60255-27,
subclause 9.1.
• the documentation of the test object shall comply with the requirements of IEC 60255-27,
subclause 9.2.
Result
The object passed the test.
Version: 1
-30- 1416-18
8 ENERGIZING QUANTITIES
Environmental conditions
Ambient temperature 22 °C
Burden Observations
Required Measured
mVA mVA
CT input 1 A < 20 12 -
(X401 1+2)
CT input 1 A < 20 14 -
(X401 5+6)
CT input 1 A < 20 14 -
(X401 11+12)
Results are re-used from report 1029-16: tests on 670-series v2.0 in 2015.
Result
The object passed the test.
Version: 1
-31- 1416-18
Environmental conditions
Ambient temperature 22 °C
Burden Observations
Specified Measured
mVA
VT input 110 V < 20 mVA at 110 V 17,0 -
(X401, 13+14)
VT input 220 V < 20 mVA at 110 V 63,4 -
(X401, 13+14)
VT input 110 V < 20 mVA at 110 V 16,3 -
(X401, 17+18)
VT input 220 V < 20 mVA at 110 V 59,8 -
(X401, 17+18)
VT input 110 V < 20 mVA at 110 V 16,5 -
(X401, 23+24)
VT input 220 V < 20 mVA at 110 V 61,6 -
(X401, 23+24)
Results are re-used from report 1029-16: tests on 670-series v2.0 in 2015.
Result
The object passed the test.
Version: 1
-32- 1416-18
Test performed on REL670, report number 1410-18 and RES670, report number 1408-18.
Version: 1
-33- 1416-18
Environmental conditions
Ambient temperature 20 °C
Results are re-used from report 1029-16: tests on 670-series v2.0 in 2015.
Result
The object passed the test.
Version: 1
-34- 1416-18
Test performed on REL670, report number 1410-18 and RES670, report number 1408-18.
Version: 1
-35- 1416-18
9 CONTACT PERFORMANCE
9.1 Inspection
9.1.1 Pre-inspection
The pre-inspection is performed to verify that the test object is in operational state as described in
IEC 60255-1, Annex A 2.5. The pre-inspection is carried out prior to the test procedure.
The communication with the maintenance computer is verified. Signals are simulated to verify the
functioning and operation with the specified performance specification for the following inputs and
outputs:
• analogue inputs
• digital inputs
• contact outputs.
After each test a visual and functional inspection is carried out as described in this chapter.
The visual inspection is carried out to verify that there is no visual mechanical damage.
There shall be no:
• burning of any components.
• paint blisters on any components.
• discolouration on components.
• deformation of modules or components.
• interruptions or damage on interconnecting cables, wires and connectors.
Functional inspection is carried out to verify the correct operation of the test object.
The measurements of analogue input data shall not exceed twice the class index for the measurement.
There shall be no:
• alarm indications on display and LED’s.
• error messages reported in the maintenance computer.
• unintentional change of contact outputs.
• unintentional change of digital input status.
Unless otherwise stated the visual and functional inspection was carried out successfully after each
test.
Version: 1
-36- 1416-18
Environmental conditions
Ambient temperature 22 °C
Results are re-used from report 1029-16: tests on 670-series v2.0 in 2015.
Requirement
The visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-37- 1416-18
Environmental conditions
Ambient temperature 21 °C
Results are re-used from report 1029-16: tests on 670-series v2.0 in 2015.
Requirement
The visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-38- 1416-18
Environmental conditions
Ambient temperature 21 °C
Results are re-used from report 1029-16: tests on 670-series v2.0 in 2015.
Requirement
The visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-39- 1416-18
Environmental conditions
Ambient temperature 21 °C
Results are re-used from report 1029-16: tests on 670-series v2.0 in 2015.
Requirement
The visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-40- 1416-18
Environmental conditions
Ambient temperature 21 °C
Results are re-used from report 1029-16: tests on 670-series v2.0 in 2015.
Requirement
The visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-41- 1416-18
10 CLIMATIC ENVIRONMENT
10.1 Inspection
10.1.1 Pre-inspection
The pre-inspection is performed to verify that the test object is in operational state as described in
IEC 60255-1, Annex A 2.5. The pre-inspection is carried out prior to the test procedure.
The communication with the maintenance computer is verified. Signals are simulated to verify the
functioning and operation with the specified performance specification for the following inputs and
outputs:
• analogue inputs
• digital inputs
• contact outputs
• data communication ports
After each test a visual and functional inspection is carried out as described in this chapter.
The visual inspection is carried out to verify that there is no visual mechanical damage.
There shall be no:
• burning of any components.
• paint blisters on any components.
• discolouration on components.
• deformation of modules or components.
• interruptions or damage on interconnecting cables, wires and connectors.
Functional inspection is carried out to verify the correct operation of the test object.
The measurements of analogue input data shall not exceed twice the class index for the measurement.
There shall be no:
• alarm indications on display and LED’s.
• error messages reported in the maintenance computer.
• unintentional change of contact outputs.
• unintentional change of digital input status.
Unless otherwise stated the visual and functional inspection was carried out successfully after each
test.
Version: 1
-42- 1416-18
Observations
1. Correct start up, normal operation
2. Correct operation within the specified accuracy
3. The contrast of the LDC display at 70 °C has been impaired in a way that it is hard to read
from the display.
Display at 70 °C
Version: 1
-44- 1416-18
Requirement
• a dielectric voltage test shall be performed.
• a measurement of insulation resistance shall be performed.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-45- 1416-18
Observations
1. Correct start up, normal operation
2. Correct operation within the specified accuracy
Requirement
• a dielectric voltage test shall be performed.
• a measurement of insulation resistance shall be performed.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-46- 1416-18
Observations
1. Correct operation after the test, accuracy measurements are within the specifications.
Requirement
• a dielectric voltage test shall be performed.
• a measurement of insulation resistance shall be performed.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-47- 1416-18
Observations
1. Correct operation after the test, accuracy measurements are within the specifications.
Requirement
• a dielectric voltage test shall be performed.
• a measurement of insulation resistance shall be performed.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-48- 1416-18
Observations
1. Correct operation within the specified accuracy
2. Correct operation within the specified accuracy
3. The contrast of the LDC display at 70°C has been impaired in a way that it is hard to read
anything from the display.
Requirement
• a dielectric voltage test shall be performed.
• a measurement of insulation resistance shall be performed.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-49- 1416-18
Requirement
• a dielectric voltage test shall be performed.
• a measurement of insulation resistance shall be performed.
• a protective bonding resistance test shall be performed.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-50- 1416-18
Requirement
• a dielectric voltage test shall be performed.
• a measurement of insulation resistance shall be performed.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-51- 1416-18
Environmental conditions
Ambient temperature 21 °C
Requirement
No discharge, no flashover.
The visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-52- 1416-18
Requirement
• the insulation resistance shall not be less than 10 MΩ.
• no visual or functional inspection required.
Result
The object passed the test.
Version: 1
-53- 1416-18
Environmental conditions
Ambient temperature 20 °C
Requirement
• the resistance between the test point and the protective conductor terminal shall not
exceed 0,1 Ω.
• the visual and functional inspection shall not reveal any defects or malfunctions.
Result
The object passed the test.
Version: 1
-54- 1416-18
Test points
Version: 1
-55- 1416-18
11 ELECTROMAGNETIC COMPATIBILITY
11.1 Inspection
11.1.1 Pre-inspection
The pre-inspection is performed to verify that the test object is in operational state as described in
IEC 60255-1, Annex A 2.5. The pre-inspection is carried out prior to the test procedure.
The communication with the maintenance computer is verified. Signals are simulated to verify the
functioning and operation with the specified performance specification for the following inputs and
outputs:
• analogue inputs
• digital inputs
• contact outputs
• data communication ports.
After each test a visual and functional inspection is carried out as described in this chapter.
The visual inspection is carried out to verify that there is no visual mechanical damage.
There shall be no:
• burning of any components.
• paint blisters on any components.
• discolouration on components.
• deformation of modules or components.
• interruptions or damage on interconnecting cables, wires and connectors.
Functional inspection is carried out to verify the correct operation of the test object.
The measurements of analogue input data shall not exceed twice the class index for the measurement.
There shall be no:
• alarm indications on display and LED’s.
• error messages reported in the maintenance computer.
• unintentional change of contact outputs.
• unintentional change of digital input status.
Unless otherwise stated the visual and functional inspection was carried out successfully after each
test.
Version: 1
-57- 1416-18
Environmental conditions
Ambient temperature 21 °C
Power supply voltage of 24 Vdc with horizontal and vertical antenna polarisation, in the
frequency range 30 MHz – 1 GHz (red = vertical, blue = horizontal)
Results
Frequency Level (QP) Limit (QP) Margin to limit Antenna
measured at 3 m distance polarisation
at 3 m distance
MHz dBV/m dBV/m dBV/m H/V
35,91 22,62 50 27,38 Vertical
104,10 27,23 50 22,77 Horizontal
120,27 25,85 50 24,15 Horizontal
133,23 31,70 50 18,30 Vertical
159,72 18,92 50 31,08 Horizontal
161,67 18,04 50 31,96 Horizontal
Version: 1
-58- 1416-18
Power supply voltage of 60 Vdc with vertical antenna polarisation, in the frequency range
30 MHz – 1 GHz (vertical = highest levels)
Full Spectrum
80
70
60
Level in dBµV/m
50
40
30
20
10
0
30M 50 60 80 100M 200 300 400 500 800 1G
Frequency in Hz
Results
Frequency Level (QP) Limit (QP) Margin to limit Antenna
measured at 3 m distance polarisation
at 3 m distance
MHz dBV/m dBV/m dBV/m H/V
121,59 32,34 50 17,66 Vertical
124,05 33,66 50 16,34 Vertical
1000,00 37,54 57 19,46 Vertical
Version: 1
-59- 1416-18
Power supply voltage of 60 Vdc with horizontal and vertical antenna polarisation, in the
frequency range 1 GHz – 6 GHz
Result;
No significant emission was measured. The emission was at background level.
Requirement
• The radiated emission shall not exceed the limits specified in the standard CISPR 11, CISPR 22
for class A equipment.
Result
The object passed the test.
Version: 1
-60- 1416-18
Environmental conditions
Ambient temperature 21 °C
Requirement
The conducted emission at the power supply port shall not exceed the levels specified in CISPR 22 for
class A equipment.
Result
The object passed the test.
Version: 1
-65- 1416-18
12 MEASUREMENT UNCERTAINTY
The measurement uncertainties in the results presented are as specified below unless otherwise
indicated.
The used EMC test generators are calibrated on an annual base and comply with the tolerances
mentioned in the applicable test standard.
Version: 1