Object Homogenous series of HV current-limiting back-up fuse-links 5122-18

Type H221B / ACT Serial No. -

Designation Rated Rated maximum Rated current Rated minimum Rated


voltage breaking current breaking current frequency
kV kA A A Hz
H221B / ACT 80A 24 63 80 413 50
H221B / ACT 100A 24 63 100 483 50

Manufacturer Înter-Teknik Elektrik Ticaret ve San. Ltd. Şti.


Kemankeş Cad. No:53, Fransız Geçidi İş Mrk. C Blok D:16,
34425 Karaköy, Beyoğlu, Istanbul, Turkey *)

Client Înter-Teknik Elektrik Ticaret ve San. Ltd. Şti.


Kemankeş Cad. No:53, Fransız Geçidi İş Mrk. C Blok D:16,
34425 Karaköy, Beyoğlu, Istanbul, Turkey

Tested by KEMA Laboratories Prague


Zkušebnictví, a.s., Podnikatelská 547, Prague 9, the Czech Republic

Date of tests 23 and 24 May 2018

The object, constructed in accordance with the description, drawings and photographs incorporated in
this Certificate, has been subjected to the series of proving tests in accordance with

IEC 60282-1:2009, subclause 6.6 (Breaking tests)


+A1:2014

This Certificate has been issued by DNV GL following exclusively the STL Guides.

The results are shown in the record of proving tests and the oscillograms attached hereto. The values
obtained and the general performance are considered to comply with the above standard(s) and to
justify the ratings assigned by the manufacturer as listed on page 5.

This Certificate applies only to the object tested. The responsibility for
conformity of any object having the same type references as that tested
rests with the manufacturer.
*) as declared by the manufacturer

This Certificate consists of 70 pages in total.

DNV GL Netherlands B.V.

J.P. Fonteijne
Executive Vice President
KEMA Laboratories

Arnhem, 13 July 2018


Version: 1

Copyright: Only integral reproduction of this Certificate is permitted without written permission from DNV GL. Electronic copies as PDF or scan of this
Certificate may be available and have the status “for information only”. The sealed and bound version of the Certificate is the only valid version.
-2- 5122-18

INFORMATION SHEET
1 KEMA Type Test Certificate
A KEMA Type Test Certificate contains a record of a series of (type) tests carried out in accordance
with a recognized standard. The object tested has fulfilled the requirements of this standard and the
relevant ratings assigned by the manufacturer are endorsed by DNV GL. In addition, the object’s
technical drawings have been verified and the condition of the object after the tests is assessed and
recorded. The Certificate contains the essential drawings and a description of the object tested. A
KEMA Type Test Certificate signifies that the object meets all the requirements of the named
subclauses of the standard. It can be identified by gold-embossed lettering on the cover and a gold
seal on its front sheet.
The Certificate is applicable to the object tested only. DNV GL is responsible for the validity and the
contents of the Certificate. The responsibility for conformity of any object having the same type
references as the one tested rests with the manufacturer.
Detailed rules on types of certification are given in DNV GL’s Certification procedure applicable to
KEMA Laboratories.

2 KEMA Report of Performance


A KEMA Report of Performance is issued when an object has successfully completed and passed a
subset (but not all) of test programmes in accordance with a recognized standard. In addition, the
object’s technical drawings have been verified and the condition of the object after the tests is
assessed and recorded. The report is applicable to the object tested only. A KEMA Report of
Performance signifies that the object meets the requirements of the named subclauses of the
standard. It can be identified by silver-embossed lettering on the cover and a silver seal on its front
sheet.
The sentence on the front sheet of a KEMA Report of Performance will state that the tests have been
carried out in accordance with …… The object has complied with the relevant requirements.

3 KEMA Test Report


A KEMA Test Report is issued in all other cases. Reasons for issuing a KEMA Test Report could be:
• Tests were performed according to the client’s instructions.
• Tests were performed only partially according to the standard.
• No technical drawings were submitted for verification and/or no assessment of the condition of
the object after the tests was performed.
• The object failed one or more of the performed tests.
The KEMA Test Report can be identified by the grey-embossed lettering on the cover and grey seal on
its front sheet.
In case the number of tests, the test procedure and the test parameters are based on a recognized
standard and related to the ratings assigned by the manufacturer, the following sentence will appear
on the front sheet. The tests have been carried out in accordance with the client's instructions. Test
procedure and test parameters were based on ..... If the object does not pass the tests such
behaviour will be mentioned on the front sheet. Verification of the drawings (if submitted) and
assessment of the condition after the tests is only done on client's request.
When the tests, test procedure and/or test parameters are not in accordance with a recognized
standard, the front sheet will state the tests have been carried out in accordance with client’s
instructions.

4 Official and uncontrolled test documents


The official test documents of DNV GL are issued in bound form. Uncontrolled copies may be provided
as a digital file for convenience of reproduction by the client. The copyright has to be respected at all
times.

5 Accreditation of KEMA Laboratories


The KEMA Laboratories of DNV GL are accredited in accordance with ISO/IEC 17025 by the respective
national accreditation bodies. KEMA Laboratories Arnhem, the Netherlands, is accredited by RvA under
nos. L020, L218, K006 and K009. KEMA Laboratories Chalfont, United States, is accredited by A2LA
under no. 0553.01. KEMA Laboratories Prague, the Czech Republic, is accredited by CAI as testing
laboratory no. 1035.
Version: 1
-3- 5122-18

TABLE OF CONTENTS

1 Identification of the object tested .................................................................................. 5


1.1 Ratings/characteristics of the object tested 5
1.2 Description of the object tested 5
1.3 List of drawings 6

2 General information ..................................................................................................... 7


2.1 The tests were witnessed by 7
2.2 The tests were carried out by 7
2.3 Accuracy of measurement 7

3 Legend ...................................................................................................................... 8

4 Summary of tests ........................................................................................................ 9

5 Breaking tests – TD1 (80 A) ....................................................................................... 15


5.1 Condition before test 15
5.2 Test circuit S01 16
5.3 Photographs before test 17
5.4 Test results and oscillograms 18
5.5 Condition/inspection after test 24

6 Breaking tests – TD1 (100 A)...................................................................................... 25


6.1 Condition before test 25
6.2 Test circuit S01 26
6.3 Photographs before test 27
6.4 Test results and oscillograms 28
6.5 Condition/inspection after test 32

7 Breaking tests – TD2 (80 A) ....................................................................................... 33


7.1 Condition before test 33
7.2 Test circuit S02 34
7.3 Photographs before test 35
7.4 Test results and oscillograms 36
7.5 Condition/inspection after test 42

8 Breaking tests – TD2 (100 A)...................................................................................... 43


8.1 Condition before test 43
8.2 Test circuit S03 44
8.3 Photographs before test 45
8.4 Test results and oscillograms 46
8.5 Condition/inspection after test 52

9 Breaking tests – TD3 (80 A) ....................................................................................... 53


Version: 1
-4- 5122-18

9.1 Condition before test 53


9.2 Test circuit S04 54
9.3 Photographs before test 55
9.4 Test results and oscillograms 56
9.5 Condition/inspection after test 60

10 Breaking tests – TD3 (100 A)...................................................................................... 61


10.1 Condition before test 61
10.2 Test circuit S05 62
10.3 Photographs before test 63
10.4 Test results and oscillograms 64
10.5 Condition/inspection after test 67

11 Measuring devices used ............................................................................................. 68


11.1 Breaking tests – TD1 68
11.2 Breaking tests – TD2 68
11.3 Breaking tests – TD3 68
11.4 Meteorological conditions 69

12 Drawings.................................................................................................................. 70
Version: 1
-5- 5122-18

1 IDENTIFICATION OF THE OBJECT TESTED

1.1 Ratings/characteristics of the object tested

Designation H221B / ACT 80A H221B / ACT 100A


Year of the manufacture 2018 2018
Voltage 24 24 kV
Number of poles 1 1
Frequency 50 50 Hz

Current:
Fuse-links 80 100 A

Maximum breaking current (I1) 63 63 kA X


Minimum breaking current (I3) 413 483 A X

Length 442 442 mm


Class back-up back-up X
Type of fuse-striker medium medium
Resistance 15,6±10% 12,9±10% m

X = This rating has been proved by the tests of this Certificate.

1.2 Description of the object tested

Homogenous series of HV current-limiting back-up fuse-links with a striker pin for indoor and outdoor
use.
Version: 1
-6- 5122-18

1.3 List of drawings

The manufacturer has guaranteed that the test object submitted for tests has been manufactured in
accordance with the following drawings and/or documents. KEMA Laboratories Prague has verified that
these drawings and/or documents adequately represent the test object. The manufacturer is
responsible for the correctness of these drawings and/or documents and the technical data presented.

The following drawings and/or documents have been included in this Certificate:
Drawing no./document no. Revision
2002 00

The following drawings and/or documents are only listed for reference and are kept in KEMA
Laboratories Prague’s files:
Drawing no./document no. Revision
203 01
045 01
041 01
20170809 00
146-11 -
1154 00
067 00
136 00
149 -
133-A -
083 -
135 02
Version: 1
-7- 5122-18

2 GENERAL INFORMATION

2.1 The tests were witnessed by

Name Company
Kerem Yalçin Înter-Teknik Elektrik Ticaret ve San. Ltd. Şti.,
Istanbul, Turkey

2.2 The tests were carried out by

Name Company
Petr Keclík KEMA Laboratories Prague,
Zkušebnictví, a.s., Prague, the Czech Republic

2.3 Accuracy of measurement

The guaranteed uncertainty in the figures mentioned, taking into account the total measuring system,
is less than 5%, unless mentioned otherwise.
The reported expanded uncertainties of measurements are stated as the standard uncertainty of
measurement multiplied by the coverage factor k=2, which for a normal distribution corresponds to a
probability of approximately 95 %. Determination is based on ENV 13005(GUM).
Version: 1
-8- 5122-18

3 LEGEND

Explanation of the letter symbols and abbreviations on the oscillograms


I Current through test object
U Voltage across test object
U Transient recovery voltage
t Time
Version: 1
-9- 5122-18

4 SUMMARY OF TESTS

Breaking tests – TD1 (80 A)


pojb23e pojb23e pojb23e pojb23e pojb23e
Test no.
e.017 e.018 e.024 e.025 e.026
Phase R, T R, T R, T R, T R, T
Prospective current kA - - 63,7 63,7 63,7
Initiation of arcing after voltage zero ° - - 53 76 74
Pre-arcing time ms - - 0,48 0,49 0,54
Cut-off current kA - - 14,2 15,7 15,621
Instantaneous current at initiation of arcing kA - - 11,9 12,9 12,655
Recovery voltage kV - - 21,1 21,3 21,1
Switching voltage, peak kV - - 49,9 59,5 59,3
Arcing time ms - - 5,01 4,39 3,83
Total operating time ms - - 5,49 4,89 4,38
Melt I²t A2s - - 22530 23529 22987
Total I²t A2s - - 121455 137218 140523
Energy J - - 347467 377767 372281
Peak value of current kA 98,8 - - - -
Symmetrical current, beginning kA 39,2 - - - -
Duration s 0,20 - - - -
Peak value of TRV kV - 45,6 - - -
Time coordinate of TRV μs - 85,7 - - -
Rated voltage kV - - 24 24 24
Rated current A - - 80 80 80
Duration of recovery voltage s - - 15 15 15
Înter- Înter- Înter-
Manufacturer of fuse-link - -
Teknik Teknik Teknik
Resistance before test m - - 15,5 15,4 15,3
Resistance after test M - - >100 >100 >100
Ambient temperature °C - - 23,9 23,9 23,9
Fuse-link No. - - 24/80/2 24/80/3 24/80/4

Remarks
Checking of prospective current at reduced voltage.
pojb23ee.017
After recalculation for 100%: prospective current 63,7 kA, cosφ=0,08.
pojb23ee.018 Checking of TRV.
Fuse cleared.
pojb23ee.024
Striker operated.
Fuse cleared.
pojb23ee.025
Striker operated.
Fuse cleared.
pojb23ee.026
Striker operated.
Version: 1
-10- 5122-18

Breaking tests – TD1 (100 A)


pojb23e pojb23e pojb23e
Test no.
e.030 e.031 e.032
Phase R, T R, T R, T
Prospective current kA 63,7 63,7 63,7
Initiation of arcing after voltage zero ° 80 78 60
Pre-arcing time ms 0,49 0,53 0,61
Cut-off current kA 17,7 17,6 16,5
Instantaneous current at initiation of arcing kA 14,4 14,2 13,4
Recovery voltage kV 21,0 21,2 20,9
Switching voltage, peak kV 60,7 59,6 53,8
Arcing time ms 3,66 4,59 4,61
Total operating time ms 4,16 5,12 5,22
Melt I²t A2s 31627 30776 29757
Total I²t A2s 196071 193316 180880
Energy J 445388 473237 424717
Rated voltage kV 24 24 24
Rated current A 100 100 100
Duration of recovery voltage s 15 15 15
Înter- Înter- Înter-
Manufacturer of fuse-link
Teknik Teknik Teknik
Resistance before test m 13,0 13,0 13,0
Resistance after test M >100 >100 >100
Ambient temperature °C 23,7 23,7 23,7
24/100/ 24/100/ 24/100/
Fuse-link No.
1 2 3

Remarks
Fuse cleared.
pojb23ee.030
Striker operated.
Fuse cleared.
pojb23ee.031
Striker operated.
Fuse cleared.
pojb23ee.032
Striker operated.
Version: 1
-11- 5122-18

Breaking tests – TD2 (80 A)


pojb24e pojb24e pojb24e pojb24e pojb24e
Test no.
e.036 e.038 e.039 e.040 e.041
Phase R, T R, T R, T R, T R, T
Prospective current kA - - 5,56 5,56 5,56
Making angle after voltage zero ° - - 10 10 10
Pre-arcing time ms - - 3,32 3,39 3,38
Cut-off current kA - - -6,20 -6,19 -6,26
Instantaneous current at initiation of arcing kA - - -5,06 -5,06 5,03
Recovery voltage kV - - 21,4 21,5 21,5
Switching voltage, peak kV - - -57,4 -56,6 -54,7
Arcing time ms - - 6,40 6,40 6,70
Total operating time ms - - 9,80 9,80 10,1
Melt I²t A2s - - 21373 20654 21067
Total I²t A2s - - 103178 103659 111314
Energy J - - 571990 576502 601110
Peak value of current kA -13,9 - - - -
Symmetrical current, beginning kA 5,56 - - - -
Duration ms 205 - - - -
Peak value of TRV kV - 46,9 - - -
Time coordinate of TRV μs - 316 - - -
Rated voltage kV - - 24 24 24
Rated current A - - 80 80 80
Duration of recovery voltage s - - 60 60 60
Înter- Înter- Înter-
Manufacturer of fuse-link - -
Teknik Teknik Teknik
Resistance before test m - - 14,3 14,3 14,4
Resistance after test M - - >100 >100 >100
Ambient temperature °C - - 23,7 23,7 23,7
Fuse-link No. - - 24/80/4 24/80/5 24/80/6

Remarks
pojb24ee.036 Checking of prospective current.
pojb24ee.038 Checking of TRV.
Fuse cleared.
pojb24ee.039
Striker operated.
Fuse cleared.
pojb24ee.040
Striker operated.
Fuse cleared.
pojb24ee.041
Striker operated.
Version: 1
-12- 5122-18

Breaking tests – TD2 (100 A)


pojb24e pojb24e pojb24e pojb24e pojb24e
Test no.
e.042 e.043 e.044 e.045 e.046
Phase R, T R, T R, T R, T R, T
Prospective current kA - - 6,49 6,49 6,49
Making angle after voltage zero ° - - 9 10 9
Pre-arcing time ms - - 3,41 3,39 3,40
Cut-off current kA - - -7,29 -7,29 -7,25
Instantaneous current at initiation of arcing kA - - -6,00 -5,99 -5,99
Recovery voltage kV - - 21,3 21,3 21,4
Switching voltage, peak kV - - -55,5 -56,0 -55,9
Arcing time ms - - 6,50 6,50 6,50
Total operating time ms - - 9,90 9,90 9,90
Melt I²t A2s - - 30953 30530 30713
Total I²t A2s - - 145018 143134 142039
Energy J - - 669419 666158 664414
Peak value of current kA 16,1 - - - -
Symmetrical current, beginning kA 6,49 - - - -
Duration ms 65,0 - - - -
Peak value of TRV kV - 45,8 - - -
Time coordinate of TRV μs - 327 - - -
Rated voltage kV - - 24 24 24
Rated current A - - 100 100 100
Duration of recovery voltage s - - 60 60 60
Înter- Înter- Înter-
Manufacturer of fuse-link - -
Teknik Teknik Teknik
Resistance before test m - - 13,0 13,1 13,0
Resistance after test M - - >100 >100 >100
Ambient temperature °C - - 24,8 24,8 24,8
24/100/ 24/100/ 24/100/
Fuse-link No. - -
4 5 6

Remarks
pojb24ee.042 Checking of prospective current.
pojb24ee.043 Checking of TRV.
Fuse cleared.
pojb24ee.044
Striker operated.
Fuse cleared.
pojb24ee.045
Striker operated.
Fuse cleared.
pojb24ee.046
Striker operated.
Version: 1
-13- 5122-18

Breaking tests – TD3 (80 A)


pojb24e pojb24e pojb24e
Test no.
e.057 e.065 e.066
Phase R, T R, T R, T
Minimum melting current A - 411 413
Recovery voltage kV - 26,7 26,6
Switching voltage, peak kV - 37,9 37,7
Power factor - - 0,42 0,42
Arcing time ms - 39,7 62,3
Pre-arcing time s - 6,19 6,82
Total operating time s - 6,23 6,88
Melt I²t kA s
2
- 1,04 1,16
Total I²t kA2s - 1,061 1,17
Voltage open-circuit kV 25,6 - -
Rated voltage kV - 24 24
Rated current A - 80 80
Duration of recovery voltage s - 60 60
Înter- Înter-
Manufacturer of fuse-link -
Teknik Teknik
Resistance before test m - 15,3 15,3
Resistance after test M - >100 >100
Ambient temperature °C - 24,8 24,8
24/80/1
Fuse-link No. - 24/80/9
0

Remarks
pojb24ee.057 Checking of TRV.
Fuse cleared.
pojb24ee.065
Striker operated.
Fuse cleared.
pojb24ee.066
Striker operated.
Version: 1
-14- 5122-18

Breaking tests – TD3 (100 A)


pojb24e pojb24e
Test no.
e.067 e.068
Phase R, T R, T
Minimum melting current A 483 479
Recovery voltage kV 27,0 26,7
Switching voltage, peak kV 38,0 37,9
Power factor - 0,42 0,00
Arcing time ms 34,2 49,7
Pre-arcing time s 4,73 4,88
Total operating time s 4,76 4,93
Melt I²t kA s
2
1,10 1,12
Total I²t kA2s 1,11 1,13
Rated voltage kV 24 24
Rated current A 100 100
Duration of recovery voltage s 60 60
Înter- Înter-
Manufacturer of fuse-link
Teknik Teknik
Resistance before test m 13,0 13,1
Resistance after test M >100 >100
Ambient temperature °C 24,8 24,8
24/100/ 24/100/
Fuse-link No.
7 8

Remarks
Fuse cleared.
pojb24ee.067
Striker operated.
Fuse cleared.
pojb24ee.068
Striker operated.
Version: 1
-15- 5122-18

5 BREAKING TESTS – TD1 (80 A)

Standard and date


Standard IEC 60282-1, subclause 6.6
Test date 23 May 2018

5.1 Condition before test

Fuse-link mounted vertically in open air.


Fuse-base new.
New fuse-link before each test.
Version: 1
-16- 5122-18

5.2 Test circuit S01

G MB L R MS PT TO
U 
C1
R1

G = Generator TO = Test Object U = Voltage Measurement to earth


MB = Master Breaker L = Reactor I = Current Measurement
MS = Make Switch R = Resistor PT = Power Transformer
C = Capacitor

Supply TRV control elements added Prospective TRV of supply


(supply)
Power MVA 1317 uC kV 45,6
C1 µF 0,862
Frequency Hz 50 t3 µs 85,7
R1 (in parallel)  18
Phase(s) 1 td µs -
R1 (in series)  -
Voltage kV 20,9 RRRV kV/µs 0,532
L1 mH -
Current kA 63
Cd nF -
Impedance  0,332
Neutral not earthed
Power factor 0,08

Neutral not earthed

Load
Short-circuit point earthed

Remarks: -
Version: 1
-17- 5122-18

5.3 Photographs before test


Version: 1
-18- 5122-18

5.4 Test results and oscillograms

Overview of test numbers


pojb23ee.017
pojb23ee.018
pojb23ee.024
pojb23ee.025
pojb23ee.026

Remarks
-
Version: 1
-19- 5122-18

Checking of prospective current – TD1

Test number: pojb23ee.017


Phase R, T
Peak value of current kA 98,8
Symmetrical current, beginning kA 39,2
Duration s 0,20

Rated voltage - kV Resistance before test - m


Rated current - A Resistance after test - M
Duration of recovery voltage - s Ambient temperature - °C
Manufacturer of fuse-link - Fuse-link No. -

Remarks: Checking of prospective current at reduced voltage.


After recalculation for 100%: prospective current 63,7 kA, cosφ=0,08.
Version: 1
-20- 5122-18

Checking of prospective TRV

Test number: pojb23ee.018


Phase R, T
Peak value of TRV kV 45,6
Time coordinate of TRV μs 85,7

Rated voltage - kV Resistance before test - m


Rated current - A Resistance after test - M
Duration of recovery voltage - s Ambient temperature - °C
Manufacturer of fuse-link - Fuse-link No. -

Remarks: Checking of TRV.


Version: 1
-21- 5122-18

Breaking tests – TD1

Test number: pojb23ee.024


Phase R, T
Prospective current kA 63,7
Initiation of arcing after voltage zero ° 53
Pre-arcing time ms 0,48
Cut-off current kA 14,2
Instantaneous current at initiation of
kA 11,9
arcing
Recovery voltage kV 21,1
Switching voltage, peak kV 49,9
Arcing time ms 5,01
Total operating time ms 5,49

Melt I²t A2s 22530

Total I²t A2s 121455


Energy J 347467

Rated voltage 24 kV Resistance before test 15,5 m


Rated current 80 A Resistance after test >100 M
Duration of recovery voltage 15 s Ambient temperature 23,9 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/80/2

Remarks: Fuse cleared.


Striker operated.
Version: 1
-22- 5122-18

Breaking tests – TD1

Test number: pojb23ee.025


Phase R, T
Prospective current kA 63,7
Initiation of arcing after voltage zero ° 76
Pre-arcing time ms 0,49
Cut-off current kA 15,7
Instantaneous current at initiation of
kA 12,9
arcing
Recovery voltage kV 21,3
Switching voltage, peak kV 59,5
Arcing time ms 4,39
Total operating time ms 4,89

Melt I²t A2s 23529

Total I²t A2s 137218


Energy J 377767

Rated voltage 24 kV Resistance before test 15,4 m


Rated current 80 A Resistance after test >100 M
Duration of recovery voltage 15 s Ambient temperature 23,9 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/80/3

Remarks: Fuse cleared.


Striker operated.
Version: 1
-23- 5122-18

Breaking tests – TD1

Test number: pojb23ee.026


Phase R, T
Prospective current kA 63,7
Initiation of arcing after voltage zero ° 74
Pre-arcing time ms 0,54
Cut-off current kA 15,621
Instantaneous current at initiation of
kA 12,655
arcing
Recovery voltage kV 21,1
Switching voltage, peak kV 59,3
Arcing time ms 3,83
Total operating time ms 4,38

Melt I²t A2s 22987

Total I²t A2s 140523


Energy J 372281

Rated voltage 24 kV Resistance before test 15,3 m


Rated current 80 A Resistance after test >100 M
Duration of recovery voltage 15 s Ambient temperature 23,9 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/80/4

Remarks: Fuse cleared.


Striker operated.
Version: 1
-24- 5122-18

5.5 Condition/inspection after test

Externally no visible change.


Fuse-link intact.
Striker operated.
Version: 1
-25- 5122-18

6 BREAKING TESTS – TD1 (100 A)

Standard and date


Standard IEC 60282-1, subclause 6.6
Test date 23 May 2018

6.1 Condition before test

Fuse-link mounted vertically in open air.


Fuse-base new.
New fuse-link before each test.
Version: 1
-26- 5122-18

6.2 Test circuit S01

G MB L R MS PT TO
U 
C1
R1

G = Generator TO = Test Object U = Voltage Measurement to earth


MB = Master Breaker L = Reactor I = Current Measurement
MS = Make Switch R = Resistor PT = Power Transformer
C = Capacitor

Supply TRV control elements added Prospective TRV of supply


(supply)
Power MVA 1317 uC kV 45,6
C1 µF 0,862
Frequency Hz 50 t3 µs 85,7
R1 (in parallel)  18
Phase(s) 1 td µs -
R1 (in series)  -
Voltage kV 20,9 RRRV kV/µs 0,532
L1 mH -
Current kA 63
Cd nF -
Impedance  0,332
Neutral not earthed
Power factor 0,08

Neutral not earthed

Load
Short-circuit point earthed

Remarks: -
Version: 1
-27- 5122-18

6.3 Photographs before test


Version: 1
-28- 5122-18

6.4 Test results and oscillograms

Overview of test numbers


pojb23ee.030
pojb23ee.031
pojb23ee.032

Remarks
-
Version: 1
-29- 5122-18

Breaking tests – TD1

Test number: pojb23ee.030


Phase R, T
Prospective current kA 63,7
Initiation of arcing after voltage zero ° 80
Pre-arcing time ms 0,49
Cut-off current kA 17,7
Instantaneous current at initiation of
kA 14,4
arcing
Recovery voltage kV 21,0
Switching voltage, peak kV 60,7
Arcing time ms 3,66
Total operating time ms 4,16

Melt I²t A2s 31627

Total I²t A2s 196071


Energy J 445388

Rated voltage 24 kV Resistance before test 13,0 m


Rated current 100 A Resistance after test >100 M
Duration of recovery voltage 15 s Ambient temperature 23,7 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/100/1

Remarks: Fuse cleared.


Striker operated.
Version: 1
-30- 5122-18

Breaking tests – TD1

Test number: pojb23ee.031


Phase R, T
Prospective current kA 63,7
Initiation of arcing after voltage zero ° 78
Pre-arcing time ms 0,53
Cut-off current kA 17,6
Instantaneous current at initiation of
kA 14,2
arcing
Recovery voltage kV 21,2
Switching voltage, peak kV 59,6
Arcing time ms 4,59
Total operating time ms 5,12

Melt I²t A2s 30776

Total I²t A2s 193316


Energy J 473237

Rated voltage 24 kV Resistance before test 13,0 m


Rated current 100 A Resistance after test >100 M
Duration of recovery voltage 15 s Ambient temperature 23,7 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/100/2

Remarks: Fuse cleared.


Striker operated.
Version: 1
-31- 5122-18

Breaking tests – TD1

Test number: pojb23ee.032


Phase R, T
Prospective current kA 63,7
Initiation of arcing after voltage zero ° 60
Pre-arcing time ms 0,61
Cut-off current kA 16,5
Instantaneous current at initiation of
kA 13,4
arcing
Recovery voltage kV 20,9
Switching voltage, peak kV 53,8
Arcing time ms 4,61
Total operating time ms 5,22

Melt I²t A2s 29757

Total I²t A2s 180880


Energy J 424717

Rated voltage 24 kV Resistance before test 13,0 m


Rated current 100 A Resistance after test >100 M
Duration of recovery voltage 15 s Ambient temperature 23,7 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/100/3

Remarks: Fuse cleared.


Striker operated.
Version: 1
-32- 5122-18

6.5 Condition/inspection after test

Externally no visible change.


Fuse-link intact.
Striker operated.
Version: 1
-33- 5122-18

7 BREAKING TESTS – TD2 (80 A)

Standard and date


Standard IEC 60282-1, subclause 6.6
Test date 24 May 2018

7.1 Condition before test

Fuse-link mounted vertically in open air.


Fuse-base in same condition.
New fuse-link before each test.
Version: 1
-34- 5122-18

7.2 Test circuit S02

G MB L R MS PT TO
U 
C1
R1

G = Generator TO = Test Object U = Voltage Measurement to earth


MB = Master Breaker L = Reactor I = Current Measurement
MS = Make Switch R = Resistor PT = Power Transformer
C = Capacitor

Supply TRV control elements added Prospective TRV of supply


(supply)
Power MVA 118 uC kV 46,9
C1 µF 2,01
Frequency Hz 50 t3 µs 316
R1 (in parallel)  20
Phase(s) 1 td µs -
R1 (in series)  -
Voltage kV 21,3 RRRV kV/µs 0,150
L1 mH -
Current kA 5,56
Cd nF -
Impedance  3,83
Neutral not earthed
Power factor 0,08
Neutral not earthed

Load
Short-circuit point earthed

Remarks: -
Version: 1
-35- 5122-18

7.3 Photographs before test


Version: 1
-36- 5122-18

7.4 Test results and oscillograms

Overview of test numbers


pojb24ee.036
pojb24ee.038
pojb24ee.039
pojb24ee.040
pojb24ee.041

Remarks
-
Version: 1
-37- 5122-18

Checking of prospective current – TD2

Test number: pojb24ee.036


Phase R, T
Peak value of current kA -13,9
Symmetrical current, beginning kA 5,56
Duration ms 205

Rated voltage - kV Resistance before test - m


Rated current - A Resistance after test - M
Duration of recovery voltage - s Ambient temperature - °C
Manufacturer of fuse-link - Fuse-link No. -

Remarks: Checking of prospective current.


Version: 1
-38- 5122-18

Checking of prospective TRV

Test number: pojb24ee.038


Phase R, T
Peak value of TRV kV 46,9
Time coordinate of TRV μs 316

Rated voltage - kV Resistance before test - m


Rated current - A Resistance after test - M
Duration of recovery voltage - s Ambient temperature - °C
Manufacturer of fuse-link - Fuse-link No. -

Remarks: Checking of TRV.


Version: 1
-39- 5122-18

Breaking tests – TD2

Test number: pojb24ee.039


Phase R, T
Prospective current kA 5,56
Making angle after voltage zero ° 10
Pre-arcing time ms 3,32
Cut-off current kA -6,20
Instantaneous current at initiation of
kA -5,06
arcing
Recovery voltage kV 21,4
Switching voltage, peak kV -57,4
Arcing time ms 6,40
Total operating time ms 9,80

Melt I²t A2s 21373

Total I²t A2s 103178


Energy J 571990

Rated voltage 24 kV Resistance before test 14,3 m


Rated current 80 A Resistance after test >100 M
Duration of recovery voltage 60 s Ambient temperature 23,7 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/80/4

Remarks: Fuse cleared.


Striker operated.
Version: 1
-40- 5122-18

Breaking tests – TD2

Test number: pojb24ee.040


Phase R, T
Prospective current kA 5,56
Making angle after voltage zero ° 10
Pre-arcing time ms 3,39
Cut-off current kA -6,19
Instantaneous current at initiation of
kA -5,06
arcing
Recovery voltage kV 21,5
Switching voltage, peak kV -56,6
Arcing time ms 6,40
Total operating time ms 9,80

Melt I²t A2s 20654

Total I²t A2s 103659


Energy J 576502

Rated voltage 24 kV Resistance before test 14,3 m


Rated current 80 A Resistance after test >100 M
Duration of recovery voltage 60 s Ambient temperature 23,7 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/80/5

Remarks: Fuse cleared.


Striker operated.
Version: 1
-41- 5122-18

Breaking tests – TD2

Test number: pojb24ee.041


Phase R, T
Prospective current kA 5,56
Making angle after voltage zero ° 10
Pre-arcing time ms 3,38
Cut-off current kA -6,26
Instantaneous current at initiation of
kA 5,03
arcing
Recovery voltage kV 21,5
Switching voltage, peak kV -54,7
Arcing time ms 6,70
Total operating time ms 10,1

Melt I²t A2s 21067

Total I²t A2s 111314


Energy J 601110

Rated voltage 24 kV Resistance before test 14,4 m


Rated current 80 A Resistance after test >100 M
Duration of recovery voltage 60 s Ambient temperature 23,7 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/80/6

Remarks: Fuse cleared.


Striker operated.
Version: 1
-42- 5122-18

7.5 Condition/inspection after test

Externally no visible change.


Fuse-link intact.
Striker operated.
Version: 1
-43- 5122-18

8 BREAKING TESTS – TD2 (100 A)

Standard and date


Standard IEC 60282-1, subclause 6.6
Test date 24 May 2018

8.1 Condition before test

Fuse-link mounted vertically in open air.


Fuse-base in same condition.
New fuse-link before each test.
Version: 1
-44- 5122-18

8.2 Test circuit S03

G MB L R MS PT TO
U 
C1
R1

G = Generator TO = Test Object U = Voltage Measurement to earth


MB = Master Breaker L = Reactor I = Current Measurement
MS = Make Switch R = Resistor PT = Power Transformer
C = Capacitor

Supply TRV control elements added Prospective TRV of supply


(supply)
Power MVA 138 uC kV 45,8
C1 µF 2,41
Frequency Hz 50 t3 µs 327
R1 (in parallel)  20
Phase(s) 1 td µs -
R1 (in series)  -
Voltage kV 21,3 RRRV kV/µs 0,140
L1 mH -
Current kA 6,49
Cd nF -
Impedance  3,28
Neutral not earthed
Power factor 0,09
Neutral not earthed

Load
Short-circuit point earthed

Remarks: -
Version: 1
-45- 5122-18

8.3 Photographs before test


Version: 1
-46- 5122-18

8.4 Test results and oscillograms

Overview of test numbers


pojb24ee.042
pojb24ee.043
pojb24ee.044
pojb24ee.045
pojb24ee.046

Remarks
-
Version: 1
-47- 5122-18

Checking of prospective current – TD2

Test number: pojb24ee.042


Phase R, T
Peak value of current kA 16,1
Symmetrical current, beginning kA 6,49
Duration ms 65,0

Rated voltage - kV Resistance before test - m


Rated current - A Resistance after test - M
Duration of recovery voltage - s Ambient temperature - °C
Manufacturer of fuse-link - Fuse-link No. -

Remarks: Checking of prospective current.


Version: 1
-48- 5122-18

Checking of prospective TRV

Test number: pojb24ee.043


Phase R, T
Peak value of TRV kV 45,8
Time coordinate of TRV μs 327

Rated voltage - kV Resistance before test - m


Rated current - A Resistance after test - M
Duration of recovery voltage - s Ambient temperature - °C
Manufacturer of fuse-link - Fuse-link No. -

Remarks: Checking of TRV.


Version: 1
-49- 5122-18

Breaking tests – TD2

Test number: pojb24ee.044


Phase R, T
Prospective current kA 6,49
Making angle after voltage zero ° 9
Pre-arcing time ms 3,41
Cut-off current kA -7,29
Instantaneous current at initiation of
kA -6,00
arcing
Recovery voltage kV 21,3
Switching voltage, peak kV -55,5
Arcing time ms 6,50
Total operating time ms 9,90

Melt I²t A2s 30953

Total I²t A2s 145018


Energy J 669419

Rated voltage 24 kV Resistance before test 13,0 m


Rated current 100 A Resistance after test >100 M
Duration of recovery voltage 60 s Ambient temperature 24,8 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/100/4

Remarks: Fuse cleared.


Striker operated.
Version: 1
-50- 5122-18

Breaking tests – TD2

Test number: pojb24ee.045


Phase R, T
Prospective current kA 6,49
Making angle after voltage zero ° 10
Pre-arcing time ms 3,39
Cut-off current kA -7,29
Instantaneous current at initiation of
kA -5,99
arcing
Recovery voltage kV 21,3
Switching voltage, peak kV -56,0
Arcing time ms 6,50
Total operating time ms 9,90

Melt I²t A2s 30530

Total I²t A2s 143134


Energy J 666158

Rated voltage 24 kV Resistance before test 13,1 m


Rated current 100 A Resistance after test >100 M
Duration of recovery voltage 60 s Ambient temperature 24,8 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/100/5

Remarks: Fuse cleared.


Striker operated.
Version: 1
-51- 5122-18

Breaking tests – TD2

Test number: pojb24ee.046


Phase R, T
Prospective current kA 6,49
Making angle after voltage zero ° 9
Pre-arcing time ms 3,40
Cut-off current kA -7,25
Instantaneous current at initiation of
kA -5,99
arcing
Recovery voltage kV 21,4
Switching voltage, peak kV -55,9
Arcing time ms 6,50
Total operating time ms 9,90

Melt I²t A2s 30713

Total I²t A2s 142039


Energy J 664414

Rated voltage 24 kV Resistance before test 13,0 m


Rated current 100 A Resistance after test >100 M
Duration of recovery voltage 60 s Ambient temperature 24,8 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/100/6

Remarks: Fuse cleared.


Striker operated.
Version: 1
-52- 5122-18

8.5 Condition/inspection after test

Externally no visible change.


Fuse-link intact.
Striker operated.
Version: 1
-53- 5122-18

9 BREAKING TESTS – TD3 (80 A)

Standard and date


Standard IEC 60282-1, subclause 6.6
Test date 24 May 2018

9.1 Condition before test

Fuse-link mounted vertically in open air.


Fuse-base in same condition.
New fuse-link before each test.
Version: 1
-54- 5122-18

9.2 Test circuit S04

G MB L R MS PT TO
U 
C1
R1

G = Generator TO = Test Object U = Voltage Measurement to earth


MB = Master Breaker L = Reactor I = Current Measurement
MS = Make Switch R = Resistor PT = Power Transformer
C = Capacitor

Supply TRV control elements added


(supply)
Power MVA 9,86
C1 µF 0,289
Frequency Hz 50
R1 (in parallel)  2000
Phase(s) 1
R1 (in series)  -
Voltage kV 24
L1 mH -
Current A 411
Cd nF -
Impedance  58,4
Neutral not earthed
Power factor 0,42
Neutral not earthed

Load
Short-circuit point earthed

Remarks: -
Version: 1
-55- 5122-18

9.3 Photographs before test


Version: 1
-56- 5122-18

9.4 Test results and oscillograms

Overview of test numbers


pojb24ee.057
pojb24ee.065
pojb24ee.066

Remarks
-
Version: 1
-57- 5122-18

Checking of prospective TRV

Test number: pojb24ee.057


Phase R, T
Voltage open-circuit kV 25,6

Rated voltage - kV Resistance before test - m


Rated current - A Resistance after test - M
Duration of recovery voltage - s Ambient temperature - °C
Manufacturer of fuse-link - Fuse-link No. -

Remarks: Checking of TRV.


Version: 1
-58- 5122-18

Breaking tests – TD3

Test number: pojb24ee.065


Phase R, T
Minimum melting current A 411
Recovery voltage kV 26,7
Switching voltage, peak kV 37,9
Power factor - 0,42
Arcing time ms 39,7
Pre-arcing time s 6,19
Total operating time s 6,23
Melt I²t kA2s 1,04
Total I²t kA2s 1,061

Rated voltage 24 kV Resistance before test 15,3 m


Rated current 80 A Resistance after test >100 M
Duration of recovery voltage 60 s Ambient temperature 24,8 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/80/9

Remarks: Fuse cleared.


Striker operated.
Version: 1
-59- 5122-18

Breaking tests – TD3

Test number: pojb24ee.066


Phase R, T
Minimum melting current A 413
Recovery voltage kV 26,6
Switching voltage, peak kV 37,7
Power factor - 0,42
Arcing time ms 62,3
Pre-arcing time s 6,82
Total operating time s 6,88
Melt I²t kA s
2
1,16
Total I²t kA2s 1,17

Rated voltage 24 kV Resistance before test 15,3 m


Rated current 80 A Resistance after test >100 M
Duration of recovery voltage 60 s Ambient temperature 24,8 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/80/10

Remarks: Fuse cleared.


Striker operated.
Version: 1
-60- 5122-18

9.5 Condition/inspection after test

Externally no visible change.


Fuse-link intact.
Striker operated.
Version: 1
-61- 5122-18

10 BREAKING TESTS – TD3 (100 A)

Standard and date


Standard IEC 60282-1, subclause 6.6
Test date 24 May 2018

10.1 Condition before test

Fuse-link mounted vertically in open air.


Fuse-base in same condition.
New fuse-link before each test.
Version: 1
-62- 5122-18

10.2 Test circuit S05

G MB L R MS PT TO
U 
C1
R1

G = Generator TO = Test Object U = Voltage Measurement to earth


MB = Master Breaker L = Reactor I = Current Measurement
MS = Make Switch R = Resistor PT = Power Transformer
C = Capacitor

Supply TRV control elements added


(supply)
Power MVA 11,5
C1 µF 0,289
Frequency Hz 50
R1 (in parallel)  2000
Phase(s) 1
R1 (in series)  -
Voltage kV 24
L1 mH -
Current A 479
Cd nF -
Impedance  50,1
Neutral not earthed
Power factor 0,42
Neutral not earthed

Load
Short-circuit point earthed

Remarks: -
Version: 1
-63- 5122-18

10.3 Photographs before test


Version: 1
-64- 5122-18

10.4 Test results and oscillograms

Overview of test numbers


pojb24ee.067
pojb24ee.068

Remarks
-
Version: 1
-65- 5122-18

Breaking tests – TD3

Test number: pojb24ee.067


Phase R, T
Minimum melting current A 483
Recovery voltage kV 27,0
Switching voltage, peak kV 38,0
Power factor - 0,42
Arcing time ms 34,2
Pre-arcing time s 4,73
Total operating time s 4,76
Melt I²t kA s
2
1,10
Total I²t kA2s 1,11

Rated voltage 24 kV Resistance before test 13,0 m


Rated current 100 A Resistance after test >100 M
Duration of recovery voltage 60 s Ambient temperature 24,8 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/100/7

Remarks: Fuse cleared.


Striker operated.
Version: 1
-66- 5122-18

Breaking tests – TD3

Test number: pojb24ee.068


Phase R, T
Minimum melting current A 479
Recovery voltage kV 26,7
Switching voltage, peak kV 37,9
Power factor - 0,00
Arcing time ms 49,7
Pre-arcing time s 4,88
Total operating time s 4,93
Melt I²t kA s
2
1,12
Total I²t kA2s 1,13

Rated voltage 24 kV Resistance before test 13,1 m


Rated current 100 A Resistance after test >100 M
Duration of recovery voltage 60 s Ambient temperature 24,8 °C
Manufacturer of fuse-link Înter-Teknik Fuse-link No. 24/100/8

Remarks: Fuse cleared.


Striker operated.
Version: 1
-67- 5122-18

10.5 Condition/inspection after test

Externally no visible change.


Fuse-link intact.
Striker operated.
Version: 1
-68- 5122-18

11 MEASURING DEVICES USED

11.1 Breaking tests – TD1

Measurand Measuring sensor / device Digital measuring system,


type DMS
Type Serial No. Transfer constant Input channel, serial No.
I Rogowski coil RC 01/98 300 kA / 10 V 100-10100-8
Integrative IZ 001/05
amplifier
U Combined voltage DK 001/90 0,5 kV / 1 V 100-10100-1
divider

11.2 Breaking tests – TD2

Measurand Measuring sensor / device Digital measuring system,


type DMS
Type Serial No. Transfer constant Input channel, serial No.
I Rogowski coil RC 01/98 300 kA / 10 V 100-10100-8
Integrative IZ 001/05
amplifier
U Combined voltage DK 001/90 0,5 kV / 1 V 100-10100-1
divider

11.3 Breaking tests – TD3

Measurand Measuring sensor / device Digital measuring system,


type DMS
Type Serial No. Transfer constant Input channel, serial No.
I Cage shunt 0786/14 2 kA / 2 V 100-10100-8
U Combined voltage DK 001/90 0,5 kV / 1 V 100-10100-1
divider

Resistance measurement
Multimeter Agilent, type U1252B, serial No. MY53010068
Multimeter Agilent, type U1252B, serial No. MY53370151

Meteorological conditions measurement


Meteorological station, type Vantage Pro 2, serial No. 3788A-6312
Version: 1
-69- 5122-18

11.4 Meteorological conditions

Test No. Date Time Temperature Relative humidity Atmospheric pressure


(dd.mm.yyyy) (hh:mm) (oC) (%) (hPa)
pojb23ee.024 23.05.2018 13:31 22,8 60 985
pojb23ee.025 23.05.2018 13:38 22,7 60 985
pojb23ee.026 23.05.2018 13:45 22,9 59 985
pojb23ee.030 23.05.2018 14:50 23,2 55 985
pojb23ee.031 23.05.2018 14:57 23,6 54 985
pojb23ee.032 23.05.2018 15:03 23,7 52 985
pojb24ee.039 24.05.2018 15:09 24,0 48 985
pojb24ee.040 24.05.2018 15:15 24,0 48 985
pojb24ee.041 24.05.2018 15:20 23,9 48 985
pojb24ee.044 24.05.2018 15:45 23,4 48 985
pojb24ee.045 24.05.2018 15:51 23,4 49 985
pojb24ee.046 24.05.2018 15:57 23,4 48 985
pojb24ee.065 24.05.2018 18:56 21,9 51 985
pojb24ee.066 24.05.2018 19:03 21,9 51 985
pojb24ee.067 24.05.2018 19:26 21,7 51 985
pojb24ee.068 24.05.2018 19:31 21,7 50 986
Version: 1
-70- 5122-18

12 DRAWINGS