Professional Documents
Culture Documents
EXPERIMENT No. : 1
Date : - -
1
Section Roll No
OBSERVATION TABLE :
Sr. I1 I2 I3 V1 V2 V3
No. (A) (A) (A) (V) (V) (V)
SAMPLE CALCULATION :
For observation No. : ..............
V V1 V2 V3
I I1 I 2 I3
CALCULATION TABLE :
Sr. V I
No. (V) (A)
7
RESULT :
Kirchhoff’s voltage law and Kirchhoff’s current law are verified. In case of
discrepancies, the errors in the instruments is one of the reasons. Using
Kirchhoff’s laws, the currents and voltages in an electric circuit can be
calculated.
_________________________________________________________
EXPERIMENT No. : 2
Date : - -
9
the inductive reactance ( X L 2 f L ) and capacitive reactance
1 1
fR
2 LC
The phasor diagram at resonance is shown in Fig (c). It may be noted
that at series resonance, the circuit impedance is minimum and the
PROCEDURE :
1) Make the connections as shown in the circuit diagram.
2).Set the dimmerstat to zero output position and switch on the supply.
3) Adjust the dimmerstat to a suitable voltage and note V , I , VR , VL ,
OBSERVATION TABLE :
Sr. V I VR VL VC P
No. (V) (A) (V) (V) (V) (W)
4
Section Roll No
SAMPLE CALCULATION :
P
cos
VI
V= and cos
CALCULATION TABLE :
PHASOR DIAGRAM :
Draw the phasor diagrams for all observations on the graph paper.
15
RESULT :
The phase relationship between voltage and current for R – L – C –
series circuit have been verified. In case of discrepancies, the errors in
the instruments and the assumption of ideal L and C components are
one of the reasons.
_________________________________________________________
EXPERIMENT No. : 3
Date : - -
17
Section Roll No
source and note the three ammeter readings which gives I1a , I 2a
source and note the three ammeter readings which gives I1b , I2b
OBSERVATION TABLE :
I1 I1a I1b
I2 I 2a I 2b
I3 I3a I3b
CALCULATION TABLE :
I1 I1a I1b I1
I 2 I 2a I 2b I2
I3 I3a I3b I3
21
RESULT :
It is verified that the algebraic sum of the currents I1a & I1b , I 2a &
EXPERIMENT No. : 4
Date : - -
23
The frequency at which this occurs is known as resonance frequency
f R . It is given by
1 1 R2
fR 2
2 LC L
PROCEDURE :
1) Make the connections as shown in the circuit diagram.
2).Set the dimmerstat to zero output position and switch on the supply.
3) Adjust the dimmerstat to a suitable voltage and note V (or VC ), I ,
OBSERVATION TABLE :
Sr. V VC I I1 I2 VR VL P
No. (V) (A) (A) (A) (V) (V) (W)
4
Section Roll No
SAMPLE CALCULATION :
P
cos
VI
V= ;I= ; cos
CALCULATION TABLE :
PHASOR DIAGRAM :
Draw the phasor diagrams for all observations on the graph paper.
29
RESULT :
The phase relationship between voltage and current for R – L – C
parallel circuit have been verified. In case of discrepancies, the errors in
the instruments and the assumption of ideal L and C components are
one of the reasons.
_________________________________________________________
EXPERIMENT No. : 5
Date : - -
31
5) Note down line current, power, phase voltage and line voltage. Take
such four readings for different phase currents.
OBSERVATION TABLE :
Sr. VL VPH I L I PH P
No. (V) (V) (A) (W)
SAMPLE CALCULATION :
VL
VPH
PCalculated 3 VL I L
PObserved 3 P
Section Roll No
CALCULATION TABLE :
Total Power
Sr. VL
No. Observed Calculated VPH
(W) (W)
RESULT :
In a balanced star connected system, it is verified that I L I PH and
VL 3 VPH .
_________________________________________________________
39
Section Roll No
EXPERIMENT No. : 6
Date : - -
41
Section Roll No
OBSERVATION TABLE :
Sr. V1 I1 P1 V2 I2 P2
No. (V) (A) (W) (V) (A) (W)
1 230 V2' 0 0
2 230
3 230
4 230
5 230
6 230
7 230
8 230
9 230
SAMPLE CALCULATION :
47
V2
K
V1
V2' V2
% Regulation = 100 100
V2'
P2
% 100 100
P1
CALCULATION TABLE :
Sr.
% Regulation % Efficiency
No.
1 0 0
9
Section Roll No
GRAPH :
1) Plot percentage regulation on the Y – axis and load current I 2 on the
X – axis.
2) Plot percentage efficiency on the Y – axis and load current I 2 on the
X – axis.
3) Plot secondary terminal voltage V2 on the Y – axis and load current
I 2 on the X – axis.
RESULT :
The regulation varies with the load. Here % regulation increases as load
on the transformer increases. The efficiency increases upto some extent
of output and then it decreases. The above performance also depends
on the power factor of the load.
_________________________________________________________
49
Section Roll No
EXPERIMENT No. : 7
Date : - -
51
5) Note down phase current, line current, power, phase voltage (= line
voltage). Take such four readings for different phase currents.
OBSERVATION TABLE :
Sr. VL VPH IL I PH P
No. (V) (A) (A) (W)
SAMPLE CALCULATION :
IL
I PH
PCalculated 3 VL I L
PObserved 3 P
Section Roll No
CALCULATION TABLE :
Total Power
Sr. IL
No. Observed Calculated I PH
(W) (W)
RESULT :
In a balanced delta connected system, it is verified that I L 3 I PH
and VL VPH .
_________________________________________________________
59
Section Roll No
EXPERIMENT No. : 8
To perform
Open circuit test & Short circuit test
on a single phase transformer.
Date : - -
61
3) With rated current in primary (h.v. winding will be the primary side),
note the readings of the wattmeter, voltmeter and the two ammeters.
OBSERVATION TABLE :
Open Circuit Test (with meters in l. v. side) :
Vo Io Pi
(V) (A) (W)
230
4.545
CALCULATION :
V
A) Transformation ratio K 2
V1
V 230
As it is a step down transformer, K 2 0.5227
V1 440
B) From open circuit test:
During the test, the meters are connected in l.v. side. Hence following
parameters are referred to l.v. side.
Pi
cos o
Vo I o
Section Roll No
Vo
Ro,lv
I o cos o
Vo
X o,lv
I o sin o
Above parameters, when referred to h.v. side, are
2 2
Ro,hv Ro,lv
2 2
X o,hv X o,lv
C) From short circuit test:
During the test, the meters are connected in h.v. side. Hence following
parameters are referred to h.v. side.
Vsc
Z e,hv
I sc
Pc, fl
Re,hv 2
I sc
Pi
max.
Load VA VARated 2000 =
Pc, fl
69
Iron Copper Input
Output
Load loss loss (P1) % % Voltage
Load P2
p.f. (Pi) (PC) P2+Pi+Pc Efficiency Regulation
(W)
(W) (W) (W)
Unity
0.8
E) Efficiency and regulation:
100%
(lagging)
0.8
(leading)
Unity
0.8
50%
(lagging)
Rated Volt - Ampere of transformer = ( VA )Rated = 2KVA = 2000 VA
0.8
(leading)
Section Roll No
RESULT :
The open circuit test on the transformer gives the parameters Ro,lv and
X o,lv (referred to l.v. side) and the short circuit test gives Re, hv and
X e,hv (referred to h.v. side). From these values, equivalent circuits of the
Ro,lv Re,lv
X o,lv X e,lv
Ro,hv Re,hv
X o,hv X e,hv
At 100% load :
% Voltage
Power factor % Efficiency
Regulation
Unity
0.8 lagging
0.8 leading
71
At 50% load :
% Voltage
Power factor % Efficiency
Regulation
Unity
0.8 lagging
0.8 leading
_________________________________________________________