You are on page 1of 20

Resetting

1. Tipikal 1-A
Rele F50-CCT2
Model : SEPAM 20
Tipe Kurva : Very Inverse
Peralatan : Lumped 6,6 kV 750 kVA
I FLA Peralatan : 65,61 A
C/T Rasio : 100/5
Isc Min INC.CCT : 5,08 kA
Isc Max INC.CCT : 6,46 kA
LRA : 6,5 x 65,61 = 426,5 A

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA
1,05 x 65,61< Iset <1,4 x 65,61
68,9< Iset < 91,8
68,9 91,8
<Tap <
100 100
0,689<Tap <0,918
Dipilih:
Tap = 0,79
Iset = 79

Time Dial
Dipilih waktu operasi (td) = 0,3 detik

Time Dial=
td x
[( ) ]
I
Is
−1

13,5

Time Dial=
0,3 x
[( ) ]
6460
79
−1

13,5
Time Dial=1,795
Instantaneous Pickup

1
LRA Lumped< I ≫<0,8 x Isc min
426,5< I ≫ <0,8 x 5080
426,5< I ≫ <4064
426,5 4064
<Tap<
100 100
4,265< Tap< 40,64
Dipilih:
Tap = 5,12
Iset = 512
Time Delay = 0,3 s

Rele F50-CB73
Model : SEPAM 40
Tipe Kurva : Very Inverse
Peralatan : Trafo 7,5 MVA 6,6 kV
I FLA Peralatan : 656 A
C/T Rasio : 1250/5
Isc Min : 6,49 kA
Isc Max : 8,56 kA

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA
1,05 x 656< Iset < 1,4 x 656
688,9< Iset < 918,5
688,9 918,5
<Tap <
1250 1250
0,55<Tap <0,73
Dipilih:
Tap = 0,63
Iset = 787,5

Time Dial
Dipilih waktu operasi (td) = 0,5 detik

2
Time Dial=
td x
[( ) ]
I
Is
−1

13,5

Time Dial=
0,5 x
[( ) ]
8560
787,5
−1

13,5
Time Dial=0,365
Instantaneous Pickup
1,6 x FLA< I ≫< 0,8 x Isc min
1,6 x 656< I ≫ <0,8 x 6490
1050< I ≫<5192
1050 5192
<Tap <
1250 1250
0,84 <Tap< 4,15
Dipilih:
Tap = 1,2
Iset = 1500
Time Delay = 0,5 s

Rele F50-CB53
Model : SEPAM 20
Tipe Kurva : Very Inverse
Peralatan : Trafo 7,5 MVA 20 kV
I FLA Peralatan : 216,5 A
C/T Rasio : 300/5
Isc Max Beban (20 kV) : 2,142 kA
Isc Max Sekunder (20 kV): 2,825 kA
Isc Max Primer : 8,6 kA :
Isc Min : 6,97 kA

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA

3
1,05 x 216,5< Iset <1,4 x 216,5
277,3< Iset <301,1
277,3 301,1
<Tap <
300 300
0,75<Tap <1,01
Dipilih:
Tap = 0,87
Iset = 260

Time Dial
Dipilih waktu operasi (td) = 0,7 detik

Time Dial=
td x
[( ) ]
I
Is
−1

13,5

Time Dial=
0,7 x
[( ) ]
2142
260
−1

13,5
Time Dial=0,375

Instantaneous Pickup
Isc Max Sek < I ≫< 0,8 x Isc min
2825< I ≫ < 0,8 x 6970
2825< I ≫<5576
2825 5576
<Tap <
300 300
9,41<Tap <18,59

Dipilih:
Tap = 11
Iset = 3300
Time Delay = 0,1 s

2. Tipikal 1-B
Rele F50-CB51 & Rele F50-CB33

4
Model : SEPAM 40 & SEPAM 20
Tipe Kurva : Very Inverse
Peralatan : Total Trafo 7,5 MVA 20 kV
I FLA Peralatan : 216,5 A
C/T Rasio : 1250/5
Isc Min : 7,01 kA
Isc Max : 8,64 kA

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA
1,05 x 216,5< Iset <1,4 x 216,5
227,3< Iset <303,1
227,3 303,1
<Tap <
1250 1250
0,18<Tap <0,24
Dipilih:
Tap = 0,21
Iset = 260

Time Dial
Dipilih waktu operasi (td) = 0,3 detik

Time Dial=
td x ([ IsI )−1]
13,5

Time Dial=
0,3 x
[( ) ]
8640
260
−1

13,5
Time Dial=0,72
Instantaneous Pickup
1,6 x FLA< I ≫< 0,8 x Isc min
1,6 x 216,5< I ≫< 0,8 x 7010
346,5< I ≫ <5608

5
346,5 5608
<Tap<
1250 1250
0,277<Tap < 4,49
Dipilih:
Tap = 2,8
Iset = 3500
Time Delay = 0,3 s

Rele F50-CB31 & Rele F50-CB24


Model : SEPAM 40 & SEPAM 20
Tipe Kurva : Very Inverse
Peralatan : Total Trafo 17,4 MVA 20 kV
I FLA Peralatan : 502,3 A
C/T Rasio : 1250/5
Isc Min : 7,85 kA
Isc Max : 9,7 kA

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA
1,05 x 502,3< Iset <1,4 x 502,3
527,5< Iset <703,2
527,5 703,2
<Tap <
1250 1250
0,42<Tap <0,56
Dipilih:
Tap = 0,44
Iset = 550

Time Dial
Dipilih waktu operasi (td) = 0,5 detik

Time Dial=
td x
[( ) ]
I
Is
−1

13,5

6
Time Dial=
0,5 x
[( ) ]
9700
550
−1

13,5
Time Dial=0,62
Instantaneous Pickup
1,6 x FLA< I ≫< 0,8 x Isc min
1,6 x 502,5< I ≫< 0,8 x 7850
803,7< I ≫ < 6280
803,7 6280
< Tap<
1250 1250
0,64 <Tap<5,02
Dipilih:
Tap = 3,6
Iset = 4500
Time Delay = 0,5 s

Rele F50-CB21 & Rele F50-CB13


Model : SEPAM 40 & SEPAM 20
Tipe Kurva : Very Inverse
Peralatan : Trafo 18,4 MVA 20 kV
I FLA Peralatan : 531,2 A
C/T Rasio : 1250/5
Isc Min : 10,07 kA
Isc Max : 12,39 kA

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA
1,05 x 531,2< Iset <1,4 x 531,2
557,7< Iset <743,6
557,7 743,6
<Tap <
1250 1250
0,45<Tap <0,59
Dipilih:

7
Tap = 0,47
Iset = 587,5

Time Dial
Dipilih waktu operasi (td) = 0,7 detik

Time Dial=
td x
[( ) ]
I
Is
−1

13,5

Time Dial=
0,7 x
[( ) ]
12390
587,5
−1

13,5
Time Dial=1,04
Instantaneous Pickup
1,6 x FLA< I ≫< 0,8 x Isc min
1,6 x 531,2< I ≫< 0,8 x 10070
850< I ≫< 8056
850 8056
<Tap <
1250 1250
0,68<Tap <6,44
Dipilih:
Tap = 4,4
Iset = 5500
Time Delay = 0,7 s

Rele F50-CB11
Model : SEPAM 40
Tipe Kurva : Very Inverse
Peralatan : Total Trafo 39,4 MVA 20 kV
I FLA Peralatan : 1137 A

8
C/T Rasio : 1250/5
Isc Min : 10,09 kA
Isc Max : 12,42 kA

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA
1,05 x 1137< Iset <1,4 x 1137
1194< Iset < 1592
1194 1592
<Tap<
1250 1250
0,96<Tap<1,27
Dipilih:
Tap =1
Iset = 1250

Time Dial
Dipilih waktu operasi (td) = 0,9 detik

Time Dial=
td x
[( ) ]
I
Is
−1

13,5

Time Dial=
0,9 x
[( ) ]
12420
1250
−1

13,5
Time Dial=0,596

Instantaneous Pickup
1,6 x FLA< I ≫< 0,8 x Isc min
1,6 x 1137< I ≫ <0,8 x 10090
1820< I ≫ < 8072
1820 8072
<Tap <
1250 1250
1,46<Tap <6,46

9
Dipilih:
Tap = 4,8
Iset = 6000
Time Delay = 0,9 s

3. Tipikal 2
LVCB LVS-51
Model : ABB E3N & ABB SACE PR112
Peralatan : Beban statik 1280 kVA 0,4 kV
I FLA Peralatan : 1850 A
Sensor : 3200 A
Isc Min : 30,07 kA
Isc Max : 34,9 kA
FLA Trafo : 2310 A (0,4 kV)

Long Time
1,05 x FLA < Iset <1,4 x FLA
1,05 x 1850< Iset <1,4 x 1850
1942,5< Iset <2590
1942,5 2590
<Tap <
3200 3200
0,607<Tap <0,809
Dipilih:
Tap = 0,69 (LT Pickup)
Iset = 2200

Short Time
FLA Trafo< I ≫ <0,8 x Isc min
2310< I ≫ < 0,8 x 30070
2310< I ≫ <24056
2310 24056
<Tap <
3200 3200
0,721<Tap <7,52

10
Dipilih:
Tap = 0,94 (ST Pikcup)
Iset = 3000
ST Band = 0,25 s

Rele F50-CB63
Model : SEPAM 20
Tipe Kurva : Very Inverse
Peralatan : Total Trafo 1,6 MVA 20 kV
I FLA Peralatan : 46,2 A
C/T Rasio : 50/5
Isc Max Sekunder : 0,698 kA
Isc Min : 6,08 kA
Isc Max : 7,85 kA

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA
1,05 x 46,2< Iset < 1,4 x 46,2
48,5< Iset < 64,67
48,5 64,67
<Tap<
50 50
0,97<Tap <1,29
Dipilih:
Tap = 1,11
Iset = 55,5

Time Dial
Dipilih waktu operasi (td) = 0,3 detik

Time Dial=
td x
[( ) ]
I
Is
−1

13,5

Time Dial=
0,3 x
[( ) ]
698
55,5
−1

13,5
Time Dial=0,26

11
Instantaneous Pickup
Isc Max Sek < I ≫< 0,8 x Isc min
698< I ≫ < 0,8 x 6080
698< I ≫< 4864
698 4864
<Tap <
50 50
13,96<Tap <97,28

Dipilih:
Tap = 18
Iset = 900
Time Delay = 0,1 s

Rele F50-CB61 & Rele F50-CB34


Model : SEPAM 40 & SEPAM 20
Tipe Kurva : Very Inverse
Peralatan : Trafo 2,4 MVA 20 kV
I FLA Peralatan : 69,3 A
C/T Rasio : 300/5
Isc Min : 6,76 kA
Isc Max : 8,26 kA

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA
1,05 x 69,3< Iset <1,4 x 69,3
72,75< Iset <97
72,75 97
<Tap <
300 300
0,24 <Tap< 0,32
Dipilih:
Tap = 0,28
Iset = 84

Time Dial
Dipilih waktu operasi (td) = 0,3 detik

12
Time Dial=
td x
[( ) ]
I
Is
−1

13,5

Time Dial=
0,3 x
[( ) ]
8260
84
−1

13,5
Time Dial=2,16

Instantaneous Pickup
1,6 x FLA< I ≫< 0,8 x Isc min
1,6 x 69,3< I ≫< 0,8 x 6760
110,85< I ≫<5408
110,85 5408
<Tap <
300 300
0,37<Tap <18,03

Dipilih:
Tap =4
Iset = 1200
Time Delay = 0,3 s

4. Tipikal 3
Rele F50-ASCI
Model : SEPAM 20
Tipe Kurva : Very Inverse
Peralatan : Lumped 375 kVA 6,6 kV
I FLA Peralatan : 32,8 A
C/T Rasio : 50/5
Isc Min : 4,8 kA
Isc Max : 5,97 kA
LRC : 6,5 x 32,8 A = 213,3 A

13
Time Overcurrent Pickup
1,05 x FLA < Iset <1,4 x FLA
1,05 x 32,8< Iset <1,4 x 32,8
34,45< Iset < 45,93
34,45 45,93
<Tap<
50 50
0,69<Tap <0,92
Dipilih:
Tap = 0,79
Iset = 39,5

Time Dial
Dipilih waktu operasi (td) = 0,3 detik

Time Dial=
td x
[( ) ]
I
Is
−1

13,5

Time Dial=
0,3 x
[( ) ]
5970
39,5
−1

13,5
Time Dial=3,34

Instantaneous Pickup
LRC < I ≫< 0,8 x Isc min
213,3< I ≫ < 0,8 x 4800
213,3< I ≫ <3840
213,3 3840
<Tap<
50 50
4,26 <Tap<76,8

14
Dipilih:
Tap = 6,4
Iset = 320
Time Delay = 0,3 s

Rele F50-CB71
Model : SEPAM 40
Tipe Kurva : Very Inverse
Peralatan : Total Trafo 7,5 MVA 6,6 kV
I FLA Peralatan : 656 A
C/T Rasio : 1250/5
Isc Min : 6,02 kA
Isc Max : 7,59 kA

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA
1,05 x 656< Iset < 1,4 x 656
688,9< Iset < 918,5
688,9 918,5
<Tap <
1250 1250
0,55<Tap <0,73
Dipilih:
Tap = 0,63
Iset = 812,5

Time Dial
Dipilih waktu operasi (td) = 0,5 detik

Time Dial=
td x
[( ) ]
I
Is
−1

13,5

Time Dial=
0,5 x
[( ) ]
7590
812,5
−1

13,5
Time Dial=0,3

15
Instantaneous Pickup
1,6 x FLA< I ≫ < 0,8 x Isc min
1,6 x 656< I ≫ <0,8 x 6020
1050< I ≫ < 4816
1050 4816
<Tap <
1250 1250
0,84 <Tap<3,85
Dipilih:
Tap = 1,6
Iset = 2000
Time Delay = 0,5 s

Rele F50-CB37
Model : SEPAM 20
Tipe Kurva : Very Inverse
Peralatan : Total Trafo 7,5 MVA 20 kV
I FLA Peralatan : 216,5 A
C/T Rasio : 300/5
Isc Min : 7,81 kA
Isc Max Lumped : 2,5 kA
Isc Max Primer : 9,64 kA

Time Overcurrent Pickup


1,05 x FLA < Iset <1,4 x FLA
1,05 x 216,5< Iset <1,4 x 216,5
227,4< Iset < 303,1
227,4 303,1
<Tap<
300 300
0,76<Tap <1,01
Dipilih:
Tap = 0,87
Iset = 261

16
Time Dial
Dipilih waktu operasi (td) = 0,7 detik

Time Dial=
td x ([ IsI )−1]
13,5

Time Dial=
0,7 x
[( ) ]
9640
261
−1

13,5
Time Dial=1,86
Instantaneous Pickup
Isc Max Sek < I ≫ < 0,8 x Isc min
2500< I ≫< 0,8 x 7810
2500< I ≫< 6248
2500 6248
<Tap <
300 300
8,33<Tap <20,83
Dipilih:
Tap = 10
Iset = 3000
Time Delay = 0,1 s

Arc Flash Existing


Arus Arus Insiden
FCT
BUS ID Bolted Arcing Energi Kategori
(s)
(kA) (kA) (cal/cm2)
OUT-T31B 7,943 7,74 1,048 10,22 Level 2
INC-MVS3B 7,905 7,7 1,992 19,32 Level 2

17
OUT-T131A 7,94 7,73 3,236 31,52 Level 3
INC-MVS3A 7,9 7,7 3,271 31,70 Level 3
OUT-T13A 7,94 7,73 3,236 31,52 Level 3
MVS3B 7,9 7,7 0,329 3,19 < Level 1
MVS3A 7,9 7,7 0,510 4,94 Level 1

a. Insiden energi
Untuk tegangan antara 1 kV hingga tegangan 15 kV (6kV), persamaan
insiden energi menggunakan persamaan berikut:

( )( )
x
0,983 1,081 t 610
E=C f ( 1,00929 I bf ) ( K 1+ K 2+ 0,0011G)
10
0,2 D

Dengan nilai Cf adalah 1, D adalah 910 mm, K1 adalah -0,555 (dalam


box), K2 adalah -0,113 (sistem ditanahkan), G adalah 153 mm dan x
adalah 0,973, maka didapatkan persamaan:

E=1,083 x I bf 1,0626 x t
Bus OUT-T31B
I bf =7,943 kA ; t=1,048 detik
1,0626
E=1,083 x I bf xt
1,0626
E=1,083 x 7,943 x 1,048
2
E=10,26 cal /cm
b. Flash Protection Boundary

Bus OUT-T31B
E=10,26 cal /cm2

[ ( )( )] [ ( ) ]
1 1
x
t 610 x E x x
DB = 4,184 C f En = 4,184 D
0,2 EB EB

[ ( ) ]
1
10,26 0,973 0,973
D B = 4,184 910 =8293 mm=8,293 m
5

18
Arc Flash Existing
Arus Arus Insiden
FCT
BUS ID Bolted Arcing Energi Kategori
(s)
(kA) (kA) (cal/cm2)
OUT-T31B 7,943 7,74 1,048 10,22 Level 2
INC-MVS3B 7,9 7.698 0.32 3.102 Level 1
OUT-T131A 7,94 7,73 3,236 31,52 Level 3
INC-MVS3A 7,9 7,7 3,271 31,70 Level 3
OUT-T13A 7,94 7,73 3,236 31,52 Level 3
MVS3B 7,9 7,7 0,329 3,19 < Level 1
MVS3A 7,9 7,7 0,510 4,94 Level 1

19