Professional Documents
Culture Documents
Micro Project On
Under Guidance of
Mr. Siddharth Shirke
1.0 Rationale :
A transformer is a passive electrical device that transfers electrical energy from one
electrical circuit to another, or multiple circuits. A varying current in any one coil of the
transformer produces a varying magnetic flux in the transformer's core, which induces a
varying electromotive force across any other coils wound around the same core. Electrical
energy can be transferred between separate coils without a metallic (conductive)
connection between the two circuits. Faraday's law of induction, discovered in 1831,
describes the induced voltage effect in any coil due to a changing magnetic flux encircled by
the coil.
For supplying a load in excess of the rating of an existing transformer, two or more
transformers may be connected in parallel with the existing transformer. The transformers
are connected in parallel when load on one of the transformers is more than its capacity.
The reliability is increased with parallel operation than to have single larger unit. The cost
associated with maintaining the spares is less when two transformers are connected in
parallel.
4.0 Action Plan:
Part B – Plan
7.0 Introduction
It is economical to install numbers of smaller rated transformers in parallel than installing a
bigger rated electrical power transformers.
8.0 : Advantages of Parallel Operation of Transformers :
Generally electrical power transformer gives the maximum efficiency at full load. If we
run numbers of transformers in parallel, we can switch on only those transformers
which will give the total demand by running nearer to its full load rating for that time.
When load increases, we can switch none by one other transformer connected in
parallel to fulfill the total demand. In this way we can run the system with maximum
efficiency.
If numbers of transformers run in parallel, we can shut down any one of them for
maintenance purpose. Other parallel transformers in system will serve the load
without total interruption of power.
If any one of the transformers run in parallel, is tripped due to fault of other parallel
transformers is the system will share the load, hence power supply may not be
interrupted if the shared loads do not make other transformers over loaded.
9.0 Conditions for Parallel Operation of Transformers
When two or more transformers run in parallel, they must satisfy the following conditions for
satisfactory performance. These are the conditions for parallel operation of transformers.
3. Same polarity.
The above said conditions must be strictly followed for parallel operation of transformers but
totally identical percentage impedance of two different transformers is difficult to achieve
practically, that is why the transformers run in parallel may not have exactly same percentage
impedance but the values would be as nearer as possible.
2. Secondary cabling from the transformers to the point of paralleling has approximately
equal
length and characteristics.
4. When the transformers are operated in parallel, the fault current would be very high on
the secondary side. Supposing percentage impedance of one transformer is say 6.25 %, the
short circuit MVA would be 25.6 MVA and short circuit current would be 35 kA.
5. If the transformers are of same rating and same percentage impedance, then the
downstream short circuit current would be 3 times (since 3 transformers are in Parallel)
approximately 105 kA. This means all the devices like ACBs, MCCBs, switch boards should
withstand the short-circuit current of 105 kA. This is the maximum current. This current will
get reduced depending on the location of the switch boards, cables and cable length etc.
However this aspect has to be taken into consideration.
7. The percent impedance of one transformer must be between 92.5% and 107.5% of the
other. Otherwise, circulating currents between the two transformers would be excessive.
The risk of circulating currents running from one transformer to another Transformer.
Circulating currents that diminish load capability and increased losses.
Paralleling transformers reduces the transformer impedance significantly, i.e. the parallel
transformers may have very low impedance, which creates the high short circuit currents.
Therefore, some current limiters are needed, e.g. reactors, fuses, high impedance buses,
etc
It is not a common practice in this industry, since Main-tie-Main is very common in this
industry.
1 ∆∆ ∆∆ or Yy
2 Yy Yy or ∆∆
3 ∆y ∆y or Y∆
4 Y∆ Y∆ or ∆y
Four common methods of connecting three transformers for 3-phase circuits are Δ-Δ, Y-Y,
Y-Δ, and Δ-Y connections.
An advantage of Δ-Δ connection is that if one of the transformers fails or is removed from
the circuit, the remaining two can operate in the open-Δ or V connection. This way, the
bank still delivers 3-phase currents and voltages in their correct phase relationship.
However, the capacity of the bank is reduced to 57.7 % (1 3) of its original value.
In the Y-Y connection, only 57.7% of the line voltage is applied to each winding but full line
current flows in each winding. The Y-Y connection is rarely used.
The Δ-Y connection is used for stepping up voltages since the voltage is increased by the
transformer ratio multiplied by 3.
12.0 Conclusions:
Loading considerations for paralleling transformers are simple unless kVA, percent
impedances, or ratios are different. When paralleled transformer turn ratios and percent
impedances are the same, equal load division will exist on each transformer. When
paralleled transformer kVA ratings are the same, but the percent impedances are
different, then unequal load division will occur.
The same is true for unequal percent impedances and unequal kVA. Circulating currents
only exist if the turn ratios do not match on each transformer. The magnitude of the
circulating currents will also depend on the X/R ratios of the transformers. Delta-delta to
delta-wye transformer paralleling should not be attempted.