STEP1:INSTALL EASY CONNECT SOFTWARE IN PC

STEP2:RIGHT CLICK EASY CONNECT AND RUN AS ADMINISTRATOR

STEP3:ENTER

USER ID: Admin

PASSWORD: Admin

STEP4:PRESS TO LOGIN

STEP5:EASY CONNECT DISPLAY A POPUP FOR RESET PASSWORD

STEP6:CREAT A NEW PASSWORD

USER ID: Admin

OLD PASSWORD: Admin

PASSWORD: S@raja1105

CONFIRM PASSWORD: S@raja1105

STEP7:CLICK SAVE,SUCCESSFULLY UPDATED THE PASSWORD

STEP8:LOGIN EASY CONNECT WITH NEW PASSWORD CREATED BY USER

STEP9:NEW PAGE WILL DISPLAY FOR CONFIGURATION

STEP10:CLICK FILE

STEP11:SELECT NEW

STEP12: RIGHT CLICK CONFIGURATION

i)CLICK OPEN

ii)SELECT .ecc FILE IF EXITS

*NOTE:SKIP STEP8 IF .ecc FILE NOT AVAILABLE

STEP13:CLICK DECVICE

STEP14:SELECT RIGHT SIDE ATTRIBUTE'S OF DEVICE CONFIGURATION

a)DEVICE NAME: SYNC

b)SERIES:SYNC2000: PROTOCOL GATEWAY

c)MODELS: SYNC2000-M2

STEP15:CLICK ADD DEVICE TO CONFIGURATION,A NEW WINDOW WILL CREAT UNDER DEVICE AS
SS1:SYNC2000-M2

STEP16:CLICK PROTOCOL CONFIGURATION

STEP17:SELECT MASTER PROTOCOLS,DISPLAY ATTRIBUTE'S ON RIGHT UNDER PROTOCOL CONFIGURATION


STEP18:ADD DLMS MASTER BY CLICKING TOUCH PAD

STEP19:SELECT CHANNEL-1 DLMS MASTER,UNDER GENERAL ATTRIBUTE'S DISPLAY ON RIGHT

STEP20:MODIFY AS PER DLMS-MASTER METER CONFIGURATION PARAMETERS

EXAMPLE:

CHANNEL TYPE:RS485

CHANNEL MODE:HALF DUPLEX

PORT:COM1

BAUD RATE:9600

DATA BITS:8

STOP BITS: 1

PARITY:NONE

RESPONSE TIMEOUT:10sec

INTERFRAME TIMEOUT:500msec

*NOTE:COM1-COM6 CAN USE AS MASTER OR SLAVE PROTOCOLS

*NOTE:COM-1 TO COM-4 AS RS485,COM-5&COM-6 AS RS232

EXAMPLE1:IF COM1 AS MASTER SELECT COM-2 OR 3,4,5,6, AS SLAVE

EXAMPLE2:IF COM2 AS MASTER SELECT COM-1 OR 3,4,5,6, AS SLAVE

EXAMPLE3:IF COM4 AS MASTER SELECT COM-2 OR 1,3,5,6, AS SLAVE

STEP21:RIGHT CLICK CHANNEL-1 DLMS MASTER,SELECT ADD STATION

STEP22:ADD STATION WILL CREAT AS NODE_1 OR 2,3,4... UNDER CHANNEL-1 DLMS MASTER

STEP23:A NODE_1 OR 2,3,4 DEFINES AS EACH INDIVIDUAL DEVICE OR METER OR RELAY.

STEP24:SELECT NODE_1 OR 2,3,4...,DISPLAY ATTRIBUTE'S ON RIGHT

STEP25:IN NODE,SOME PARAMETERS WERE UNIQUE WHICH WERE DIFFER BY DEVICE BRAND(METER OR
RELAY)

a)HDLC ADDRESSING SCHEME: 4

There 1byte,2byte,4byte,In L&T ERP-300,SECURE P-300,Landys Gyr+ E650,We are using 4BYTE

b)PHYSICAL ID:256

Initially any DLMS Meter ID will be 256

c)CLIENT ID:32

It was used to read data, which was defined as per Meter Manufacturer

1.L&T ERP-300:32

2.SECURE P-300:32

3.Landys Gyr+ E650:48


d)APPLICATION CONTEXT:LN

It was defined by the Meter Manufacturer, whether device supports Short Name(SN) or Long Name(LN),for the following
models(L&T ERP-300,SECURE P-300,Landys Gyr+ E650) it was Long name(LN).

*NOTE: After confirming Meter in DLMS, need to identify it supports Long Name or Short Name as per supported Application
context OBIS codes(address registers) will vary

e)AUTHENTICATION LEVEL:LOW

It was defined by Meter manufacturer in which authentication level meter can access to read the Data, As per the following
Models it was defined

1.L&T ERP-300:LOW

2.SECURE P-300:LOW

3.Landys Gyr+ E650:HIGH

f)PASSWORD

It was defined by Meter manufacturer in which Password meter can access to read the Data, As per the following Models it was
defined

1.L&T ERP-300:lnt1

2.SECURE P-300:ABCD0001

3.Landys Gyr+ E650:2222222222222222

STEP26:Right Click on node add profile or import profile if existing.

STEP27:Click on ADD Row define OBIS Code address need to read data from meter and Parameters need to define

1.Interface Class :Register

2.DATA TYPE :ANALOG INPUT

3.Attribute/Method index :value(Attribute-2)

4.Periodic Scale(DD:h:m:s ) :0:0:0:5 or 0:0:0:10

5.Manual scale :1 or 0.1(min) or 0.01 or 0.000001(max)

6.Description :KVA or KW or Kwh or Frequency or Voltage or Current


STEP27:Save and close, continue above Step22 for adding required no of OBIS CODES to read data from meter ,Go through for
Below mentioned OBIS CODES.

In profile we need to add OBIS codes, it was defined in below details:

1.R-PHASE CURRENT :1.0.31.7.0.255

2.Y-PHASE CURRENT :1.0.51.7.0.255

3.B-PHASE CURRENT :1.0.71.7.0.255

4.R-PHASE VOLTAGE :1.0.32.7.0.255

5.Y-PHASE VOLTAGE :1.0.52.7.0.255

6.B-PHASE VOLTAGE :1.0.72.7.0.255

7.REAL POWER(KW) :1.0.01.7.0.255

8.REACTIVE POWER(KVAR) :1.0.03.7.0.255

9.ENERGY(KWH) :1.0.01.8.0.255

10.FREQUENCY :1.0.14.7.0.255

11.POWER FACTOR :1.0.13.7.0.255

STEP28: DLMS Configuration made for meter to read data, but for reading data in RTU(C264) OR FRTU We need to follow
below steps.

STEP29:CLICK PROTOCOL CONFIGURATION

STEP30:SELECT SLAVE PROTOCOLS,DISPLAY ATTRIBUTE'S ON RIGHT UNDER PROTOCOL CONFIGURATION

STEP31:ADD MODBUS RTU SLAVE BY CLICKING TOUCH PAD

STEP32:SELECT CHANNEL-2 MODBUS RTU SLAVE,UNDER GENERAL ATTRIBUTE'S DISPLAY ON RIGHT

STEP33:MODIFY AS PER MODBUS RTU SLAVE CONFIGURATION PARAMETERS

EXAMPLE:

CHANNEL TYPE:RS485

CHANNEL MODE:HALF DUPLEX

PORT:COM2 or COM3

BAUD RATE:9600

DATA BITS:8

STOP BITS: 1

PARITY:NONE

RESPONSE TIMEOUT:10sec

INTERFRAME TIMEOUT:500msec

STEP34:RIGHT CLICK CHANNEL-2 MODBUS RTU SLAVE,SELECT ADD STATION

STEP35:ADD STATION WILL CREAT AS NODE_1 OR 2,3,4... UNDER CHANNEL CHANNEL-2 MODBUS RTU SLAVE

STEP36:A NODE_1 OR 2,3,4 DEFINES AS MODBUS ADDRESS MADE FOR NO OF METERS LOOPED FOR COM1 or
COM2 OF CHANNEL-1 DLMS MASTER .
STEP37:GO TO INDIVIDUAL PROFILE OF NODE IN CHANNEL-1 DLMS MASTER

STEP38:CHOOSE CHANNEL-1 DLMS MASTER_NODE_1 FROM TOP SIDE DROP DOWN BOX, BY DRAGING MOUSE
SELECT ALL ADDED OBIS CODES.

STEP39:CHOOSE CHANNEL-2 MODBUS RTU SLAVE_NODE_2 or 3 or 4 FROM BOTTOM SIDE DROP DOWN BOX.

STEP40:CLICK ON AUTO MAP

STEP41:A NEW TAB WILL OPEN SELECT DESTINATION TYPE AS AI,READ HOLDING REGISTER FLOAT(lsw_msw).

STEP42:START ADDRESS DEFINDED FROM 0 OR 100 OR 200 OR 300 WHICH THE ADDRESS NEED TO ASSISGN IN
RTU(C264) OR FRTU.

STEP43:OK

STEP44:SAVE

STEP45:CLICK DOWNLOAD( ) CONFIGURATION TO DEVICE

STEP46:CLICK DIAGNOSTICS AND SELECT TRAFFIC MONITOR.

STEP47:A WINDOW OPEN UNCHECK CHANNEL-1 AND SELECT CHANNEL-1 MASTER FROM DROP DOWN BOX.

STEP48:START LOG

STEP49:FOR MONITORING DATA FROM METER, CLICK DIAGNOSTICS AND SELECT SYNC DB MONITOR.

STEP50:CLICK ON START

PREPARED BY

S.RAJA