Professional Documents
Culture Documents
STATUS
SL. NO. DESCRIPTION DRG. NO. REV. No. DATE
C REFERENCE APPROVAL ASBUILT C
TABLE OF CONTENTS
SL.No. DRAWING No. SHEET No. DESCRIPTION
A A
11 518-01-C 3 OF 4 PANEL AUX. CIRCUIT,DC CONTROL CIRCUIT AND POTENTIAL FREE CONTACTS.
C C
H1H2H3H4
Bolted
2000
1500
FRONT
2000
DANGER
2115
2115
2115
DANGER
Counter Sunk
Screw Type Both Sides
B B
Hinged Bolted
1F1
LV
MIN 1000mm
500
WALL
15mm, Anti
Vibration pad
15
FFL
1F2 15
100
100
100
100mm BASE 100mm BASE 100mm BASE
15 750 15 1200 32
750 32
FOUNDATION PLAN (GP,CGP AT BOTTOM)
100 550 100 Ø13.5 HOLES
FOR FOUNDATION
C C
RUBBER GROMMET
H1 AC SUPPLY ON
GP(Al) H2 DC SUPPLY ON
H3 NIS ON
H4 NIS OFF
NGR
TH
NGR
A A
PIL
NIS
NIS
1500
FRONT
CT-1(R/Y/B)
1500
2000
2000
2000
DLS2 NGT CT-1(R/Y/B)
2115
2115
P1
NGT
B P2 B
ADDITIONAL FRP
SUPPORT FOR CT
CABLE TRUFF
PIL DLS
I/C
560
500
500
NGT
CABLE TRUFF
WALL EARTHING
6.6kV
2Rx1Cx300 Sq.mm/Ph
CHAMBER
100
100
RATING NAME PLATE DETAILS
750 750 1200
Refer Note. 1
For NGT EARTHING
C Refer Note. 1 C
NOTE. 1
Remove & keep loose if fouling with Base frame during dispatch.
D LOTUS POWERGEAR PVT, LTD. D
2019.J3520.01-02.GA
KS M/s. B FOURESS (P) LTD. 518 R3
AJS NEUTRAL GROUNDING PANEL(UNIT - 1 & 2) DORDI-1 HEP 2 13
SH 6.3kV, 2X6MW
GENERAL ARRANGEMENT DRAWING 518-01-GA
03.10.19 HORIZONTAL FRANCIS
1 2 3 4 5 6
1 2 3 4 5 6
A A
1 NEUTRAL GROUND TRANSFORMER SHALL BE FIXED WITH PROPER SUPPORT.
2 SOLID BUSBAR BETWEEN NIS TO NGT AT THE NGT CONNECTION END APPROXIMATE 1 FEET SHALL BE PROVIDED.
3 CROSS SECTIONAL AREA OF CABLE BETWEEN NGT SECONDARY AND NG-LR SHALL BE SUITABLE FOR NGT SECONDARY RATED CURRENT.
7a PROPER BUSBAR TERMINATION SHALL BE PROVIDED DEPENDING ON THE NUMBER OF RUNS OF CABLE. IF THREE OR FOUR RUNS BUSBAR SHALL BE SUITABLY PROVIDED.
7b SUITABLE HOLE SIZE ON BUSBAR SHALL BE PROVIDED FOR TERMINATION OF CABLE DEPENDING ON THE SIZE OF CABLE.
11 BI-METAL STRIPS TO BE PROVIDED IN CASE OF COPPER/ALLUMINIUM BUS BAR JOINTS / ANY EQUIPMENTS.
12 ADDITIONAL INSULATOR SUPPORT TO BE PROVIDED IF THE NUMBER OF BUSBAR ARE MORE THAN 2 RUNS.
13 CTTB SHALL BE DISCONNECTING TYPE TB SUITABLE FOR RING TYPE LUGS. FTP SUITABLE FOR 6 Sq.mm CABLE WITH END PLATES.
GLAND PLATE HOLE DIMENSIONS WITH RESPECT TO BUS BAR (PERPENDICULAR DROP) TO BE INDICATED IN THE DRAWINGS. (ENSURE THE GLAND PLATE SIZE FOR
14 ACCESSING THE CABLE ENTRY FROM THE BUS BAR TO GLAND PLATE WITHOUT BENDING)
15 GLAND PLATE DETAILS WITH NUMBER OF PUNCHING, AFTER PUNCHING FIX THE RUBBER GROMMET TO AVOID FOREIGN MATERIAL ENTRY.
20 ALL SCHEME RELATED EQUIPMENTS SHALL BE NUMBERED AS PER THE DETAILED DRAWING.
21 NGT EARTHING GLAND PLATE SHALL BE SEAL OF BUSHING (EPOXY BASED BUSHING)
2019.J3520.01-02.GA
KS M/s. B FOURESS (P) LTD. 518 R3
AJS NEUTRAL GROUNDING PANEL(UNIT - 1 & 2) DORDI-1 HEP 3 13
SH 6.3kV, 2X6MW
SPECIFIC GENERAL NOTES 518-01-GA
03.10.19 HORIZONTAL FRANCIS
1 2 3 4 5 6
1 2 3 4 5 6
2019.J3520.01-02.GA
KS M/s. B FOURESS (P) LTD. 518 R3
AJS NEUTRAL GROUNDING PANEL(UNIT - 1 & 2) DORDI-1 HEP 4 13
SH 6.3kV, 2X6MW
GENERAL NOTES 518-01-GA
03.10.19 HORIZONTAL FRANCIS
1 2 3 4 5 6
1 2 3 4 5 6
TO CT LAVT PANEL-1
SYNC. GEN-1
HORIZONTAL FRANCIS
3
A A
TURBINE
6000kW,+10% COL
G 6.3kV,0.85PF, 750RPM
50Hz SYN. GEN
3
2RX1CX300Sq.mm/Ph
BOTTOM
ENTRY XLPE, Ar. Al. CABLE(UE)
TGRMP-1
NGT PANEL-1
2RX60X10mm/Ph
Al. BUSBAR
B B
P2 2S2
1-CT-1
6.3kV,800/1-1A
CORE-2: CL:0.5, 10VA
2S1 1CTTB2 TB
ISF<5 METERING(MDM)
1S2
CORE-1:CL:PS,Vkp>=325V
POWER FLOW Imag@Vk/2<=15mA,RCT-3Ohms
FOR PROTECTION
DIRECTION 1S1 1CTTB1 TB TO GEN. PROTECTION
P1
NUMERICAL RELAY(GPR)
STAR POINT
1RX30X5mm/Ne
C Al. BUSBAR C
1-NIS-1
6.3kV, 100A, SP
25kA FOR 1Sec
MANUAL OPTD
ISOLATOR OFF LOAD
1-NGT-1
1 3 6sq.mm 1PTB TB
x1
TO GEN. PROTECTION
1-NG-LR NUMRICAL RELAY
2 4 x2 1PTB TB (59GN/27TN)(GPR)
110V, 0.3519Ohms
6.3kV/110V,2kVA
POWER RATING-11.46kW
CONTI.
GENERATOR NEUTRAL
D VENDOR DETAILS: LOTUS POWERGEAR PVT, LTD. D
EARTHING
VENDOR DRG NO.: J3520.01-02.SLD
R3 ASBUILT RM 05.03.20 Approved KS Equipment: Customer M/s. DORDI KHOLA JAL BIDYUT CO. LTD. PROJECT CODE: 518 REV No: R3
R2 REVISED AS PER CC DTD-6.12.19 PRA 07.11.19 Checked AJS NEUTRAL GROUNDING TRANSFORMER PANEL Project DORDI-1 HEP THIS SHEET: 1 TOTAL PAGE: 13
R1 REVISED AS PER CC DTD-17.10.19 PRA 25.10.19 Drawn PRA Title:
B FOURESS (P) LIMITED
Rating 6.3kV, 2X6MW Drg No:
SINGLE LINE DIAGRAM 518-01-SLD
REV. REVISION NOTES Prep. Date. Date: 14.09.19 Bengaluru Turbine Type HORIZONTAL FRANCIS
1 2 3 4 5 6
1 2 3 4 5 6
TO CT LAVT PANEL-2
SYNC. GEN-2
HORIZONTAL FRANCIS
3
A A
TURBINE
6000kW,+10% COL
G 6.3kV,0.85PF, 750RPM
50Hz SYN. GEN
3
2RX1CX300Sq.mm/Ph
BOTTOM XLPE, Ar. Al. CABLE(UE)
ENTRY
TGRMP-2
NGT PANEL-2
2RX60X10mm/Ph
Al. BUSBAR
B B
P2 2S2
2-CT-1
6.3kV,800/1-1A
CORE-2: CL:0.5, 10VA
2S1 2CTTB2 TB
ISF<5 METERING(MDM)
1S2
CORE-1:CL:PS,Vkp>=325V
Imag@Vk/2<=15mA,RCT-3Ohms
FOR PROTECTION
P1 1S1 2CTTB1 TB TO GEN. PROTECTION
NUMERICAL RELAY(GPR)
POWER FLOW
DIRECTION
STAR POINT
1RX30X5mm/Ne
C Al. BUSBAR C
2-NIS-1
6.3kV, 100A, SP
25kA FOR 1Sec
MANUAL OPTD
ISOLATOR OFF LOAD
2-NGT-1 6sq.mm
1 3 2PTB TB
x1
TO GEN. PROTECTION
2-NG-LR NUMRICAL RELAY
2 4 x2 2PTB TB (59GN/27TN)(GPR)
110V, 0.3519Ohms
6.3kV/110V,2kVA
POWER RATING-11.46kW
CONTI.
GENERATOR NEUTRAL
D VENDOR DETAILS: LOTUS POWERGEAR PVT, LTD. D
EARTHING
VENDOR DRG NO.: J3520.01-02.SLD
R3 ASBUILT RM 05.03.20 Approved KS Equipment: Customer M/s. DORDI KHOLA JAL BIDYUT CO. LTD. PROJECT CODE: 518 REV No: R3
R2 REVISED AS PER CC DTD-6.12.19 PRA 07.11.19 Checked AJS NEUTRAL GROUNDING TRANSFORMER PANEL Project DORDI-1 HEP THIS SHEET: 2 TOTAL PAGE: 13
R1 REVISED AS PER CC DTD-17.10.19 PRA 25.10.19 Drawn PRA Title:
B FOURESS (P) LIMITED
Rating 6.3kV, 2X6MW Drg No:
SINGLE LINE DIAGRAM 518-01-SLD
REV. REVISION NOTES Prep. Date. Date: 14.09.19 Bengaluru Turbine Type HORIZONTAL FRANCIS
1 2 3 4 5 6
1 2 3 4 5 6
R Y B **NOTE:
1. PREFIX '1' TO BE ADDED FOR COMPONENTS & FERRULES FOR UNIT-1
2. PREFIX '2' TO BE ADDED FOR COMPONENTS & FERRULES FOR UNIT-2
+SYNC.GEN-*
A A
G
2RX1CX300Sq.mm/Ph
XLPE, Ar. Al. CABLE(UE)
NGT PANEL-*
D81 +TGRMP-*
1
2
D21
B B
4
P2 D41
D61 6
D20 1 TB
A71
A11 2
A31 4
C C
A51 6
STAR POINT
D VENDOR DETAILS: LOTUS POWERGEAR PVT, LTD. D
T
2.2:B VENDOR DRG NO.: J3520.01-02.SCH
R3 ASBUILT RM 05.03.20 Approved KS Equipment: Customer M/s. DORDI KHOLA JAL BIDYUT CO. LTD. PROJECT CODE: 518 REV No: R3
R2 REVISED AS PER CC DTD-6.12.19 PRA 07.11.19 Checked AJS NEUTRAL GROUNDING TRANSFORMER PANEL Project DORDI-1 HEP THIS SHEET: 1 TOTAL PAGE: 13
R1 REVISED AS PER CC DTD-17.10.19 PRA 25.10.19 Drawn PRA Title:
B FOURESS (P) LIMITED
Rating 6.3kV, 2X6MW Drg No:
POWER CIRCUIT. 518-01-C
REV. REVISION NOTES Prep. Date. Date: 14.09.19 Bengaluru Turbine Type HORIZONTAL FRANCIS
1 2 3 4 5 6
1 2 3 4 5 6
**NOTE:
1. PREFIX '1' TO BE ADDED FOR COMPONENTS & FERRULES FOR UNIT-1
2. PREFIX '2' TO BE ADDED FOR COMPONENTS & FERRULES FOR UNIT-2
A A
T
1.2:D
11 11 13 33
*-NIS-1
6.3kV, 100A, SP 12 12 14 34
25kA FOR 1Sec
/3.3:D
/3.5:D
/3.3:D
/3.5:C
B MANUAL OPTD B
ISOLATOR
*-NGT-1
E70 PTTB1 TB
1 3
1 1
x1 TO GEN. PROTECTION
*-LR-1 NUMRICAL RELAY
(59GN/27TN)(GPR)
2 4 x2
E71 PTTB1 TB
110V, 0.3519Ohms 2 2
6.3kV/110V,2kVA
POWER RATING-11.46kW
CONTI.
C C
1
GEN. NEUTRAL
EARTHING
*NOTE:
PANEL SPACE HEATER & ILLUMINATION LAMP CIRCUIT 1. PREFIX '1' TO BE ADDED FOR COMPONENTS & FERRULES FOR UNIT-1
2. PREFIX '2' TO BE ADDED FOR COMPONENTS & FERRULES FOR UNIT-2
*-F1
A +LTAC A
TB ACTB H01 1 2
H03 H03 H03 H03
230V AC, 50Hz 1 1
SUPPLY FROM
LTAC PANEL 1 H03
H02 *-F2
3 4
6A, SP 2
2 2
10A,DP
*F4 H05 *DLS1 21 *DLS2 21 *DLS3 21
*SK
TO OPU TANK
HEATER-1 TB ACTB H1A 1 2 22 22 22
3 3 21
H08 H08
SW
H2A *TH1
3 4
22 H07
1
4 4 16A,DP MCB
*F5 H06 PE
H1B x1 x1
TO LOS TANK TB ACTB 1 2 x1
x1 2
HEATER-1 5 5 *PIL1 *PIL2
*H1 *PSH1 (LED) (LED)
H2B RED x2
B 3 4
H04 x2 B
6 6 x2H04 x2H04
16A DP MCB
-*-NIS-1
J05 J06 12 11 U03
3
/2.2:B NIS OPEN
U04 STATUS(SPARE)
4
x1 x1 x1
J04 J04
D DC SUPPLY ON NIS ON NIS OFF VENDOR DETAILS: LOTUS POWERGEAR PVT, LTD. D
Terminal Diagram
ACTB -*-CT-1(R/Y/B):2S2 D61 6 CT SEC:1A FOR GEN. PROT. RELAY
PTTB1
CTTB1
B B
External Target wiring jumper Function text jumper wiring Internal Target
External Target wiring jumper Function text jumper wiring Internal Target
-*-NGT-1:3 E70 1 NGT SEC:110V FOR NUMRICAL RELAY (59GN/27TN)(GPR)
-*-CT-1(R/Y/B):1S1 A10 1 CT SEC:1A FOR GEN. PROT. RELAY
-*-NGT-1:4 E71 2 NGT SEC:110V FOR NUMRICAL RELAY (59GN/27TN)(GPR)
-*-CT-1(R/Y/B):1S2 A11 2 CT SEC:1A FOR GEN. PROT. RELAY
External Target wiring jumper Function text jumper wiring Internal Target
Neutral Grounding Resin cast, Impedence-4%, Single Phase, Resin cast 6.3kV/110V, 50Hz, Output: Z30347,
7 *-NGT-1 Instrans 1 2
Transformer 2kVA, Insulation Class F(Temp rise limit to class-B), BIL : 7.2/20/60kV Z30348
Voltage: 110V, 50Hz, Resistance: 0.3519Ω @ 20°, Heavy duty, Non magnetic,
2019-20/J276/P-
8 Loading Resistor *-NG-LR Ohmark Stainless Steel Power rating Continuous, 11.46kW for Cont. On the LV Side of the 1 2
14664,14665
NGT
9 Miniature circuit breaker *-F1 ABB 10kA, 'C' curve, 10A, DP, 230V AC, 50Hz 1 2
10 Miniature circuit breaker *-F2 ABB 10kA, 'C' curve, 6A, SP, 230V AC, 50Hz 1 2
11 Miniature circuit breaker *-F3 ABB 10kA, 'C' curve, 6A, DP, 110V DC 1 2
12 Miniature circuit breaker *-F4,F5 ABB 10kA, 'C' curve, 16A, DP, 230V AC, 50Hz 2 4
13 Terminal Block ACTB, DCTB Elmex Stud type TB, FTP suitable for upto 10sq.mm cable with end plates KAT M4 6 12
14 Terminal Block CTTB1-2,PTB1 Elmex Disconnecting type TB, FTP suitable for upto 6sq.mm cable with end plates KLTD M4 14 28
15 Terminal Block X1 Elmex Control TB, FTP suitable for upto 2.5sq.mm cable with end plates KUT 2.5 4 8
PANEL ACCESSORIES
1 SP. Heater *PSH1 KWK Panel space Heater, 230V AC, 50Hz, 80 Watts 1 2
2 Thermostat *TH1 Alfa Electric Thermostat range 0-60 Deg C with 1NC, 230V AC 1 2
3 Door Limit Switch *DLS1,2,3 Siemens Door limit switch with 1NO+1NC contacts 3 6
4 Panel Lamp *PIL1,2 Philips Panel llumination lamp, LED type, 230V AC, 50Hz,4w 2 4
5 Service Socket *SK ROMA 5A, 3P, Universal type socket with built-in switch, 230V AC 1 2