AC-3
380 V 400 V Ie A 32
AC-1
Open
at 40 °C Ith =Ie A 45
enclosed Ith A 36
enclosed Ith A 90
AC-3
220 V 230 V P kW 10
380 V 400 V P kW 15
660 V 690 V P kW 17
AC-4
220 V 230 V P kW 4
380 V 400 V P kW 7
660 V 690 V P kW 10
Contacts
Contact sequence
Frame size 2
Technical data
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
DC operated Operations x 10
6 10
Ambient temperature
Enclosed °C - 25 - 40
Storage °C - 40 - 80
Mounting position
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 10
Auxiliary contacts
N/O contact g 7
N/C contact g 5
Half-sinusoidal shock, 10 ms
Main contacts
Auxiliary contacts
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Weight
DC operated kg 0.534
Solid mm
2 1 x (0.75 - 16)
2 x (0.75 - 10)
Stranded mm
2 1 x 16
Stripping length mm 10
Terminal screw M5
Tool
Stripping length mm 10
Tool
Up to 690 V A 384
Breaking capacity
500 V A 320
Short-circuit rating
Open
at 40 °C Ith =Ie A 45
at 50 °C Ith =Ie A 43
at 55 °C Ith =Ie A 42
at 60 °C Ith =Ie A 40
enclosed Ith A 36
enclosed Ith A 90
AC-3
220 V 230 V Ie A 32
240 V Ie A 32
380 V 400 V Ie A 32
440V Ie A 32
500 V Ie A 32
660 V 690 V Ie A 18
220 V 230 V P kW 10
240V P kW 11
380 V 400 V P kW 15
415 V P kW 19
440 V P kW 20
500 V P kW 23
660 V 690 V P kW 17
AC-4
220 V 230 V Ie A 15
240 V Ie A 15
380 V 400 V Ie A 15
415 V Ie A 15
440 V Ie A 15
500 V Ie A 15
660 V 690 V Ie A 12
220 V 230 V P kW 4
240 V P kW 4.5
380 V 400 V P kW 7
415 V P kW 7.5
440 V P kW 8
500 V P kW 9
660 V 690 V P kW 10
DC
Rated operational current, open
DC-1
60 V Ie A 40
110 V Ie A 40
220 V Ie A 40
DC operated Pick-up W 12
Main contacts
DC operated ms
Closing delay ms
Closing delay ms 47
Opening delay ms 30
Arcing time ms 10
Electromagnetic compatibility (EMC)
Emitted interference according to EN 60947-1
Three-phase
200 V HP 10
208 V
230 V HP 10
240 V
460 V HP 20
480 V
575 V HP 25
600 V
Single-phase
115 V HP 2
120 V
230 V HP 5
240 V
General use A 40
Auxiliary contacts
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
AC A 10
DC V 250
DC A 1
Basic Rating
SCCR kA 5
max. CB A 125
max. CB A 50/32
max. CB A 50/32
Elevator Control
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching (ecl@ss10.0.1-27-37-10-03 [AAB718015])
Modular version No
Approvals
Product Standards IEC/EN 60947-4-1; UL 60947-4-1; CSA - C22.2 No. 60947-4-1-14; CE marking
1: Overload relay
2: Suppressor
3: Auxiliary contact modules
X-Start - Modern Switching Installations Efficiently Fitted and Wired Securely http://www.moeller.net/binary/ver_techpapers/ver938en.pdf
Effect of the Cabel Capacitance of Long Control Cables on the Actuation of http://www.moeller.net/binary/ver_techpapers/ver949en.pdf
Contactors
Standard Compliant and Functionally Safe Engineering Design with Mechanical http://www.moeller.net/binary/ver_techpapers/ver956en.pdf
Auxiliary Contacts
Contactor, 3 pole, 380 V 400 V 7.5 kW, 1 NC, RDC 24: 24 - 27 V DC, DC
operation, Screw terminals
AC-3
380 V 400 V Ie A 18
AC-1
Open
at 40 °C Ith =Ie A 40
enclosed Ith A 32
open Ith A 88
enclosed Ith A 80
AC-3
220 V 230 V P kW 5
660 V 690 V P kW 11
AC-4
Contacts
Contact sequence
Frame size 2
Technical data
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
DC operated Operations x 10
6 10
Ambient temperature
Enclosed °C - 25 - 40
Storage °C - 40 - 80
Mounting position
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 10
Auxiliary contacts
N/O contact g 7
N/C contact g 5
Half-sinusoidal shock, 10 ms
Main contacts
Auxiliary contacts
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Weight
DC operated kg 0.53
Solid mm
2 1 x (0.75 - 16)
2 x (0.75 - 10)
Stranded mm
2 1 x 16
Stripping length mm 10
Terminal screw M5
Tool
Stripping length mm 10
Tool
Up to 690 V A 238
Breaking capacity
500 V A 170
Short-circuit rating
Open
at 40 °C Ith =Ie A 40
at 50 °C Ith =Ie A 38
at 55 °C Ith =Ie A 37
at 60 °C Ith =Ie A 35
enclosed Ith A 32
open Ith A 88
enclosed Ith A 80
AC-3
220 V 230 V Ie A 18
240 V Ie A 18
380 V 400 V Ie A 18
440V Ie A 18
500 V Ie A 18
660 V 690 V Ie A 12
220 V 230 V P kW 5
240V P kW 5.5
415 V P kW 10
440 V P kW 10.5
500 V P kW 12
660 V 690 V P kW 11
AC-4
220 V 230 V Ie A 10
240 V Ie A 10
380 V 400 V Ie A 10
415 V Ie A 10
440 V Ie A 10
500 V Ie A 10
660 V 690 V Ie A 8
240 V P kW 3
415 V P kW 5
440 V P kW 5.5
500 V P kW 6
DC-1
60 V Ie A 35
110 V Ie A 35
220 V Ie A 35
DC operated Pick-up W 12
Main contacts
DC operated ms
Closing delay ms
Closing delay ms 47
Opening delay ms 30
Arcing time ms 10
Electromagnetic compatibility (EMC)
Emitted interference according to EN 60947-1
Three-phase
200 V HP 5
208 V
230 V HP 5
240 V
460 V HP 10
480 V
575 V HP 15
600 V
Single-phase
115 V HP 2
120 V
230 V HP 3
240 V
General use A 40
Auxiliary contacts
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
AC A 10
DC V 250
DC A 1
Basic Rating
SCCR kA 5
max. CB A 125
max. CB A 50/32
max. CB A 50/32
Elevator Control
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching (ecl@ss10.0.1-27-37-10-03 [AAB718015])
Modular version No
Approvals
Product Standards IEC/EN 60947-4-1; UL 60947-4-1; CSA - C22.2 No. 60947-4-1-14; CE marking
1: Overload relay
2: Suppressor
3: Auxiliary contact modules
X-Start - Modern Switching Installations Efficiently Fitted and Wired Securely http://www.moeller.net/binary/ver_techpapers/ver938en.pdf
Effect of the Cabel Capacitance of Long Control Cables on the Actuation of http://www.moeller.net/binary/ver_techpapers/ver949en.pdf
Contactors
Standard Compliant and Functionally Safe Engineering Design with Mechanical http://www.moeller.net/binary/ver_techpapers/ver956en.pdf
Auxiliary Contacts
Referencia PKZM0-32/AK
Catalog No. 156398
Alternate Catalog XTPR032BC1
No.
Delivery program
Product range PKZM0 motor protective circuit-breakers up to 32 A
Contact sequence
AC-3
440 V P kW 15
500 V P kW 22
660 V 690 V P kW 30
Setting range
Overload releases Ir A 25 - 32
short-circuit release
Technical data
General
Standards IEC/EN 60947, VDE 0660,UL, CSA
Ambient temperature
Storage °C - 40 - 80
Enclosed °C - 25 - 40
Mounting position
Device IP20
Terminations IP00
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Screw terminals
Solid mm
2 1 x (1 - 6)
2 x (1 - 6)
Stripping length mm 10
Rated frequency f Hz 40 - 60
Short-circuit rating
DC
Short-circuit rating kA 40
Notes up to 250 V
Operating range °C - 25 … 55
Three-phase
200 V HP 7.5
208 V
230 V HP 10
240 V
460 V HP 20
480 V
575 V HP 25
600 V
Single-phase
240 V kA 18
480 Y / 277 V kA 18
SCCR (fuse) kA 10
SCCR (CB) kA 10
max. CB A 125
10.2.2 Resistencia a la corrosión Cumple con los requisitos de la norma del producto.
10.2.3.1 Verificación de la estabilidad térmica de los armarios Cumple con los requisitos de la norma del producto.
10.2.3.2 Verificación de la resistencia de los materiales aislantes en Cumple con los requisitos de la norma del producto.
condiciones de calor normales
10.2.3.3. Verificación de la resistencia de los materiales aislantes al calor Cumple con los requisitos de la norma del producto.
excesivo y al fuego debido a los efectos eléctricos internos
10.2.4 Resistencia a radiación ultravioleta (UV) Cumple con los requisitos de la norma del producto.
10.2.5 Elevación No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.2.6 Impacto mecánico No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.3 Grado de protección de montajes No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.4 Distancias de separación y fuga Cumple con los requisitos de la norma del producto.
10.5 Protección contra descargas eléctricas No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.6 Incorporación de dispositivos y componentes de conmutación No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.10 Aumento de la temperatura El cuadrista es responsable del cálculo del aumento de la temperatura. Eaton
proporcionará datos de disipación de calor para los dispositivos.
10.11 Resistencia a los cortocircuitos Es responsabilidad del cuadrista. Deben tenerse en cuenta las especificaciones de
la aparamenta.
10.12 Compatibilidad electromagnética Es responsabilidad del cuadrista. Deben tenerse en cuenta las especificaciones de
la aparamenta.
10.13 Función mecánica El dispositivo cumple los requisitos, siempre que se observe la información del
folleto de instrucciones (IL).
Tecnología electrónica, de automatización y de mando de procesos / Tecnología de conmutación de baja tensión / Interruptor de potencia, interruptor de potencia (baja tensión) / Interruptor de
potencia para protección de motor (ecl@ss10.0.1-27-37-04-01 [AGZ529016])
Liberación del corto circuito sin retardo del intervalo de ajuste Ampere 496 - 496
Número de polos 3
Altura Millimeter92.4
Anchura Millimeter45
Profundidad Millimeter93.2
Approvals
Product Standards IEC/EN 60947-4-1; UL 60947-4-1; CSA - C22.2 No. 60947-4-1-14; CE marking
Suitable for Branch circuit: Manual type E if used with terminal, or suitable for group
installations
Motor starters and "Special Purpose Ratings" for the North American market http://www.eaton.eu/ecm/groups/public/@pub/@europe/@electrical/documents/content/pct_3258146.pdf
Delivery program
Product range Accessories
Contacts
Contact diagram
Contact sequence
Technical data
Auxiliary contacts
Rated impulse withstand voltage Uimp V AC 6000
Ue V DC 250
AC-15
380 - 415 V Ie A 2
440 V 500 V Ie A 1
24 V Ie A 2
60 V Ie A 1
110 V Ie A 0.5
220 V Ie A 0.25
Lifespan S
Fuse A gG/gL 10
Terminal capacities
Solid or flexible conductor, with ferrule mm
2 0,75 - 2,5
AC operated A600
DC operated Q300
General Use
AC V 600
AC A 5
DC V 250
DC A 1
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Auxiliary switch block
(ecl@ss10.0.1-27-37-13-02 [AKN342013])
Approvals
Product Standards UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
Characteristics
1: Motor-protective circuit-breakers
2: Standard auxiliary contact