Professional Documents
Culture Documents
net/publication/263219968
CITATIONS READS
11 5,721
2 authors:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Rob J. Smith on 13 October 2017.
Summary
In the design of tall buildings, the dynamic response in wind is a dominant consideration. The
damping of the building has a major influence on the dynamic response, and the structural engineer
has to make an informed decision as to an appropriate value to assume for design.
This paper reviews available measured data on the damping of tall buildings and compares against
values in common usage. It is found that damping ratios commonly assumed in design are
inappropriate and unconservative.
The paper describes the consequences of over-estimation of damping at the design stage, and
illustrates the benefits of incorporating robust supplementary damping systems to reduce dynamic
response, to reduce uncertainty and to improve economy in design.
Keywords: damping; wind; seismic; dampers; high-rise buildings; risk; occupant comfort.
1. Introduction
The predicted dynamic response of tall buildings in wind is particularly sensitive to assumptions
about the intrinsic damping made by the structural engineer. Current practice uses rules of thumb
based on limited measurements, most of these made on relatively low rise (70-100m) buildings by
spectral methods at low levels of response.
This paper reviews good quality measurements, recently published in a variety of journals, of the
intrinsic damping in buildings up to 450m in height. These are compared to values in common
practice for use in the design of buildings. It is evident that current practice overestimates the
damping in the many buildings of 200m+ now being constructed worldwide, and the need for more
reliable damping predictions is imperative.
The consequences of overestimation of damping during design include higher lateral accelerations
(potential occupant comfort problems), increased lateral deflections (potential damage to cladding
and fit-out) and higher forces in structural members (reduced factor of safety and potential
structural damage and fatigue in extreme winds).
2.3 Foundations
Foundations provide two generic sources of dissipation. There is the intrinsic damping of the soil
material, and also radiation damping – the propagation of energy away from the building in body
and surface waves in the soil. The main mode of wind-induced foundation deformation in many tall
buildings is low frequency rocking, which is associated with very low radiation damping.
3. Measurements of damping
3.1 Measurement techniques
The only basis for the prediction of damping in a tall building is the evidence of previous
measurements. Unfortunately, damping is difficult to measure with precision, and some historically
much-used techniques are unreliable, almost always resulting in over-estimation of the actual
damping. It is now well established that the various ‘random decrement’ methods are more
representative than the previously used spectral methods.
3.2 Variation of damping with height
Figure 1 shows a collation of high-quality data from a number of recent sources. The primary
source is Satake [7], but also included are a number of other recent measurements, for buildings up
to 450m This collation was first presented in [8]
The data shows a lower ‘floor’ of damping, at about 0.4% of critical at all building heights greater
than 50m. For buildings lower than 100m, whilst damping is generally below 3% of critical,
considerably higher damping is sometimes measured. However, for buildings above 250m it is
exceptional for measured values to significantly exceed 1% of critical. There is therefore a clear
trend that damping reduces with increasing building height. The authors believe that this decrease in
damping is because as the primary structural members become much larger in very tall buildings
the contribution of non-structural elements to energy dissipation becomes relatively less significant.
Also plotted on figure 1 are a number of measurements from tall chimneys. Chimneys, by their
nature of construction, are dominated by their primary structure, with internal flues contributing
little to damping and stiffness. British Standard 4076 [2] shows this variation in the treatment of
damping – flues typically increase damping by 15-20%. It can be seen that damping ratios for tall
buildings are similar to those of chimneys.
8
7
Damping ratio (%)
on tall buildings. However, the data referenced above indicates that peak damping may be reached
at relatively low amplitude. It should be noted that damping ratio reducing with amplitude is a
normal characteristic of friction-damped systems.
8
Buildings, Steel, measured
7
Damping ratio (%)
Lower trendline
4 Design assumption
3
2
1
0
0 100 200 300 400 500
Height [m]
It is common to assume different levels of damping for serviceability and ultimate wind design.
Where this is done, both values are shown. However, as shown in section 3.4, peak damping ratio
can occur at relatively low amplitude, so the authors believe that this practice may not be fully
justified.
15000
damping. This is clearly a significant
t = 8.75 sec difference. Given that measured damping
10000 in buildings can be as low as 0.3% and
assumed as high as 3%, there is clearly
5000
cause for caution.
0 If the damping were very high (>10%),
0
10
12
As with the overturning moment, the consequences of overestimation of damping leads to higher
accelerations in the building than predicted at design stage.
• Uncertainty in wind speed data at the level of the top of the building.
• Uncertainty in wind tunnel model testing
• Uncertainty in dynamic response.
Wind loading codes are written with smaller buildings in mind where these points are of low
relevance. The uncertainty in design wind speed at the top of a tall building is significant. Almost
all wind climate estimates are based upon measurements made at 10m above ground level.
Extrapolation to heights in excess of 200m is therefore inevitably prone to some uncertainty.
As was demonstrated in section 4.2, it is possible that a traditional overestimation of damping alone
may lead to design loads that are only 63% of their “true” value. This uncertainty effectively “uses
up” the whole of a 1.6 load factor.
5. Supplementary damping
5.1 Overview
Supplementary damping systems are a means of providing additional energy dissipation using
engineered systems. They have a distinct advantage in that the damping can be predicted before
construction. Even if the damping systems are not operating at optimum performance, the relative
error in dynamic response is likely to be less, as is shown in table 1.
Case Assumed Actual Assumed Actual Effect on
intrinsic intrinsic supplementary supplementary dynamic
damping (%) damping (%) damping (%) damping (%) response
Undamped 1.5 0.5 0 0 (1.5/0.5)=1.72
Damped 1.5 0.5 5 4.0 (6.5/4.5)=1.20
Table 1 - Consequence of error in damping assumptions
When adopting supplemental damping in design, it is important to consider the redundancy and
robustness of the damping system. The engineer should only rely upon a supplementary damping
for strength design there is confidence in the absolute reliability of the system.
The next section describes two forms of building supplementary damping system – tuned mass or
liquid dampers and fluid-viscous dampers.
7.2 Recommendations
Structural engineers and wind loading specialists should either:
• Assume damping ratios consistent with measurements – typically 0.5% - for buildings
above 250m in height.
• Incorporate supplementary damping systems, preferably robust systems which can improve
the economy and performance of tall buildings.
8. References
[1] BAKER et al, “Burj Dubai : Engineering the worlds tallest building”, The structural design of
tall and special buildings, Vol 16, 2007, pp 361 – 375
[2] BRITISH STANDARDS INSTITUTE, British Standard 4076, Specification for Steel
Chimneys, London, BSI, 1989
[3] COLE D, SPOONER D, “The damping Capacity of Concrete,” International conference on
the structure of concrete and its behaviour under load, London, Sep 1965, pp 217-225
[4] ENGINEERING SCIENCES DATA UNIT, Damping of Structures, Part 1, Tall Buildings,,
London, ESDU, data Item 83009
[5] FANG, J.Q., LI, Q.S., JEARY, A.P., LIU, D.K., “Damping of Tall Buildings: Its Evaluation
and Probabilistic Characteristics”, Structural Design of Tall Buildings, Vol 8, 1999, pp. 145-
153.
[6] LI QS, YANG K, ZHANG N, WONG CK, JEARY AP. “Field measurement of amplitude-
dependent damping in a 79-storey tall building and its effects on the structural dynamic
responses”. The Structural design of tall buildings, Vol 11, 2002, pp 129-153
[7] SATAKE N, SUDA K, ARAKAWA T, SASAKI A, TAMURA Y.. “Damping evaluation Using
Full-Scale Data of Building in Japan” ASCE Journal of Structural Engineering, Vol 129, 2003:
pp470–477
[8] SMITH R, WILLFORD M, “The damped outrigger concept for tall buildings”, The Structural
Design of Tall and Special Buildings, Vol 16, 2007, pp 501-517
[9] TAMURA Y., “Amplitude Dependency of Damping in Building and Estimation Techniques”
Keynote lecture, 12th Australasian Wind Engineering Conference, Queenstown, New Zealand,
Jan 31–Feb 2 2006.
Data sources for figure 1 and 2 are listed in Smith and Willford [8].