You are on page 1of 10

Engineering Structures 103 (2015) 53–62

Contents lists available at ScienceDirect

Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct

Wind load factors for dynamically sensitive structures


with uncertainties
Dae Kun Kwon a,⇑, Ahsan Kareem a, Rachel Stansel b, Bruce R. Ellingwood c
a
Department of Civil & Environmental Engineering & Earth Sciences, Univ. of Notre Dame, Notre Dame, IN 46556, United States
b
ABS Consulting, San Antonio, TX 78232, United States
c
School of Civil and Environmental Engineering, Colorado State University, Ft. Collins, CO 80517, United States

a r t i c l e i n f o a b s t r a c t

Article history: The current recommendations for the load factors on wind load in ASCE Standard 7 are based on an anal-
Received 5 February 2015 ysis of performance of rigid buildings, which may not be adequate for dynamically sensitive structures. In
Revised 10 August 2015 light of the uncertainties associated with dynamic characteristics of flexible buildings such as natural fre-
Accepted 19 August 2015
quency and damping ratio, the load factors for such buildings may deviate from that in ASCE 7. This study
investigates the efficacy of the current wind load factor for dynamically sensitive structures in the pres-
ence of uncertainties. A systematic analysis is performed using Monte Carlo simulations. Uncertainties
Keywords:
associated with each component of the wind load effects such as the wind speeds, natural frequency
Buildings (codes)
Design (buildings)
and damping ratio of a building are incorporated in the load effects based on both ASCE Standard 7-05
Hurricanes and ASCE Standard 7-10. In addition, a database-enabled design (DED) procedure is utilized to support
Structural engineering the analysis of the wind load factor, especially for the acrosswind case where ASCE 7 does not offer
Uncertainty any guidance. In addition, the effects of terrain conditions, amplitude-dependent frequency and damping,
Wind engineering and negative aerodynamic damping on the wind load factor are also discussed. Recommendations are
Wind load factors made for wind load factors for dynamically sensitive structures both in the alongwind and acrosswind
directions and for non-hurricane and hurricane winds.
Ó 2015 Elsevier Ltd. All rights reserved.

1. Introduction (or load factors) that are more conservative than the factor cur-
rently used in ASCE 7 may be required for tall building design.
The wind load factor recommended in ASCE Standard 7 [1–3] for The aforementioned studies considered a sample building to deter-
load combinations involving wind load are based on an analysis of mine wind induced effects such as wind pressures/loads, base
performance of rigid buildings [17,18]. It accounts for deviations in moments and top displacements based on wind tunnel datasets.
the actual loads from the nominal loads and for the uncertainties Uncertainties associated with wind speeds, frequency and damp-
associated with the load effects. To estimate this factor realisti- ing, and other parameters such as errors in wind tunnel experi-
cally, studies have been carried out to account for the effects of ments and measured datasets were taken into account. Overall
both aleatory and epistemic uncertainties, including those in the trends from the studies have indicated an increase of the load
estimation of extreme wind speeds, wind load effect model, wind factor.
tunnel experiment results, etc., which significantly influence the A number of issues remain concerning wind load factors for
wind effects on rigid buildings (e.g., [37,15,16]). flexible buildings. First, ASCE 7-10 [3] has introduced new wind
Wind effects on flexible buildings are more significant than maps based on a mean recurrence interval (MRI) of 700 years for
those on rigid buildings, and the dynamic response parameters, basic wind speed for the Category II buildings [44,45], which
especially frequency and damping, contribute additional uncer- replaced the 50-year MRI wind speed map in ASCE 7-05 [2]. Along
tainty to the response (e.g., [19,5,10]). In light of these uncertain- with this change, the wind load factor was reduced from 1.6 to 1.0
ties and the fact that the building response is no longer for the load combinations in which the wind load is the principal
proportional to the square of the wind velocity, a wind load factor action. Most previous studies of tall, flexible buildings have
focused on the wind loads and wind load factors in ASCE Standard
7-05. These earlier studies must be revisited to explore how these
⇑ Corresponding author.
recent changes might affect the wind load factors and other wind
E-mail addresses: dkwon@nd.edu (D.K. Kwon), kareem@nd.edu (A. Kareem),
rstansel@eagle.org (R. Stansel), bruce.ellingwood@colostate.edu (B.R. Ellingwood).
load requirements for flexible buildings in the current edition of

http://dx.doi.org/10.1016/j.engstruct.2015.08.031
0141-0296/Ó 2015 Elsevier Ltd. All rights reserved.
54 D.K. Kwon et al. / Engineering Structures 103 (2015) 53–62

ASCE 7. Second, although past studies (e.g., [19,5,10]) have con- a = the sensitivity coefficient; and VW = the coefficient of variation
cluded that the load factor for flexible buildings should be higher (COV) in the wind load/pressure. Using the values for a rigid build-
than that for rigid buildings, the results among these studies were ing reported by Ellingwood and Tekie [18], i.e., lW/Wn = 0.78,
inconsistent. In addition, given that the effect of the uncertainties b = 2.5, a = 0.75, VW = 0.37, the load factor defined in Eq. (1) results
on the acrosswind response of tall buildings would be different in cw = 1.32, which is equivalent to the load factor (1.3) used in ASCE
from their alongwind response due to more significant aerody- 7-95. The mean wind load/pressure in that study implicitly included
namic interactions and negligibly small contribution of the mean a wind directionality factor of 0.85. When an explicit wind direc-
response, the load factor in the acrosswind direction may also be tionality coefficient, Kd = 0.85 was added to the ASCE 7 provisions
different from that in the alongwind direction. For example, Gabbai for rectangular buildings in 1998, the corresponding wind load fac-
et al. [19] reported that overall wind load factors for selected mem- tor (=1.3/0.85), excluding the directionality factor, was increased to
bers of an example tall building using synchronous pressure mea- 1.6. When Ellingwood and Tekie [18] later revisited the choice of
surement data ranged from 1.9 to 3.5 for the alongwind and probability distribution for modeling the extreme wind speed and
acrosswind top displacements based on the probabilistic peak the difference between wind speed models in hurricane zones ver-
wind load effects used in rigid buildings [37,16]. However, these sus non-hurricane zones, they concluded that the reliability index,
load factors for the case of rigid building ranged from 1.9 to 2.3, b, for wind loads should be approximately 3.0. A single wind load
which depart from the expected load factor of 1.5–1.7 in Elling- factor of 1.6 was employed for editions of ASCE 7 between 1998
wood and Tekie [18] and 1.51 in Bashor and Kareem [5]. In addi- and 2005.
tion, the load factors reported in Gabbai et al. [19] were very In ASCE Standard 7-10, the wind load factor in combinations 4
close in the alongwind and acrosswind cases, while Bashor and and 6 was reduced to 1.0 because of the change in the specification
Kareem [5] reported that load factors for the acrosswind response of the design wind speed. The wind speeds for strength design
were larger than those for the alongwind response. This suggested were re-mapped at much longer MRIs, which are 700–1700 years
that the current load factor might not be adequate to account for the depending on the Occupancy Category (Figure 26.5 in the ASCE
acrosswind load effects. Overall, the load factors suggested by 7-10), thus eliminating the need for an importance factor for differ-
Gabbai et al. [19] were considerably higher than those suggested ent building risk categories and the discontinuity in the risk
by others (e.g., [5]). Chen and Huang [10] also examined wind load between the hurricane-prone coastal areas and the remainder of
factors, quantifying the probabilistic wind load effects with the the country, and better aligning the treatment of wind and earth-
assumption of parametric variations of wind speed and extreme load quake effects (C2.3.2 in ASCE 7-10).
coefficient and finding that the structural response was proportional
to the wind velocity to the power of 2–3 for flexible buildings. Their 2.2. Relationship between the wind load factor and MRI of wind speed
load factor was close to that reported in Bashor and Kareem [5] when in ASCE 7
the power was 2.5. Third, there has been little consideration of the
impact of different terrain conditions (exposures) on response of The wind pressures/loads in ASCE Standard 7 are calculated
dynamically sensitive buildings, which may be one of the key param- from the 3-s gust wind speed, V3-s. The ratio of this wind speed
eters for proper assessment of the wind load factor. Finally, there is for any MRI, T, (VT) to the 50-yr MRI wind speed (V50) in non-
limited information for the load factor associated with hurricane hurricane prone regions is (e.g., [38]):
winds, which might be higher due to inherently higher uncertainties
in hurricane wind speeds, as shown in the literature for rigid build- VT
¼ 0:36 þ 0:1 lnð12TÞ ð2Þ
ings (e.g., [18,37,15,16]). V 50
To address the above issues, this study investigates the applica-
When the wind speed maps in ASCE 7-2010 were developed, the
bility of the current wind load factor for dynamically sensitive
wind load factor (cw) was defined as the ratio between the point
structures in the presence of uncertainties. A systematic analysis
estimates of the T-yr and 50-yr wind speeds as:
is performed using Monte Carlo simulations in which uncertainties
associated with each parameter involved in the wind load effects,  n
VT
such as wind speeds, natural frequency and damping ratio, are cw ¼ ð3Þ
V 50
incorporated using both ASCE Standard 7-05 and ASCE Standard
7-10 procedures. In addition, a database-enabled design (DED) pro- where n equals 2, which is based on the behavior of rigid buildings
cedure [48,33,34] is also included to validate the assessment of the in the absence of any dynamic amplification. Eq. (3) implies that all
wind load factor, especially for the acrosswind direction where uncertainty in the wind load is vested in the uncertainty in the wind
ASCE Standard 7 does not offer any guidance. Finally, recommenda- speed. Using the load factor of 1.6 defined in ASCE 7-05, Eqs. 2 and 3
tions are made for wind load factors for dynamically sensitive yield T = 709 years for Risk Category II structures (where the impor-
structures loaded in both the alongwind and acrosswind directions tance factor (I) is 1.0). Accordingly, T was set equal to 700 years in in
as well as in non-hurricane and hurricane wind regimes. developing the wind speed maps in ASCE 7-10 and cw was set equal
to 1.0. For example, V50 defined in ASCE 7-05 was 40 m/s in the Mid-
2. Wind load factor in ASCE Standard 7 west region; using T = 700-yr MRI and V50 = 40 m/s in Eq. (2) for the
Risk Category II structures (I = 1.0), V700 becomes 51 m/s, which is
2.1. Background of the wind load factor for load combinations the new basic wind speed defined in ASCE 7-10.
in ASCE 7 For rigid buildings such as low-rise structures, the wind loads
are proportional to the square of the wind speed because the wind
The wind load factor (cw) in ASCE Standard 7 is defined using the responses are governed by mean (static) and background turbu-
first-order reliability method (FORM) as [17,18]: lence effects (quasi-static). However, in the case of flexible build-
  ings, n may exceed 2 because the response is dominated by
lW
cw ¼ ð1 þ abV W Þ ð1Þ inertial effects (e.g., [10]). For example, assuming that n = 2.5 and
Wn
T = 700-yr, V700 = 51 m/s; with V50 = 40 m/s, as before, the implied
where lW/Wn = the bias or ratio between the mean and the nominal wind load factor based on Eq. (3) would increase from 1.6 to 1.84
wind loads/pressures, where the nominal value (Wn) is determined for flexible buildings. Such increases will be considered in more
in accordance with the ASCE 7 criteria; b = the reliability index; detail in the sequel.
D.K. Kwon et al. / Engineering Structures 103 (2015) 53–62 55

3. Evaluation of wind load factor and TKU databases have two common terrain conditions (Expo-
sures A and C), but the TKU database also has a greater subdivision
3.1. Analysis methods in the datasets with an additional terrain condition (Exposure B).
We have included Exposure A in this paper, despite the fact that
In order to determine appropriate wind load factors for dynam- ASCE 7 no longer includes this exposure, in order to examine the
ically sensitive buildings, extensive Monte Carlo simulations were effect of terrain exposure on flexible building response in later
performed for over 100 separate cases, in which the effects of rigid sections. The databases consist of non-dimensional base moment/
versus flexible buildings and uncertainties associated with wind torque power spectral density [CM(f)] and RMS base moment/
speeds, frequency, damping, and other parameters such as pres- torque coefficients (rCM) in alongwind, acrosswind and torsional
sure/force coefficients and wind parameters (e.g., wind profile directions in each dataset, which are the key parameters for esti-
and turbulence coefficients) were investigated. Two structural mating wind responses using a 3-D gust loading factor approach.
responses – base moments and building top displacements – were For completeness, a brief summary of the DED procedure is dis-
selected to assess the wind load factor. In an earlier study by cussed in the Appendix A. More detailed descriptions of the analy-
Ellingwood and Tekie [18], the load factor was derived based on sis scheme, the datasets, wind tunnel test conditions, and validity
wind load/pressure of low-rise buildings in which displacement of the HFBB datasets can be found in Kareem and Zhou [31], Zhou
response is negligible. However, for flexible buildings both the base et al. [48], and Cheng and Wang [12], Kwon et al. [33], and Kwon
moments and top displacements have their respective significance. and Kareem [34].
Two different methods were employed to estimate the wind
load factors. The first method is the ASCE 7 analysis procedure
for rigid and flexible buildings, i.e., gust loading/effect factor 3.2. Load factor definitions and uncertain parameters
approach (e.g., [40,41]). Provisions for the wind load effects on
structures in most codes and standards, including ASCE 7, gener- The test cases for the wind load factor analysis are classified in
ally focus primarily on the alongwind (buffeting) response. How- terms of: rigid or flexible buildings; uncertainties in wind speed;
ever, this method fails to capture the loading mechanisms in the uncertainties in fundamental natural frequency and damping ratio
acrosswind and torsional directions. Given the fact that the across- of buildings; all uncertainties. Tables 1 and 2 describe the uncer-
wind response is generally dominant for flexible buildings, a tain parameters for the ASCE 7 and DED procedures, respectively,
database-enabled design (DED) procedure, which is a promising based on a comprehensive review of the literature. The parameters
design procedure for assessing wind-induced response in a more are used to estimate the base moment and top displacement of the
reliable way than is possible with conventional codes and stan- case study buildings. Note that the uncertain parameters b, c and q
dards, is employed as a alternative approach to load factor deter- are associated with the wind speed, which includes errors in the
mination. The DED procedure used in this study employs a base estimation of extreme wind speeds such as a proper choice of
moment-based 3-D gust loading factor approach [31] drawing probability distribution of extreme winds, sampling errors, wind
from a high-frequency base balance (HFBB) database. This speed conversion errors for different averaging time (e.g., 3-s to
approach has been adopted in cyberbased on-line DED modules 1-h for wind response estimation), and observation error in wind
such as the NatHaz Aerodynamic Loads Database (NALD) speed, respectively. In addition, note that the epistemic uncertain-
[48,33,35] and has been introduced in the Commentaries of both ties that arise from the use of HFBB aerodynamic loads, such as
ASCE 7-05 and 7-10. A more recent expanded e-module for high- that used in the DED procedure (Appendix A), may become impor-
rise buildings, DEDM-HR has a unique capability, of hosting multi- tant when the fundamental mode shapes depart from the ideal
ple databases [34]. For reference, both e-modules are accessible via uncoupled linear form [7]. Although Zhou et al. [47] reported that
an engineering virtual organization, VORTEX-Winds (https:// the influence of non-ideal mode shapes is negligible for base bend-
vortex-winds.org) [30]. ing moments (and the DED procedure used in this study), such
Two HFBB databases are utilized in the DED procedure: the first uncertainties may also affect the load factors to some degree.
is from the NatHaz Modeling Laboratory at the University of Notre Two load factor definitions are utilized in this study:
Dame, USA, which was the basic HFBB database used in the NALD
[48,33], and the second is from the Wind Engineering Research (1) Load Factor 1 (LF 1): This load factor, defined in Eq. (1),
Center (WERC) at Tamkang University (TKU), Taiwan [12]. Both was developed from traditional First-Order reliability
databases are housed in e-module, DEDM-HR [34]. Both NatHaz analysis. The sensitivity coefficient, a = 0.8, reflects the

Table 1
Uncertain parameters used in ASCE 7 procedure.

Parameter Description PDF COV Reference


b Errors in the estimation of extreme wind speeds Normal 0.075 Minciarelli et al. [37], Coles and Simiu [13], Diniz et al. [15], Gabbai
et al. [19]
c Wind speed conversion for different averaging time Normal 0.05 Minciarelli et al. [37]
q Observation error in wind speed Normal 0.025 Minciarelli et al. [37]
f Fundamental natural frequency Lognormal 0.05 Kareem [26], Kareem [27]; Bashor et al. [6]; Gabbai et al. [19]
f Damping ratio Lognormal 0.4 Davenport and Hill-Carroll [14], Kareem [26], Kareem [27]; Bashor
et al. [6]; Gabbai et al. [19]
Cpw, Cpl Windward and leeward external pressure Normal 0.1 Bashor et al. [6]
coefficients, respectively
q Air density Normal 0.05 Bashor et al. [6]
K Mode shape Normal 0.05 Bashor et al. [6]
qB Building density Normal 0.05 Bashor et al. [6]
a; zg ; a^ ; b^ Wind parameters pertaining to wind profile, Normal 0.05 Minciarelli et al. [37]; Bashor et al. [6]
 c; d; ‘; 
a ; b; e turbulence intensity, etc.*

*
Symbols used for wind parameters are the same with those defined in the ASCE 7, thus detailed explanation for each symbol is omitted here for brevity.
56 D.K. Kwon et al. / Engineering Structures 103 (2015) 53–62

Table 2
Uncertain parameters used in DED procedure.

Parameter Description PDF COV Reference


b Errors in the estimation of extreme wind speeds Normal 0.075 Minciarelli et al. [37], Coles and Simiu [13], Diniz et al. [15], Gabbai et al. [19]
c Wind speed conversion for different averaging Normal 0.05 Minciarelli et al. [37]
time
q Observation error in wind speed Normal 0.05 Minciarelli et al. [37]
f Fundamental natural frequency Lognormal 0.05 Kareem [26]; Bashor et al. [6]; Gabbai et al. [19]
f Damping ratio Lognormal 0.40 Davenport and Hill-Carroll [14], Kareem [26]; Bashor et al. [6]; Gabbai et al.
[19]
e1, e2  and a
Uncertainty of b * Normal 0.05 Bashor et al. [6]
e3 Uncertainty of CM(fr) ** Normal 0.15 Bashor et al. [6]
e4 Uncertainty of rCM** Normal 0.25 Bashor et al. [6]
q Air density Normal 0.05 Bashor et al. [6]
K Mode shape Normal 0.05 Bashor et al. [6]
qB Building density Normal 0.05 Bashor et al. [6]
CD Drag coefficient Lognormal 0.10 Kareem [26]; Bashor et al. [6]
*
Power law coefficients in the wind profile definition.
**
CM(fr) = Non-dimensional power spectral density; rCM = Non-dimensional RMS base moment coefficient.

skew-positive nature of the Type I extreme value distribu- f = 0.01; air density qA = 1.22 kg/m3. The building is assumed to
tion used to model the wind response. The reliability index, be located in an urban environment within the continental US,
b = 3.0, is used [18]. which corresponds to Exposure A defined in ASCE 7-98 [1]; b)
(2) Load Factor 2 (LF 2): Generally when a variable is a function Building 2: B = D = 40 m (square cross-section); H = 200 m; funda-
of a product of other independent random variables, the mental natural frequencies in alongwind and acrosswind direc-
resulting distribution is similar to a lognormal distribution. tions, fx = fy = 0.2 Hz, respectively; linear mode shape; building
Accordingly, the second load factor definition is introduced bulk density qB = 245 kg/m3; damping ratio f = 0.02; air density
here which assumes that the resulting wind response has a qA = 1.22 kg/m3. This building is located in a suburban area (Expo-
Lognormal distribution: sure B in ASCE 7-10).
 qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi Various magnitudes of 3-s gust wind speeds were utilized to
compare the 2005 and 2010 versions of ASCE Standard 7 and to
  exp be‘ lnð1 þ V 2W Þ
lW consider non-hurricane and hurricane wind climatologies. This
cw;LF2 ¼ qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi ð4Þ
provides overall trends in the wind load factors associated with
Wn
1 þ V 2W
the recent changes in the ASCE 7 wind load provisions, especially
for the different basic wind speeds.
where e‘ ¼ 0:72 (e.g., [36]) and the other variables are the same as
defined in LF1.
In both LF1 and LF2 definitions, the nominal wind response
4. Wind load factors for flexible building response
(Wn), either the base moment or displacement, is determined by
ASCE 7 or the DED procedure assuming that there are no uncertain-
4.1. Load factors using basic wind speed defined in ASCE -05 – non-
ties involved, while lW and VW are determined by Monte Carlo
hurricane winds
simulation (100,000 samples) taking uncertainties in the parame-
ters into account. Note that the effect of wind directionality is
The basic wind speed,V3-s, was assumed to be 40 m/s for Build-
excluded in this study, as in Ellingwood and Tekie [18], in which
ing 1 and 63 m/s for Building 2 for the estimation of alongwind
they recommended a separation between the wind directionality
load factors. No special consideration for hurricane winds was con-
effects and the load factor.
sidered in this case study; the hurricane case will be examined sep-
arately in a later section. The DED procedure utilized the TKU
3.3. Example buildings database for Building 2 because the NatHaz database does not con-
tain datasets for Exposure B. A comparison of the alongwind
Two example buildings were utilized in the assessment of the responses computed from the ASCE 7 and DED procedures, e.g.,
wind load factor: (a) Building 1, the CAARC (Commonwealth Aero- the base moments, top displacements and top root-mean-square
nautical Advisory Research Council) standard tall building (e.g., (RMS) accelerations, is presented in Table 3. Some differences
[21]): width B = 46 m; depth D = 30 m; height H = 183 m; funda- can be seen, with the DED results being slightly higher than those
mental natural frequencies in alongwind and acrosswind direc- given by ASCE 7. This may be attributed to the building-specific
tions, fx = 0.17 Hz and fy = 0.177 Hz, respectively; linear mode aerodynamic load introduced in DED, whereas ASCE 7 is based
shape; building bulk density qB = 157 kg/m3; damping ratio on a simplified procedure, i.e., gust loading/effect factor. In view

Table 3
Comparison of alongwind responses based on ASCE 7-05 and DED procedures (V3-s = 40 m/s).

Procedure* Base moment (106 kN-m) Top displacement (m) Top RMS acceleration (milli-g)
Building 1 ASCE 7 1243 0.39 4.46
DED  NatHaz 1241 0.45 5.40

Building 2 ASCE 7 4257 0.46 4.25


DED  TKU 4711 0.57 5.94

ASCE 7 = ASCE 7 procedure; DED  NatHaz = DED procedure using NatHaz database; DED  TKU = DED procedure using TKU database.
D.K. Kwon et al. / Engineering Structures 103 (2015) 53–62 57

Table 4
Alongwind load factors for example buildings 1 and 2 based on ASCE 7-05 basic wind speed for non-hurricane case using ASCE 7 and DED procedures.

Uncertainty cases* Example building and procedure** Base moment Displacement


LF1 LF2 LF1 LF2
Rigid None B1, ASCE 7 1.00 1.00 1.00 1.00
B1, DED–NatHaz 1.00 1.00 1.00 1.00
B2, ASCE 7 1.00 1.00 1.00 1.00
B2, DED–TKU 1.00 1.00 1.00 1.00
Flexible None B1, ASCE 7 1.00 1.00 1.00 1.00
B1, DED–NatHaz 1.00 1.00 1.00 1.00
B2, ASCE 7 1.00 1.00 1.00 1.00
B2, DED–TKU 1.00 1.00 1.00 1.00
Rigid bcq B1, ASCE 7 1.49 1.52 1.49 1.52
B1, DED–NatHaz 1.49 1.49 1.49 1.49
B2, ASCE 7 1.49 1.52 1.49 1.52
B2, DED–TKU 1.49 1.52 1.49 1.52
Flexible bcq B1, ASCE 7 1.61 1.67 1.61 1.66
B1, DED–NatHaz 1.59 1.63 1.59 1.63
B2, ASCE 7 1.59 1.64 1.59 1.64
B2, DED–TKU 1.56 1.60 1.56 1.60
Flexible bcq, f B1, ASCE 7 1.61 1.67 1.71 1.79
B1, DED–NatHaz 1.59 1.64 1.69 1.76
B2, ASCE 7 1.59 1.64 1.69 1.76
B2, DED–TKU 1.56 1.60 1.65 1.71
Flexible bcq, f & f B1, ASCE 7 1.71 1.78 1.81 1.91
B1, DED–NatHaz 1.68 1.74 1.77 1.86
B2, ASCE 7 1.67 1.73 1.76 1.86
B2, DED–TKU 1.66 1.72 1.75 1.83
Flexible All B1, ASCE 7 1.74 1.83 1.93 2.08
B1, DED–NatHaz 1.98 2.14 2.08 2.28
B2, ASCE 7 1.71 1.78 1.89 2.01
B2, DED–TKU 1.93 2.08 2.02 2.20
*
Rigid = rigid building; Flexible = flexible building; None = no uncertainties; bcq = wind speed uncertainties; f and f = fundamental natural frequency and damping ratio
uncertainties, respectively; All = all uncertainties (e.g., pressure coefficients, etc.) were considered. See Tables 1 and 2.
**
B1 and B2 = building examples 1 and 2, respectively.

of the inherent differences between the two procedures, the build- building, especially when uncertainties associated with wind
ing responses agree reasonably well. Similar conclusions have been speed, frequency and damping (Flexible bcq, f & f case) were intro-
drawn in other studies [48,33,34]. duced. The effects of frequency uncertainty (Flexible bcq, f) for the
Table 4 shows the load factors for both example buildings using base moment-based load factors turned out to be very small as
the ASCE and DED procedures for the alongwind response. Note compared to the effect of wind speed uncertainty (Flexible bcq);
that the response for rigid buildings was obtained by excluding however, such effects were more apparent in the displacement-
the resonant response component, i.e., including only mean and based load factors. Given the fact that there exists large uncer-
background components. For the cases in which no uncertainties tainty associated with damping (COV = 0.40 in Tables 1 and 2), it
were involved (described as None in the table), the load factors is not surprising that damping effects are dominant in the esti-
both for the rigid and flexible buildings reduced to unity (1.0). This mated load factors for the Flexible bcq, f & f case. In addition, the
indicates that the bias (lW/Wn in Eqs. 1 or 4) between the mean scatter between the Flexible bcq, f & f and all uncertainties involv-
and the nominal wind loads/displacement was unity. The load fac- ing wind profile, turbulence intensity, external pressure coeffi-
tors for the two example buildings using ASCE 7 and DED showed cients parameters, etc. using the ASCE 7 procedure tends to be
very good agreement despite different wind characteristics (e.g., negligible. This shows that uncertainties associated with wind
basic wind speeds, exposures) and building properties except speed, and frequency and damping (Flexible bcq, f & f case) are
when all uncertainties are involved (Flexible All in Table 4), the lat- the key factors that contribute most to uncertainty in flexible
ter due to the level of uncertainties (i.e., COV) assumed in the non- building response. Additional simulations [4], not reported here
dimensional base moment spectrum [CM(fr)] and RMS base for brevity, include an uncertainty analysis with wind-related
moment coefficients (rCM) in Table 2. The displacement-based load parameters such as wind speed, wind profile, and turbulence
factors were slightly higher than the base moment-based load fac- intensity parameters. The results were virtually the same when
tors especially when frequency and damping uncertainties were compared to the case involving only wind speed uncertainty
involved. This is attributed to the involvement of frequency and parameters (Flexible bcq).
damping multiple times in displacement calculations. For example, For the acrosswind case, only the DED procedure could be uti-
the displacement calculation procedure in ASCE 7 is explicitly lized to assess wind load factors because there are no comparable
expressed as a function of frequency and gust effect factor (G) provisions in ASCE 7 for this case. The basic wind speed was
and the latter is also associated with frequency and damping assumed to be 40 m/s both for Building 1 and 2. The results for
parameters. the acrosswind analysis are given in Table 5. The overall trends
Overall, the wind load factors LF2 were slightly higher than LF1, are similar to those for the alongwind case given in Table 4: the
but they generally showed good agreement with less than 5% dif- load factors for flexible buildings are notably affected by the wind
ference between them. With regard to rigid versus flexible build- speed, frequency and damping and the displacement-based factors
ings, there was an increase in the load factors for the flexible are larger than the base moment-based factors. It is observed that
58 D.K. Kwon et al. / Engineering Structures 103 (2015) 53–62

Table 5
Acrosswind load factors for building 1 and 2 examples based on ASCE 7-05 basic wind speed for non-hurricane case using DED procedure (V3-s = 40 m/s in all cases).

Uncertainty cases Example building, procedure and exposure Base moment Displacement
LF1 LF2 LF1 LF2
Rigid and flexible None All cases 1.00 1.00 1.00 1.00
Rigid bcq B1, DED–NatHaz, Exp. A 1.49 1.52 1.49 1.52
B2, DED–TKU, Exp. B 1.49 1.52 1.49 1.52
B2, DED–NatHaz, Exp. A 1.49 1.52 1.49 1.52
Flexible bcq B1, DED–NatHaz, Exp. A 1.78 1.89 1.78 1.89
B2, DED–TKU, Exp. B 1.70 1.78 1.70 1.78
B2, DED–NatHaz, Exp. A 1.79 1.93 1.79 1.93
Flexible bcq, f B1, DED–NatHaz, Exp. A 1.81 1.94 1.93 2.10
B2, DED–TKU, Exp. B 1.72 1.80 1.82 1.94
B2, DED–NatHaz, Exp. A 1.81 1.95 1.93 2.11
Flexible bcq, f & f B1, DED–NatHaz, Exp. A 2.04 2.23 2.15 2.40
B2, DED–TKU, Exp. B 1.93 2.07 2.04 2.21
B2, DED–NatHaz, Exp. A 2.00 2.19 2.11 2.35
Flexible All B1, DED–NatHaz, Exp. A 2.63 3.13 2.75 3.32
B2, DED–TKU, Exp. B 2.37 2.71 2.48 2.88
B2, DED–NatHaz, Exp. A 2.57 3.06 2.69 3.23

unlike the alongwind case, discrepancies between Buildings 1 and directions. The nominal wind effect (Wn) was determined using
2 are more notable for the flexible cases. However, such discrepan- both ASCE 7-10 and DED procedures with the new basic wind
cies are less significant when the acrosswind load factors for Build- speed for non-hurricane winds, assuming that building 1 was
ing 2 are estimated in Exposure A, included for comparison in located in the Midwest region. The 3-s gust speed increased from
Table 5 (‘‘B2, DED–NatHaz, Exp. A”). This trend is due to the effect 40 m/s (ASCE 7-05) to 51 m/s using the new ASCE 7-10 wind
of different exposures for each building example, i.e., Exposure A map. The method for establishing the new wind map in ASCE 7-
for Building 1 vs. Exposure B for the Building 2, which will be 10 implies that the uncertainties (e.g., wind speeds) considered
examined further in the next section. The load factors for the in ASCE 7-05 (50-yr MRI) are implicitly encompassed in ASCE 7-
acrosswind response are larger than those for the alongwind 10 (700-yr MRI). For this reason, uncertainties associated with fre-
response for flexible buildings, which indicates that the uncer- quency and damping were examined only to compare wind load
tainty in the acrosswind response is higher than that in the along- factors for the flexible building case. Fig. 1 shows probability of
wind response. This trend will also be investigated in the next exceedance curves for alongwind base moments and displace-
section. ments of the building 1 example using both ASCE 7-05 and 7-10
In summary, for non-hurricane wind speeds in ASCE 7-05 in the winds. It is clearly seen that at the same level of exceedance prob-
alongwind direction, uncertainties in response of flexible buildings ability, the effects of two different return periods (50-yr in ASCE 7-
(‘‘Flexible All” in the Table 4) yield wind load factors of about 1.9 05 and 700-year in ASCE 7-10) for both rigid and flexible cases are
and 2.1 for the base moment and displacement using the ASCE 7 significant.
procedure, respectively, while the factors using the DED procedure The alongwind and acrosswind load factors using ASCE 7-10
result in slightly higher values, about 2.1 (base moment) and 2.3 basic wind speeds under three exposures (Exposure A, B and C)
(displacement), due to the aerodynamic uncertainty. The factors are summarized in Table 6(a); the values in parentheses were
are much higher in the acrosswind case and depend on the expo- obtained through the DED procedure. The load factors for the
sure conditions as shown in Table 5. Based on these observations, alongwind direction obtained by the ASCE 7 and DED procedures
wind load factors in ASCE 7-05 for flexible buildings should be for the same exposure agree reasonably well. The discrepancies
higher than the factor 1.6 used for rigid buildings if the same level among exposures become more noticeable when the terrain
of reliability is to be achieved in both cases; moreover, the along- roughness becomes smoother, i.e., moving toward Exposure C.
wind wind load factors are not adequate if the acrosswind load For the alongwind case, the increase in the load factors from Expo-
effects are predominant. sure A to C for both base moment and displacement were marginal,
while the increases were more apparent in the acrosswind cases
4.2. Load factors using basic wind speed defined in ASCE 7-10 – non- which are more sensitive to inflow conditions.
hurricane winds Terrain effects tend to be different for load factors on alongwind
and acrosswind responses. When the terrain roughness becomes
ASCE Standard 7-10 reduced the wind load factor from 1.6 to 1.0 smoother, the alongwind load factor decreases, while the across-
when wind is treated as the principal action in the load combina- wind load factor increases. An examination of the wind load spec-
tion as a result of increasing the MRI for nominal wind speed to tra sheds further light on this observation. Fig. 2 shows non-
700 years from the 50-year MRI used previously. However, any dimensional base moment spectra for Building 1 under different
adjustments to the load factor to account for flexible or across- exposures, which represent typical alongwind and acrosswind
wind response have yet to be considered. The load factors moment spectra for tall buildings. The vertical lines shown in
determined in the previous section were relatively insensitive to Fig. 2 denote corresponding reduced frequencies (fr1 = f1B/UH, f1
different building properties including frequency and damping = natural frequency of building) for different exposures, where fr1
values and to different load factor definitions (LF1 and LF2). is inversely proportional to the mean hourly wind speed at the
Accordingly, only Building 1 and LF2 were utilized to evaluate top of the building (UH). The reduced frequencies decrease when
the wind load factors for ASCE 7-10 cases. Three exposures, defined the terrain becomes smoother due to an increase in the mean
in ASCE 7 as Exposures A, B and C, were employed to investigate hourly wind speed at the top of the building. The gust effect factor
the effects of exposures both in the alongwind and acrosswind in the ASCE 7 procedure and 3-D gust loading factor in DED
D.K. Kwon et al. / Engineering Structures 103 (2015) 53–62 59

cies associated with different exposures for the given building


example, uncertainty associated with wind speed results in varia-
tions in the wind spectral value of interest corresponding to the
reduced frequency that are dependent on building exposure.
Accordingly, Building 1 in Exposure A experiences higher uncer-
tainty in the response than in Exposure C because the spectrum
is more variable at the relevant reduced frequency in that Expo-
sure. This explains the trends in alongwind load factors for differ-
ent exposure conditions observed in Table 6a since the load factors
defined here (Eq. (4)) depend on the COV of the building response.
The effect is the opposite in the acrosswind direction. A typical
acrosswind spectrum exhibits a sharp peak around the Strouhal
number due to vortex shedding that strongly depends on the
intensity of the incident turbulence. Accordingly, the building in
Exposure C has a sharper (or narrow-band) peak around the Strou-
hal number than the same building in Exposure A because the vor-
tex shedding is vitiated by the presence of high levels of turbulence
intensity in the incident flow (e.g., [25]). Unlike the alongwind
spectra, the slope of the acrosswind spectra increases with the
decrease of the frequency, i.e., as the Strouhal number is
approached, and this trend is more predominant in smoother ter-
rain due to the influence of turbulences on vortex-shedding. Since
the slope changes around the reduced frequencies of interest are
more rapid in the acrosswind spectrum, the acrosswind load fac-
tors for different exposures exhibit larger scatter than the along-
wind factors.
Table 6(a) suggests that wind load factors for flexible buildings
in the alongwind case should be 1.3 (base moment) and 1.5 (dis-
placement) in Exposure B to achieve the same reliability as in rigid
buildings. For the acrosswind case, the load factors of about 1.6
(base moment) and 1.8 (displacement) in Exposure B are reason-
able but this factor may further increase if the tall building is
located in a smoother terrain, e.g., Exposure C or D, as noted in
Table 6a.
The current analysis is based on the assumption that the build-
ing dynamic characteristics remain constant under the design
loading condition. Recent full-scale studies reveal changes in both
frequency and damping are possible, even at below-design wind
speeds; damping in particular may exceed nominal values used
Fig. 1. Probability of exceedance curves of the alongwind response by ASCE 7-05
in design when buildings experience extreme excursions under
(50-yr wind) and 7-10 (700-yr wind) procedures (non-hurricane winds): (a) base
moment and (b) displacement. design loads or local inelastic action within the structural system
(e.g., [32,5]). Full-scale studies have revealed that with increasing
amplitudes of motion, natural frequency decreases and damping
procedure are key parameters for estimating response of flexible ratio increases (e.g., [43,22,28,29,39,42]). The increase in wind
structures to wind; both utilize a non-dimensional spectral value speeds in ASCE 7-10 (700-yr MRI) for flexible buildings would
corresponding to a reduced frequency (i.e., a point value). Consid- result in higher building response than calculated using the 50-
ering the features of the alongwind spectra and reduced frequen- year winds in ASCE 7-05 because the gust factor is velocity-

Table 6
Alongwind and acrosswind load factors based on ASCE 7–10 basic wind speed for non-hurricane and hurricane cases using ASCE 7–10 and DED procedures.

Uncertainty cases ASCE 7 procedure and exposure (DED procedure)* Alongwind Acrosswind
Base moment Displacement Base moment Displacement
(a) Non-Hurricane case (V3-s = 51 m/s)
Flexible f & f Exp. A (DED–NatHaz) 1.31 (1.34) 1.49 (1.55) (1.57) (1.75)
Exp. B (DED–TKU) 1.30 (1.33) 1.48 (1.48) (1.60) (1.77)
Exp. C (DED–NatHaz) 1.27 (1.32) 1.45 (1.44) (1.69) (1.94)
(b) Hurricane case (V3-s = 72 m/s) in Exposure B
Flexible f & f COV = 0** ASCE 7 1.36 1.53 – –
DED–TKU 1.36 1.49 2.20 2.67
Flexible f & f COV = 0.05 ASCE 7 1.53 1.68 – –
DED–TKU 1.49 1.61 2.83 3.20
Flexible f & f COV = 0.1 ASCE 7 1.91 2.03 – –
DED–TKU 1.82 1.92 3.68 3.91
*
Values in the parentheses of the non-hurricane case represent the results from DED procedure using NatHaz or TKU database.
**
COV value indicates additional uncertainty with regard to hurricane wind speeds.
60 D.K. Kwon et al. / Engineering Structures 103 (2015) 53–62

increasing to about 16% along the coast of Maine. Considering


these observations, three different levels of uncertainty (COVs)
regarding hurricane winds such as 0, 0.05 and 0.1 were assumed
to examine the wind load factors.
Wind load factors using Building 1 with a hurricane wind speed
of V3-s = 72 m/s are shown in Table 6(b) for Exposure B. The
assumption of Exposure B is based on the following premises: (a)
the load factor in Exposure B is likely to be an average value of
all three exposures (Exposure A, B and C) as observed in the non-
hurricane case (Table 6a); (b) practically all tall buildings in the
United States have been constructed in urban/suburban areas
rather than open terrains, with the exception of coastal develop-
ments. The DED procedure produces reasonably good agreement
with the ASCE 7 procedure, a trend noted earlier in Table 6(a).
The acrosswind load factors are much larger than those in the
non-hurricane case (Table 6) and also are larger than the along-
wind load factors in the hurricane case because the reduced fre-
quencies corresponding to hurricane wind speed (V3-s = 72 m/s)
tend to be closer to the Strouhal number (see Fig. 2b). However,
such a high wind speed in tall buildings may introduce negative
aerodynamic damping, which may lead to a reduction in total
damping, especially for the acrosswind response
[23,24,8,46,11,20,9]. It is anticipated that aerodynamic damping
in the alongwind case may be negligibly small for the building
example considered herein; however, for the acrosswind case, it
may reduce the total damping. Thus, the effect of amplitude-
dependency may be partially offset by aerodynamic damping for
the acrosswind case.
Assuming that the expected level of uncertainty regarding hur-
ricane winds is 0.05 (‘‘COV = 0.05” in Table 6b), the alongwind load
factors (consistent with ASCED 7-10) for flexible buildings should
be approximately 1.5 (based moment) and 1.7 (displacement) to
achieve the same reliability as rigid buildings. For the acrosswind
case, load factors of about 2.8 (base moment) and 3.2 (displace-
ment) may be reasonable values. Caution should be exercised in
the case of super-tall buildings in different terrain conditions,
Fig. 2. Non-dimensional base moment spectra for building 1 example: (a) especially for the acrosswind case under Exposures C or D, where
alongwind and (b) acrosswind – values in the parentheses represent 3-s gust the wind load factors may be impacted by the presence of negative
speed (V3-s). aerodynamic damping due to low turbulence intensity and high
wind speed conditions (high reduced velocity).
dependent. For an independent change either in frequency or
damping, it is obvious that a decrease in natural frequency would
5. Concluding remarks
result in an increase in the response; similarly an increase in the
damping ratio would lead to a reduction in the response. Correla-
This study presented an assessment of the alongwind and
tion between changes in frequency and damping remains to be
acrosswind wind load factors in ASCE Standard 7 for LRFD of
established.
dynamically sensitive structures, in which uncertainties associated
with wind speeds, natural frequency and damping ratio of build-
4.3. Load factors using basic wind speed defined in ASCE 7-10 – ings are taken into account. A systematic analysis was performed
hurricane case using extensive Monte Carlo simulations in which uncertainties
in the wind load effects were incorporated based on ASCE 7-05
Although the new hurricane model adopted in ASCE 7-10 is an and 7-10 procedures as well as a database-enabled design (DED)
improvement over previous editions of the standard, estimates of procedure using HFBB measurements.
hurricane wind speeds inevitably have higher uncertainty than Overall, the analysis suggests that the wind load factor defined
non-hurricane wind speeds due to errors in such factors as wind in ASCE 7 based on rigid buildings is not adequate for flexible
speed conversion for different averaging times, observation errors, buildings for either alongwind or acrosswind directions due to
and hurricane wind field modeling especially when much higher the sensitivity of flexible buildings to dynamic load effects and
MRI wind speeds (700-yr) are considered. For example, Coles and associated uncertainties related to frequency and damping. In
Simiu [13] noted an increase in the sampling uncertainty of hurri- addition, the effects of terrain conditions on the wind load factor
cane wind speeds for higher MRI, which was due to limitations in for flexible buildings are significant for the acrosswind case. The
the data from which the hurricane wind model used in the simula- displacement-based load factors were generally higher than the
tion was inferred and led to increase in wind speed uncertainty base moment-based factors, especially when frequency and damp-
when the model was extrapolated to long return periods [13]. ing uncertainties were considered. The load factors for hurricane
Vickery et al. [44] investigated uncertainties in the new hurricane winds are larger than for non-hurricane winds, and increase when
model and reported that the uncertainty in the estimated 100-yr uncertainty associated with hurricane wind speed estimation is
MRI wind speed was about 6% along the Gulf of Mexico coastline, taken into account. Furthermore, the acrosswind load factors were
D.K. Kwon et al. / Engineering Structures 103 (2015) 53–62 61

generally higher than the alongwind load factors. The acrosswind frequency of a building in the direction of motion; SM(f) = power
response of tall buildings results from complex aerodynamic inter- spectral density (PSD) of the fluctuating base moment or torque
actions, whereas the alongwind response follows the buffeting response; Since CM(fr) and rCM are obtained from the HFBB experi-
action of gusts; the uncertainties associated with acrosswind aero- ments, the mean, background and resonant base moments/torques
dynamics (e.g., wind tunnel test conditions) are more pronounced. can be computed using the building properties.
In addition, the contribution of the mean response is considerable Using Eq. (1), the equivalent static wind loads (ESWL) on a
in the alongwind response, which tends to negate the effects of the building can be computed by distributing the peak base moments
aerodynamic uncertainties, while it is negligible in the acrosswind to each floor in a similar fashion to how the base shear is dis-
response. Hence, since the design is often controlled by the across- tributed to each floor in earthquake engineering applications. In
wind direction, the relative significance of the alongwind load fac- addition, the displacement response calculation can be computed
tor is diminished. by invoking a modal analysis procedure. Details can be found in
Note that these observations, which delineate the difference Zhou et al. [48], Kareem and Zhou [31], and Kwon et al. [33].
between the rigid and flexible buildings, presume that the building
dynamic features remain unchanged under the design loading con- References
dition. Recent full-scale studies reveal that changes in both fre-
quency and damping are possible at even below-design wind [1] American Society of Civil Engineers (ASCE). Minimum design loads for
buildings and other structures. ASCE 7-98, Reston (VA): ASCE; 1998.
speeds. In addition, in high wind speed conditions like in hurri- [2] American Society of Civil Engineers (ASCE). Minimum design loads for
canes, negative aerodynamic damping may reduce total damping, buildings and other structures. ASCE 7-05, Reston (VA): ASCE; 2005.
especially for the acrosswind response. Thus, there is a possibility [3] American Society of Civil Engineers (ASCE). Minimum design loads for
buildings and other structures. ASCE 7-10, Reston (VA): ASCE; 2010.
that amplitude-dependency of frequency and damping and nega- [4] Bashor R. Dynamics of wind sensitive structures. Ph.D. Dissertation, University
tive aerodynamic damping may offset one another to some degree. of Notre Dame; 2011.
Accordingly, caution should be exercised in the assessment of [5] Bashor R, Kareem A. Load factors for dynamically sensitive structures. In: 11th
Americas conference on wind engineering, San Juan, Puerto Rico; 2009.
appropriate wind load factors for super-tall buildings in different [6] Bashor R, Kijewski-Correa T, Kareem A. On the wind-induced response of tall
terrain conditions. buildings: The effect of uncertainties in dynamic properties and human
comfort thresholds. Proc. Americas Conference on Wind Engineering, Baton
Rouge, LA; 2005.
Acknowledgements [7] Bernardini E, Spence SMJ, Kareem A. A probabilistic approach for the full
response estimation of tall buildings with 3D modes using the HFBB. Struct
The authors are grateful for the financial support provided in Safety 2013;44:91–101.
[8] Boggs DW. Validation of the aerodynamic model method. J Wind Eng Ind
part by a collaborative research project between the NatHaz
Aerodyn 1992;42:1011–22.
Modeling Laboratory and the Global Center of Excellence (GCOE) [9] Cao H, Gu M. Alongwind aerodynamic damping of tall buildings. Personal
at Tokyo Polytechnic University funded by MEXT, Japan and the communication; 2013.
NSF Grant # CMMI 1301008. Dr. Seymour M.J. Spence of [10] Chen X, Huang G. Estimation of probabilistic extreme wind load effects:
combination of aerodynamic and wind climate data. J Eng Mech 2010;136
the NatHaz Modeling Laboratory is thanked for his comments on (6):747–60.
the manuscript. [11] Cheng C-M, Lu P-C, Tsai M-S. Acrosswind aerodynamic damping of isolated
square-shaped buildings. J Wind Eng Ind Aerodyn 2002;90:1743–56.
[12] Cheng C-M, Wang J. Wind tunnel database for an intermediate wind resistance
Appendix A. Theoretical background of DED procedure design of tall buildings. In: Proc. 1st international symposium on wind effects
on buildings and urban environment. Tokyo (Japan): Tokyo Polytechnic
University; 2004.
The theory and procedure employed in the DED procedure are
[13] Coles S, Simiu E. Estimating uncertainty in the extreme value analysis of data
basically similar to NALD [48,33] and DEDM-HR [34] in which aero- generated by a hurricane simulation model. J Eng Mech 2003;129
dynamic base moment/torque spectra obtained from HFBB experi- (11):1288–94.
[14] Davenport AG, Hill-Carroll P. Damping in tall buildings: its variability and
ments are utilized for evaluating the base moment/torque, the
treatment in design. In: Building Motion in Wind. Seattle (USA): ASCE Spring
mean/background/resonant equivalent static wind loads (ESWL), Convention; 1986. p. 42–57.
the maximum displacements and the peak/RMS (root-mean- [15] Diniz SMC, Sadek F, Simiu E. Wind speed estimation uncertainties: effects of
square) acceleration of a building. For the sake of completeness, climatological and micrometeorological parameters. Probabilist Eng Mech
2004;19:361–71.
the underlying theoretical background is briefly described here. [16] Diniz SMC, Simiu E. Probabilistic descriptions of wind effects and wind-load
Assuming a stationary Gaussian process, the expected maxi- factors for database-assisted design. J Struct Eng 2005;131(3):507–16.
mum base moment/torque response in the alongwind, acrosswind [17] Ellingwood B, MacGregor JG, Galambos TV, Cornell CA. Probability-based load
criteria: Load factors and load combinations. J Struct Div 1982;108(5):978–97.
and torsional directions can be expressed as: [18] Ellingwood B, Tekie P. Wind load statistics for probability-based structural
qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi design. J Struct Eng 1999;125(4):453–63.
b ¼ M þ g  rM  M þ M 2 þ M 2
M [19] Gabbai RD, Fritz WP, Wright AP, Simiu E. Assessment of ASCE 7 standard wind
B R
sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi loaf factors for tall building response estimates. J Struct Eng 2008;134
 rffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi2
2 p (5):842–5.
¼ M þ ðg B  rCM  M 0 Þ þ g R  rCM  M 0  C M ðf r1 Þ ð5Þ [20] Gabbai RD, Simiu E. Aerodynamic damping in the along-wind response of tall
4f1 buildings. J Struct Eng 2010;136(1):117–9.
[21] Holmes JD, Melbourne WH, Walker GR. A commentary on the Australian
where M = mean base moment that becomes zero in the acrosswind standard for wind loads. AS 1170 Part 2, Australian Wind Engineering Society;
1990.
and torsional responses; MB, MR = peak background and resonant [22] Jeary AP. Damping in tall buildings – a mechanism and a predictor. Earthquake
base moment or torque component, respectively; g, gB, gR = peak Eng Struct Dyn 1986;14:733–50.
factors for total, background and resonant moments, respectively; [23] Kareem A. Wind excited motion of buildings. Ph.D. dissertation, Fort Collins
(Colorado): Colorado State University; 1978.
rM, rCM = RMS of the fluctuating base moment/torque response [24] Kareem A. Acrosswind response of buildings. J Struct Div 1982;108
and non-dimensional base moment/torque response coefficient (ST4):869–87.
(=rM =M0 ), respectively; M 0 = reference moment or torque; f1 = [25] Kareem A, Cermak JE. Pressure fluctuations on a square building model in
boundary-layer flows. J Wind Eng Ind Aerodyn 1984;16:17–41.
damping ratio of a building in the first mode; CM(fr1) = non- [26] Kareem A. Aerodynamic response of structures with parametric uncertainties.
dimensional base moment spectrum value corresponding to fr1 Struct Safety 1988;5(3):205–25.
[CM(fr) = f r  SM ðf r Þ=r2M ]; fr1 = reduced frequency (fr = fB/UH); f = [27] Kareem A. Effect of parametric uncertainties on wind excited structural
response. J Wind Eng Ind Aerodyn 1988;30(1–3):233–41.
frequency [Hz]; UH = mean wind velocity at building height H; fr1 = [28] Kareem A, Sun W-J. Dynamic response of structures with uncertain damping.
reduced frequency according to f1 (fr = fB/UH); f1 = natural Eng Struct 1990;12(1):2–8.
62 D.K. Kwon et al. / Engineering Structures 103 (2015) 53–62

[29] Kareem A, Gurley K. Damping in structures: its evaluation and treatment of [38] Peterka JA, Shahid S. Design gust wind speeds in the United States. J Struct Eng
uncertainty. J Wind Eng Ind Aerodyn 1996;59(2–3):131–57. 1998;124(2):207–14.
[30] Kareem A, Kwon DK, Tamura Y. Cyberbased analysis, modeling and simulation [39] Satake N, Suda K, Arakawa T, Sasaki A, Tamura A. Damping evaluation using
of wind load effects in VORTEX-Winds. In: 3rd American association for wind full-scale data of buildings in Japan. J Struct Eng 2003;129(4):470–7.
engineering workshop, Hyannis, Massachusetts, USA, August 12–14; 2012. [40] Solari G. Gust buffeting. I: Peak wind velocity and equivalent pressure. J Struct
[31] Kareem A, Zhou Y. Gust loading factor – past, present and future. J Wind Eng Eng 1993;119(2):365–82.
Ind Aerodyn 2003;91(12–15):1301–28. [41] Solari G, Kareem A. On the formulation of ASCE 7-95 gust effect factor. J Wind
[32] Kijewski-Correa T. Full-scale measurements and system identification: A time- Eng Ind Aerodyn 1998;77–78:673–84.
frequency perspective. Ph.D. dissertation, Notre Dame (IN): Univ. of Notre [42] Spence SMJ, Kareem A. Tall buildings and damping: a concept-based data-
Dame; 2003. driven model. J Struct Eng 2014;140(5):04014005.
[33] Kwon D, Kijewski-Correa T, Kareem A. E-Analysis of high-rise buildings [43] Trifunac MD. Comparisons between ambient and forced vibration
subjected to wind loads. J Struct Eng 2008;134(7):1139–53. experiments. Earthquake Eng Struct Dyn 1972;1(2):133–50.
[34] Kwon DK, Kareem A. A multiple database-enabled design module with [44] Vickery PJ, Wadhera D, Twisdale Jr LA, Lavelle FM. United States hurricane
embedded features of international codes and standards. Int J High-Rise wind speed risk and uncertainty. J Struct Eng 2009;135(3):301–20.
Build 2013;2(3):257–69. [45] Vickery PJ, Wadhera D, Galsworthy J, Peterka JA, Irwin PA, Griffis LA. Ultimate
[35] Kwon D, Spence S, Kareem A. Performance evaluation of database-enabled wind load design gust wind speeds in the United States for use in ASCE-7. J
design frameworks for the preliminary design of tall buildings. J Struct Eng Struct Eng 2010;136(5):613–25.
2014. http://dx.doi.org/10.1061/(ASCE)ST.1943-541X.0001229 [04014242]. [46] Watanabe Y, Isyumov N, Davenport AG. Empirical aerodynamic damping
[36] Lind NC. Consistent partial safety factors. J Struct Div 1971;97(ST6): function for tall buildings. J Wind Eng Ind Aerodyn 1997;72:313–21.
1651–70. [47] Zhou Y, Kareem A, Gu M. Mode shape corrections for wind load effects. J Struct
[37] Minciarelli F, Gioffrè M, Grigoriu M, Simiu E. Estimates of extreme wind effects Eng 2002;128(1):15–23.
and wind load factors: influence of knowledge uncertainties. Probabilist Eng [48] Zhou Y, Kijewski T, Kareem A. Aerodynamic loads on tall buildings: interactive
Mech 2001;16(4):331–40. database. J Struct Eng 2003;129(3):394–404.

You might also like