Domestic Water Booster Pump Calculation

Green Oasis (Strip Mall) Project

Pump Schedule given as follows

Flow in Head in
S.No. Building Location Quantity Unit Remarks
GPM Metre
1 Thumama A Part A 70 50 1 Duty + 1 Standby Set

2 Thumama A Part B 65 60 1 Duty + 1 Standby Set

3 Thumama B Part A 60 50 1 Duty + 1 Standby Set

4 Thumama B Part B 70 50 1 Duty + 1 Standby Set

5 Shahaba Part A 70 60 1 Duty + 1 Standby Set

6 Shahaba Part B 75 60 1 Duty + 1 Standby Set

7 Shahaba Part C 70 50 1 Duty + 1 Standby Set


Project: The Green Oasis Mall - Thumama A ( Part - A )
Subject: Water Supply Demand load selection by using Fixture units As per UPC System
Occupancy: Private
Fixture / Trim Quantity Demand
Total Demand
S.No. Fixture Weight in
Basement Ground Mezzanine First Second Roof Total Qty in Fixture Units
Fixture Units
European Water
1 9 19 6 34 3 102
Closet
2 Perenial Spray 9 19 6 34 1 34
3 Lavatory 9 18 6 33 1 33
4 Kitchen Sink 14 6 20 2 40
5 Hose Bibb 8 4 3 15 1 15
Total Demand in Fixture Units 224

Selected Demand As Per UPC Chart 18-2 for 224 Fixture Unit will be 70 Gallons/Minute

Project: The Green Oasis Mall - Thumama A ( Part - B )


Subject: Water Supply Demand load selection by using Fixture units As per UPC System
Occupancy: Private
Fixture / Trim Quantity Demand
Total Demand
S.No. Fixture Weight in
Basement Ground Mezzanine First Second Roof Total Qty in Fixture Units
Fixture Units
European Water
1 6 4 16 5 31 3 93
Closet
2 Perenial Spray 6 4 16 5 31 1 31

3 Lavatory 6 4 15 5 30 1 30

4 Kitchen Sink 1 11 4 16 2 32

5 Hose Bibb 7 3 10 1 10

Total Demand in Fixture Units 196

Selected Demand As Per UPC Chart 18-2 for 196Fixture Unit will be 65 Gallons/Minute
Project: The Green Oasis Mall - Thumama B ( Part - A )
Subject: Water Supply Demand load selection by using Fixture units As per UPC System
Occupancy: Private
Fixture / Trim Quantity Demand
Total Demand
S.No. Fixture Weight in
in Fixture Units
Basement Ground First Second Roof Total Qty Fixture Units
European Water
1 6 16 4 26 3 78
Closet
2 Perenial Spray 6 16 4 26 1 26

3 Lavatory 6 16 4 26 1 26

4 Kitchen Sink 10 4 14 2 28

5 Hose Bibb 8 2 10 1 10

Total Demand in Fixture Units 168

Selected Demand As Per UPC Chart 18-2 for 168 Fixture Unit will be 60 Gallons/Minute
Project: The Green Oasis Mall - Thumama B ( Part - B )
Subject: Water Supply Demand load selection by using Fixture units As per UPC System
Occupancy: Private
Fixture / Trim Quantity Demand
Total Demand in
S.No. Fixture Weight in
Fixture Units
Basement Ground Mezanine First Second Roof Total Qty Fixture Units
European Water
1 7 8 19 5 39 3 117
Closet
2 Perenial Spray 7 8 19 5 39 1 39

3 Lavatory 7 7 18 5 37 1 37

4 Kitchen Sink 10 4 14 2 28

5 Hose Bibb 5 3 8 1 8

Total Demand in Fixture Units 229

Selected Demand As Per UPC Chart 18-2 for 229 Fixture Unit will be 70 Gallons/Minute
Project: The Green Oasis Mall - Shahaba ( Part - A )
Subject: Water Supply Demand load selection by using Fixture units As per UPC System
Occupancy: Private
Fixture / Trim Quantity Demand
Total Demand in
S.No. Fixture Weight in
Basement Ground Mezanine First Second Roof Total Qty Fixture Units
Fixture Units
European Water
1 10 2 24 8 44 3 132
Closet
2 Perenial Spray 10 2 24 8 44 1 44

3 Lavatory 10 2 23 8 43 1 43

4 Kitchen Sink 8 8 2 16

5 Hose Bibb 15 3 4 22 1 22

Total Demand in Fixture Units 257

Selected Demand As Per UPC Chart 18-2 for 257 Fixture Unit will be 70 Gallons/Minute
Project: The Green Oasis Mall - Shahaba ( Part - B )
Subject: Water Supply Demand load selection by using Fixture units As per UPC System
Occupancy: Private
Fixture / Trim Quantity Demand
Total Demand in
S.No. Fixture Weight in
Basement Ground Mezanine First Second Roof Total Qty Fixture Units
Fixture Units
European Water
1 10 3 23 8 44 3 132
Closet
2 Perenial Spray 10 3 23 8 44 1 44

3 Lavatory 10 3 22 8 43 1 43

4 Kitchen Sink 19 8 27 2 54

5 Hose Bibb 10 3 3 16 1 16

Total Demand in Fixture Units 289

Selected Demand As Per UPC Chart 18-2 for 289 Fixture Unit will be 75 Gallons/Minute
Project: The Green Oasis Mall - Shahaba ( Part - C )
Subject: Water Supply Demand load selection by using Fixture units As per UPC System
Occupancy: Private
Fixture / Trim Quantity Demand
Total Demand in
S.No. Fixture Weight in
Basement Ground Mezanine First Second Roof Total Qty Fixture Units
Fixture Units
European Water
1 8 0 19 6 33 3 99
Closet
2 Perenial Spray 8 0 19 6 33 1 33
3 Lavatory 8 0 18 6 32 1 32
4 Kitchen Sink 15 6 21 2 42
5 Hose Bibb 8 3 2 13 1 13
Total Demand in Fixture Units 219

Selected Demand As Per UPC Chart 18-2 for 219 Fixture Unit will be 70 Gallons/Minute
Project: The Green Oasis Mall - Thumama A ( Part - A )
Subject: Water Booster Pump Head Selection

Pipe Length Friction Loss / Total Friction


S.No. Section Item Fixture Unit GPM Pipe Size
in Feet 100 Ft Loss in Feet

1 AB Pipe 224 70 65mm 12 1.5 0.18


2 BC Pipe 224 70 65mm 12 1.5 0.18
3 CD Pipe 216 70 65mm 6 1.5 0.09
4 DE Pipe 158 60 50mm 5 3 0.15
5 EF Pipe 129 50 50mm 1 2.2 0.022
6 FG Pipe 104 45 50mm 48 2 0.96
7 GH Pipe 79 40 50mm 44 1.4 0.616
8 HI Pipe 54 30 50mm 31 1 0.31
9 IJ Pipe 29 23 32mm 39 6 2.34
10 JK Pipe 29 23 32mm 40 6 2.4
11 KL Pipe 14 15 32mm 15 2.5 0.375
12 LM Pipe 1 1 20mm 5 0.1 0.005
13 MN Pipe 1 1 20mm 4 0.1 0.004
Total friction loss in Feet 8
Friction Loss in Total Friction
S.No. Section Item Fixture Unit GPM Size Quantity
Feet Loss in Feet
1 A1 Flexible 224 70 65mm 1 2.5 2.5
2 A2 Check Valve 224 70 65mm 1 25 25
3 A3 Gate Valve 224 70 65mm 1 2.8 2.8
4 B Elbow 45 deg 224 70 65mm 1 5 5
5 C Elbow 45 deg 224 70 65mm 1 5 5
6 C Tee 224 70 65mm 1 2.5 2.5
7 D Tee 216 70 65mm 1 2.5 2.5
8 E Tee 158 60 50mm 1 2 2
9 F Tee 129 50 50mm 1 2 2
10 G Tee 104 45 50mm 1 2 2
11 H Tee 79 40 50mm 1 2 2
12 I Tee 54 30 50mm 1 2 2
13 J Elbow 29 23 32mm 1 4 4
14 K Tee 29 23 32mm 1 1.2 1.2
15 L Tee 14 15 32mm 1 1.2 1.2
16 M Elbow 1 1 20mm 1 2 2
Total friction loss in Feet 64
Grand Total friction loss in Feet 71 Feet
19 Metres
''Say 20 metres
Total Head Loss = Total Friction Loss + Static Head
= 20+20
= 40 m
= 4 bar
Considering 10% Safety Factor
= 4.5 bar
Say = 5 bar
Project: The Green Oasis Mall - Thumama A ( Part -B )
Subject: Water Booster Pump Head Selection

Pipe Length Friction Loss / Total Friction


S.No. Section Item Fixture Unit GPM Pipe Size
in Feet 100 Ft Loss in Feet

1 AB Pipe 196 65 65mm 12 1.3 0.156


2 BC Pipe 196 65 65mm 7 1.3 0.091
3 CD Pipe 196 65 65mm 4 1.3 0.052
4 DE Pipe 196 65 65mm 5 1.3 0.065
5 EF Pipe 188 65 65mm 8 1.3 0.104
6 FG Pipe 173 60 50mm 1 3 0.03
7 GH Pipe 139 50 50mm 30 2.2 0.66
8 HI Pipe 124 45 50mm 31 2 0.62
9 IJ Pipe 104 45 50mm 47 2 0.94
10 JK Pipe 55 30 40mm 45 3.5 1.575
11 KL Pipe 30 23 32mm 40 6 2.4
12 LM Pipe 30 23 32mm 40 6 2.4
13 MN Pipe 14 15 32mm 15 2.5 0.375
14 NO Pipe 1 1 20mm 5 0.1 0.005
15 OP Pipe 1 1 20mm 4 0.1 0.004
Total friction loss in Feet 9
Friction Loss in Total Friction
S.No. Section Item Fixture Unit GPM Size Quantity
Feet Loss in Feet
1 A1 Flexible 196 65 65mm 1 2.5 2.5
2 A2 Check Valve 196 65 65mm 1 25 25
4 A3 Gate Valve 196 65 65mm 1 2.8 2.8
5 B Elbow 196 65 65mm 1 8 8
6 C Elbow 45 deg 196 65 65mm 1 5 5
7 D Elbow 45 deg 196 65 65mm 1 5 5
8 D Tee 196 65 65mm 1 2.5 2.5
9 E Elbow 196 65 65mm 1 8 8
10 F Tee 188 65 65mm 1 2.5 2.5
11 G Tee 173 60 50mm 1 2 2
12 H Tee 139 50 50mm 1 2 2
13 I Elbow 124 45 50mm 1 7 7
14 J Tee 104 45 50mm 1 2 2
15 K Tee 55 30 40mm 1 1.5 1.5
16 L Elbow 30 23 32mm 1 4 4
17 M Tee 30 23 32mm 1 1.2 1.2
18 N Tee 14 15 32mm 1 1.2 1.2
19 O Elbow 1 1 20mm 1 2 2
Total friction loss in Feet 84
Grand Total friction loss in Feet 94 Feet
28 Metres
''Say 30 metres
Total Head Loss = Total Friction Loss + Static Head
= 30+20
= 50 m
= 5 bar
Considering 10% Safety Factor
= 5.5 bar
Say = 6 bar
Project: The Green Oasis Mall - Thumama B ( Part - A )
Subject: Water Booster Pump Head Selection

Pipe Length Friction Loss / Total Friction


S.No. Section Item Fixture Unit GPM Pipe Size
in Feet 100 Ft Loss in Feet

1 AB Pipe 168 60 65mm 8.25 1 0.0825


2 BC Pipe 168 60 65mm 4 1 0.04
3 CD Pipe 168 60 65mm 9 1 0.09
4 DE Pipe 168 60 65mm 4 1 0.04
5 EF Pipe 168 60 65mm 5 1 0.05
6 FG Pipe 52 30 50mm 42 0.9 0.378
7 GH Pipe 52 30 50mm 64 0.9 0.576
8 HI Pipe 28 17 32mm 40 2 0.8
9 IJ Pipe 28 17 32mm 32.34 2 0.6468
10 JK Pipe 14 17 25mm 14.5 2 0.29
11 KL Pipe 1 1 20mm 3.3 1 0.033
Total friction loss in Feet 3
Friction Loss in Total Friction
S.No. Section Item Fixture Unit GPM Size Quantity
Feet Loss in Feet
1 A1 Flexible 168 60 65mm 1 2.5 2.5
2 A2 Check Valve 168 60 65mm 1 25 25
4 A3 Gate Valve 168 60 65mm 1 2.8 2.8
5 B Elbow 90 deg 168 60 65mm 1 8 8
5 C Elbow 90 deg 168 60 65mm 1 8 8
8 D Elbow 45 deg 168 60 65mm 1 5 5
10 E Elbow 45 deg 168 60 65mm 1 5 5
12 F Tee 168 35 50mm 1 2 2
14 G Tee 76 35 50mm 1 2 2
16 H Elbow 52 30 50mm 1 7 7
18 I Elbow 28 17 32mm 1 4 4
20 J Tee 28 17 32mm 1 1.2 1.2
22 K Tee 14 17 25mm 1 1.2 1.2
24 L Elbow 1 1 25mm 1 2.5 2.5
Total friction loss in Feet 76
Grand Total friction loss in Feet 79 Feet
23 Metres
''Say 25 metres
Total Head Loss = Total Friction Loss + Static Head
= 25+20
= 45 m
= 4.5 bar
Considering 10% Safety Factor
= 5 bar
Project: The Green Oasis Mall - Thumama B ( Part -B )
Subject: Water Booster Pump Head Selection

Pipe Length Friction Loss / Total Friction


S.No. Section Item Fixture Unit GPM Pipe Size
in Feet 100 Ft Loss in Feet

1 AB Pipe 229 70 65mm 12 1.5 0.18


2 BC Pipe 229 70 65mm 10.5 1.5 0.1575
3 CD Pipe 224 70 65mm 3.62 1.5 0.0543
4 DE Pipe 118 50 50mm 52.5 2.4 1.26
5 EF Pipe 94 40 50mm 1 1 0.01
6 FG Pipe 70 35 50mm 57 1.2 0.684
7 GH Pipe 46 30 50mm 27.5 0.9 0.2475
8 HI Pipe 20 15 32mm 40 2.5 1
9 IJ Pipe 20 15 32mm 14.5 2.5 0.3625
10 JK Pipe 15 10 32mm 14.5 1.2 0.174
11 KL Pipe 15 10 32mm 19 1.2 0.228
12 LM Pipe 8 8 25mm 19 1.8 0.342
13 MN Pipe 1 1 20mm 3.3 0.2 0.0066
14 NO Pipe 1 1 20mm 3.3 0.2 0.0066
15 OP Pipe 1 1 20mm 16.5 0.2 0.033
Total friction loss in Feet 5
Friction Loss in Total Friction
S.No. Section Item Fixture Unit GPM Size Quantity
Feet Loss in Feet
1 A1 Flexible 229 70 65mm 1 2.5 2.5
2 A2 Check Valve 229 70 65mm 1 25 25
4 A3 Gate Valve 229 70 65mm 1 2.8 2.8
5 B Elbow 45 deg 229 70 65mm 1 5 5
6 C Elbow 45 deg 229 70 65mm 1 5 5
7 C Tee 229 70 65mm 1 2.5 2.5
8 D Tee 224 70 65mm 1 2.5 2.5
9 E Tee 118 50 50mm 1 2 2
10 F Tee 94 40 50mm 1 2 2
11 G Tee 70 35 50mm 1 2 2
12 H Tee 46 30 50mm 1 2 2
13 I Elbow 20 15 32mm 1 4 4
14 J Tee 20 15 32mm 1 1.2 1.2
15 K ---N/A--- 15 10 32mm 1 0
16 L Tee 15 10 32mm 1 1.2 1.2
17 M Tee 8 8 25mm 1 0.9 0.9
18 N Elbow 1 1 25mm 1 3 3
19 O Elbow 1 1 25mm 1 3 3
Total friction loss in Feet 67
Grand Total friction loss in Feet 71 Feet
22 Metres
''Say 25 metres
Total Head Loss = Total Friction Loss + Static Head
= 25+20
= 45 m
= 4.5 bar
Considering 10% Safety Factor
= 5 bar
Project: The Green Oasis Mall - Shahaba ( Part - A )
Subject: Water Booster Pump Head Selection

Pipe Length Friction Loss / Total Friction


S.No. Section Item Fixture Unit GPM Pipe Size
in Feet 100 Ft Loss in Feet

1 AB Pipe 257 70 65mm 12 1.4 0.168


2 BC Pipe 257 70 65mm 12 1.4 0.168
3 CD Pipe 242 70 65mm 5 1.4 0.07
4 DE Pipe 196 65 65mm 5 1.3 0.065
5 EF Pipe 172 60 65mm 27 1.2 0.324
6 FG Pipe 158 60 65mm 21 1.2 0.252
7 GH Pipe 131 50 65mm 43 0.8 0.344
8 HI Pipe 107 45 65mm 2 0.7 0.014
9 IJ Pipe 78 40 65mm 60 0.5 0.3
10 JK Pipe 53 30 50mm 60 0.7 0.42
11 KL Pipe 29 23 32mm 40 5 2
12 LM Pipe 29 23 32mm 27 5 1.35
13 MN Pipe 14 15 32mm 14 2.5 0.35
14 NO Pipe 1 1 20mm 5 0.1 0.005
15 OP Pipe 1 1 20mm 4 0.1 0.004
Total friction loss in Feet 6
Friction Loss in Total Friction
S.No. Section Item Fixture Unit GPM Size Quantity
Feet Loss in Feet
1 A1 Flexible 257 70 65mm 1 2.5 2.5
2 A2 Check Valve 257 70 65mm 1 25 25
3 A3 Gate Valve 257 70 65mm 1 2.8 2.8
4 B Elbow 257 70 65mm 1 8 8
5 C Elbow 257 70 65mm 1 8 8
6 D Elbow 45 deg 196 65 65mm 1 5 5
7 D Tee 196 65 65mm 1 2.5 2.5
8 E Elbow 172 60 65mm 1 8 8
9 F Tee 158 60 65mm 1 2.5 2.5
10 G Tee 131 50 65mm 1 2.5 2.5
11 H Tee 107 45 65mm 1 2.5 2.5
12 I Tee 78 40 65mm 1 2.5 2.5
13 J Elbow 53 30 50mm 1 7 7
14 K Tee 29 23 32mm 1 1.2 1.2
15 L Elbow 29 23 32mm 1 4 4
16 M Tee 14 15 32mm 1 1.2 1.2
17 N Tee 1 1 32mm 1 1.2 1.2
18 O Elbow 1 1 20mm 1 2.5 2.5
Total friction loss in Feet 89
Grand Total friction loss in Feet 95 Feet
27 Metres
''Say 30 metres
Total Head Loss = Total Friction Loss + Static Head
= 30+20
= 50 m
= 5 bar
Considering 10% Safety Factor
= 5.5 bar
Say = 6 bar
Project: The Green Oasis Mall - Shahaba ( Part -B )
Subject: Water Booster Pump Head Selection

Pipe Length Friction Loss / Total Friction


S.No. Section Item Fixture Unit GPM Pipe Size
in Feet 100 Ft Loss in Feet

1 AB Pipe 289 75 65mm 12 1.7 0.204


2 BC Pipe 289 75 65mm 12 1.7 0.204
3 CD Pipe 279 75 65mm 5 1.7 0.085
4 DE Pipe 204 65 65mm 5 1.4 0.07
5 EF Pipe 180 60 65mm 27 1.2 0.324
6 FG Pipe 152 50 65mm 21 0.8 0.168
7 GH Pipe 127 45 50mm 43 2 0.86
8 HI Pipe 103 45 50mm 2 2 0.04
9 IJ Pipe 78 40 50mm 60 1.5 0.9
10 JK Pipe 53 30 50mm 60 1 0.6
11 KL Pipe 29 23 32mm 40 6 2.4
12 LM Pipe 29 23 32mm 27 6 1.62
13 MN Pipe 15 15 32mm 14 2.5 0.35
14 NO Pipe 1 1 20mm 5 0.1 0.005
15 OP Pipe 1 1 20mm 4 0.1 0.004
Total friction loss in Feet 8
Friction Loss in Total Friction
S.No. Section Item Fixture Unit GPM Size Quantity
Feet Loss in Feet
1 A1 Flexible 289 75 65mm 1 2.5 2.5
2 A2 Check Valve 289 75 65mm 1 25 25
4 A3 Gate Valve 289 75 65mm 1 2.8 2.8
5 B Elbow 289 75 65mm 1 8 8
6 C Elbow 45 deg 289 75 65mm 1 5 5
7 C Tee 289 75 65mm 1 2.5 2.5
8 D Tee 279 75 65mm 1 2.5 2.5
9 E Tee 204 65 65mm 1 2.5 2.5
10 F Tee 180 60 65mm 1 2.5 2.5
11 G Tee 152 65 65mm 1 2.5 2.5
12 H Tee 127 45 50mm 1 2 2
13 I Tee 103 45 50mm 1 2 2
14 J Tee 78 40 50mm 1 2 2
15 K Elbow 53 30 50mm 1 7 7
16 L Elbow 29 23 32mm 1 4 4
17 M Tee 29 23 32mm 1 1.2 1.2
18 N Tee 15 15 32mm 1 1.2 1.2
19 O Elbow 1 1 20mm 1 2.5 2.5
Total friction loss in Feet 78
Grand Total friction loss in Feet 86 Feet
26 Metres
''Say 30 metres
Total Head Loss = Total Friction Loss + Static Head
= 30+20
= 50 m
= 5 bar
Considering 10% Safety Factor
= 5.5 bar
Say = 6 bar
Project: The Green Oasis Mall - Shahaba ( Part -C )
Subject: Water Booster Pump Head Selection

Pipe Length Friction Loss / Total Friction


S.No. Section Item Fixture Unit GPM Pipe Size
in Feet 100 Ft Loss in Feet

1 AB Pipe 219 70 65mm 12 1.4 0.168


2 BC Pipe 219 70 65mm 12 1.4 0.168
3 CD Pipe 211 70 65mm 5 1.4 0.07
4 DE Pipe 105 45 50mm 38 1.9 0.722
5 EF Pipe 80 40 50mm 39 1.5 0.585
6 FG Pipe 53 30 50mm 58 0.1 0.058
7 GH Pipe 29 23 32mm 40 6 2.4
8 HI Pipe 29 23 32mm 27 6 1.62
9 IJ Pipe 15 15 32mm 14 2.5 0.35
10 JK Pipe 1 1 20mm 5 0.1 0.005
11 KL Pipe 1 1 20mm 4 0.1 0.004
Total friction loss in Feet 6
Friction Loss in Total Friction
S.No. Section Item Fixture Unit GPM Size Quantity
Feet Loss in Feet
1 A1 Flexible 219 70 65mm 1 2.5 2.5
2 A2 Check Valve 219 70 65mm 1 25 25
4 A3 Gate Valve 219 70 65mm 1 2.8 2.8
5 B Elbow 219 70 65mm 1 8 8
6 C Elbow 45 deg 219 70 65mm 1 5 5
7 C Tee 219 70 65mm 1 2.5 2.5
8 D Tee 211 70 65mm 1 2.5 2.5
9 E Tee 105 45 50mm 1 2 2
10 F Tee 80 40 50mm 1 2 2
11 G Elbow 53 30 50mm 1 7 7
12 H Elbow 29 23 32mm 1 4 4
13 I Tee 29 23 32mm 1 1.2 1.2
14 J Tee 15 15 32mm 1 1.2 1.2
15 K Elbow 1 1 20mm 1 2.5 2.5
Total friction loss in Feet 68
Grand Total friction loss in Feet 74 Feet
23 Metres
''Say 25 metres
Total Head Loss = Total Friction Loss + Static Head
= 25+20
= 45 m
= 4.5 bar
Considering 10% Safety Factor
= 5 bar
Say = 5 bar
Project: The Green Oasis Mall - Thumama B ( Part - A )
Subject: Plumbing Fixture Qty for Demand Selection

Fixture Total Fixture


S.No. Location Item Qty
Unit Unit
1 Basement Hose Bib 8 3
2 Ground Floor WC 6 3
3 Ground Floor Lav 6 1.5
4 Ground Floor Perenial Spray 6 3
5 First Floor WC 10 3
6 First Floor Lav 10 1.5
7 First Floor Perenial Spray 10 3
8 First Floor Kitchen Sink 10 3
Public Area
9 First Floor WC 6 5

Public Area
10 Lav 6 3
First Floor
Public Area
11 Perenial Spray 6 5
First Floor
12 Second Floor WC 4 3
13 Second Floor Lav 4 1.5
14 Second Floor Perenial Spray 4 3
15 Second Floor Kitchen Sink 4 3
16 Roof Floor Hose Bib 2 3
Project: The Green Oasis Mall - Thumama B ( Part - B )
Subject: Plumbing Fixture Qty for Demand Selection

Fixture Total Fixture


S.No. Location Item Qty
Unit Unit
1 Basement Hose Bib 5 3
2 Ground Floor WC 7 3
3 Ground Floor Lav 7 1.5
4 Ground Floor Perenial Spray 7 3
Public Areas -
5 WC 8 5
Mezanine Floor
Public Areas -
6 Mezanine Floor Lav 7 3

Public Areas -
7 Mezanine Floor Perenial Spray 8 5

8 First Floor WC 11 3
9 First Floor Lav 11 1.5
10 First Floor Perenial Spray 11 3
11 First Floor Kitchen Sink 10 3
Public Area First
12 Floor WC 8 5

Public Area First


13 Lav 7 3
Floor

14 Public Area First Perenial Spray 8 5


Floor
15 Second Floor WC 5 3
16 Second Floor Lav 5 1.5
17 Second Floor Perenial Spray 5 3
18 Second Floor Kitchen Sink 4 3
19 Roof Floor Hose Bib 3 3
Project: The Green Oasis Mall - Thumama B ( Part - B )
Subject: Water Supply Demand load selection by using Fixture units As per UPC System

Fixture / Trim Quantity Demand


Total Demand in
S.No. Fixture Weight in
Basement Ground Mezanine First Second Roof Total Qty Fixture Units Fixture Units
European Water
1 7 16 11 5 39 3 117
Closet
2 Perenial Spray 7 16 11 5 1 3 3

3 Lavatory 7 16 11 5 1 1.5 1.5

4 Kitchen Sink 10 4 2 3 6

5 Hose Bibb 5 3 1 3 3

Total Demand in Fixture Units 130.5

Selected Selected
Demand Demand
As Per UPC
As Per
Chart
UPC
18-2
Chart
for 168
18-1Fixture
for 440.5
Unit
Fixture 60
will beUnit will 115
Gallons/Minute
be Gallons/Minute

19

19 1

18 1

1
Total Demand in Fixture Units

Selected Demand As Per UPC Chart 18-2 for 229 Fixture Unit will be 70 Gallons/Minute
Project: The Green Oasis Mall - Thumama A ( Part - A )
Subject: Water Supply Demand load selection by using Fixture units As per UPC System
Occupancy: Private
Fixture / Trim Quantity Demand
Total Demand
S.No. Fixture Weight in
Basement Ground Mezzanine First Second Roof Total Qty in Fixture Units
Fixture Units
European Water
1 6 5 12 3 26 3 78
Closet
2 Perenial Spray 6 5 12 3 26 1 26
3 Lavatory 6 5 12 3 26 1 26
4 Kitchen Sink 9 3 12 2 24
5 Hose Bibb 8 3 2 13 1 13
Total Demand in Fixture Units 167

Selected Demand As Per UPC Chart 18-2 for 167 Fixture Unit will be 60 Gallons/Minute

Project: The Green Oasis Mall - Thumama A ( Part - B )


Subject: Water Supply Demand load selection by using Fixture units As per UPC System
Occupancy: Private
Fixture / Trim Quantity Demand
Total Demand
S.No. Fixture Weight in
Basement Ground Mezzanine First Second Roof Total Qty in Fixture Units
Fixture Units
European Water
1 7 6 16 5 34 3 102
Closet
2 Perenial Spray 7 6 16 5 34 1 34

3 Lavatory 7 6 15 5 33 1 33

4 Kitchen Sink 11 4 15 2 30

5 Hose Bibb 5 3 3 11 1 11

Total Demand in Fixture Units 210

Selected Demand As Per UPC Chart 18-2 for 210 Fixture Unit will be 70 Gallons/Minute
Domestic Water Booster Pump Calculation
Project: Green Oasis Mall
Building: Shahaba (Part A, B & C)

Calculation obtained as follows;

For Part A, 70 GPM @ 60m Head with one Duty and one Standby

For Part B, 75 GPM @ 60m Head with one Duty and one Standby

For Part C, 70 GPM @ 50m Head with one Duty and one Standby

You might also like