Professional Documents
Culture Documents
TECHNOLOGY MANUAL
AUX - BF
TH ER MA X
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
INDEX
1. OBJECTIVE 3
2. BASIC CONCEPT OF APC EQUIPMENT 3-4
3. DESIGN CRITERIA 5
4. INTRODUCTION 5
5. BASIC CONCEPT OF DUCT WORK 5-8
5.1 CLASSIFICATION
5.2 METHODS TO BE USED
5.3 CIRCULAR DUCT
5.4 RECTANGULAR DUCT
5.5 IMPORTANT NOTES
6. SOME IMPORTANT TERMINOLOGY 8-9
7. VOLUME CALCULATION 9
8. MINIMUM CONVEYING VELOCITIES OF DUST 10
9. DUCT WORK 10 - 11
9.1 REQUIRED CONVEYING VELOCITIES IN DUCT
9.2 WHY WE NEED DUCT VELOCITY
9.3 DUCT SIZING
10. HOODS 11 - 20
10.1 REQUIRED FACE VELOCITIES IN HOOD
10.2 RANGE OF CAPTURE VELOCITIES
10.3 TYPES OF HOODS
10.4 HOODS NOMENCLATURE OF LOCAL EXHAUST
10.5 HOOD TYPES
10.6 EXHAUST HOOD
10.7 TYPES OF EXHAUST HOODS
10.8 DESIGN OF EXHAUST HOODS
10.9 WHY WE NEED SIZING HOOD PROPERLY
10.1.1 HOOD SIZING
10.1.2 HOOD DESIGN FOR SPECIFIC APPLICATIONS
11. BRANCH PIECES 21
11.1 WHY WE NEED SIZING BRANCH PIECE PROPERLY
11.2 PRINCIPLE OF DUCT DESIGN BRANCH ENTRY
11.3 BRANCH PIECE SIZING
12. RECOMMENDED FAN INLET & OUTLET CONNECTIONS 22
13. STACKS 23 - 24
13.1 REQUIRED FAN EXHAUST DUCT HEIGHT
13.2 STACK VELOCITY
13.3 STACK HEIGHT
14. DAMPERS 24 - 25
15. SOME PHOTOS OF INDUSTRIAL INSTALLATIONS 25 - 27
16. GUIDELINE FOR PREPERATION OF DUCTING 28 - 33
16.1 STUDY OF OC
16.2 STUDY OF PLANT/BUILDING AND EQUIPMENTS
16.3 STUDY OF SUCTION POINTS
16.4 DETAILS REQUIRED FOR ANY DE-DUSTING DUCTING LAYOUT
16.5 DESIGN CALCULATION
16.6 FLOW DIAGRAM
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
1. OBJECTIVE
There are no published standards on duct design. Most of the information
available is in the form of company in-house information, which is generally
evolved over a period of time, based on experience.
We have tried to compile the information available from such sources adding our
own knowledge and experience.
This Manual should help both designer / draftsman in understanding basic
concept in duct design, pressure drop calculation and duct supporting and other
mechanical requirements.
But before start the duct design we require to know the Basic concept of APC
equipment.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
3. DESIGN CRITERIA
Several design criteria are common to all industrial ventilation systems; use the
ACGIH IV Manual for primary guidance.
ACGIH = American Conference of Governmental Industrial Hygienists.
4. INTRODUCTION
Most control devices are located some distance from the emission sources they
control. This separation may be needed for several reasons. For one thing, there
may not be enough room to install the control device close to the source. Or, the
device may collect emissions from several sources located throughout the facility
and, hence, must be sited at some convenient, equidistant location. Or, it may be
that required utility connections for the control device are only available at some
remote site.
Regardless of the reason, the dust / waste gas stream must be conveyed from
the source to the control device and from there to a stack before it can be
released to the atmosphere.
The type of equipment needed to convey the dust / waste gas are the same for
most kinds of control devices.
These are: (1) hoods, (2) ductwork, (3) stacks, and (4) fans.
Together, these items comprise a ventilation system.
(1) Hood: It is used to capture the emissions at the source;
(2) Ductwork: It is to convey them to the control device;
(3) Stack: To disperse them after they leave the device; and
(4) Fan: To provide the energy for moving them through the control system.
5. BASIC CONCEPT OF DUCTWORK
5.1 Classification: We can classify ductwork as follows:
DUCTWORK
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
7. VOLUME CALCULATION
For frequently used Equipments as per ACGIH Norms
Sl.
Equipment Formula Criterion
No
for Belt speed < 1
1950 m3/Hr x Belt Width in M x Safety Factor
DISCHARGE m/s
END 2785 m3/Hr x Belt Width in M x Safety Factor for Belt speed > 1
m/s
SAME AS DISCHARGE END BUT SAFETY
Belt Conveyor
1 FACTOR IS HEIGHER AND IF Height of
(VS-50-20)
Fall is > 1 m
RECEIPT END to be added IF Width
1700 m3/Hr > 900 mm
to be added IF Width
1200 m3/hr < 900 mm
Magnetic
2 Seperator 2785 m3/Hr x Belt Width in M x Safety Factor
(VS-50-20)
Bucket
3 Elevator Per m2 Casing Cross
(VS-50-01) 1800 m3/Hr x Casing Area x Safety Factor sectional Area
Per M2 of Screen
Vibrating FLAT DECK Area / No increase
4 Screen 920 m3/hr x Screen Area x Safety Factor for Multiple Decks
(VS-99-01) Per M2 of Circular
CYLINDRICAL Cross Sectional Area
1800 m3/Hr x Circular Area x Safety Factor of Screen
Vibratory
5
Feeder 1400 m3/Hr x Width x Safety Factor ** per m of feeder width
Bunkers /
6 Hopper Per M2 of all open
(VS-50-10) 3650 m3/hr x Open Area x Safety Factor Area
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
9. DUCTWORK
Once the emission stream is captured by either a hood or a direct exhaust
connection, it is conveyed to the control device via ductwork. The term
“ductwork” denotes all of the equipment between the capture device and the
control device. This includes: (1) straight duct; (2) fittings, such as elbows and
tees; (3) flow control devices (e.g., dampers); and (4) duct supports.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
10. HOODS
Of the several components of an air pollution control system, the capture device
is the most important. This should be self-evident, for if emissions are not
efficiently captured at the source they cannot be conveyed to and removed by a
control device. There are two general categories of capture devices: (1) direct
exhaust connections (DEC) and (2) Local Exhaust hoods. As the name implies, a
DEC is a section of duct (typically an elbow) into which the emissions directly
flow. These connections often are used when the emission source is itself a duct
or vent, such as a process vent in a chemical manufacturing plant or petroleum
refinery.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
Local exhaust systems are designed to capture and remove process emissions
prior to their escape into the workplace environment. The local exhaust hood is
the point of entry into the exhaust system and is defined herein to include all
suction openings regardless of their physical configuration. The primary function
of the hood is to create an air flow field which will effectively capture the
contaminant and transport it into the hood. Figure in next page provides
nomenclature associated with local exhaust hoods.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
Local Hood
Booths or enclosures
Booth Hood
Enclosure Hood
Local hoods are relatively small structures. They are normally located close to
the point of dust generation and capture the dust before it escapes. Local hoods
are generally efficient and typically used for processes such as abrasive grinding
and woodworking.
Side, downdraft, and canopy hoods are larger versions of local hoods. They
also rely on the concept of preventing dust emissions beyond the control zone.
They are typically used for plating tank exhausts, foundry shakeouts, melting
furnaces, etc. These hoods are generally less efficient than local hoods.
Booth and enclosure hoods isolate the dust generating process from the
workplace and maintain an inward flow of air through all openings to prevent the
escape of dust. These hoods are the most popular type in minerals processing
DOCUMENT NO REVISION NO PAGE NUMBER
TM-B-DCT-001 0 15
THERMAX ENVIRO
TECHNOLOGY MANUAL
AUX - BF
TH ER MA X
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
operations because they are very efficient at minimum exhaust volumes. They
are typically used for areas such as vibrating or rotating screens, belt conveyors,
bucket elevators, and storage bins.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
C ru c ib le
R oom
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
CAST HOUSE
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
13. STACKS
Short stacks are installed after control devices to disperse the exhaust gases
above ground level and surrounding buildings. As opposed to “tall” stacks, which
can be up to 1,000 feet high, short stacks typically are no taller than 120 feet.
Certain packaged control devices come equipped with short (“stub”) stacks, with
heights ranging from 30 to 50 feet. But if such a stack is neither provided nor
adequate, the facility must erect a separate stack to serve one or more devices.
Essentially, this stack is a vertical duct erected on a foundation and supported in
some manner. For structural stability, the diameter of the stack bottom is slightly
larger than the top diameter, which typically ranges from 1 to 7 feet.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
14. DAMPERS
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
a. Butterfly Damper
Application:- Basically used for isolation (ON/OFF) applications. It can also be
used as a control damper when sizes are limited to around 800mm flap diameter,
for larger diameters multi vane type dampers are preferred.
b. Guillotine Damper
Application:- Basically used for isolation (ON/OFF) applications. It is preferred in
lines where there are no or negligible dust load and temperatures are high. Main
advantage is being the sealing efficiency as claimed by manufacturers as 99.9%.
It can be used in both circular and rectangular ducts.
c. Multi louver Damper (MLPB)
Application:- Basically used for control duty applications. It is preferred in
rectangular duct lines but can be provided in circular ducts also. Controlling
range is better than single flap butterfly dampers. For fans with inlet box Multi
louver dampers are used for flow / pressure control.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
16.1 Study of OC
When we get any OC with ducting, from proposals, we have to study the OC.
Here we will consider the study only from the ducting point of view.
1. Scope of supply of ducting – Thermax scope
2. Duct MOC, - IS:2062 Gr.-A, 5 mm Thickness, etc.
3. Surface preparation & painting / scope of painting
4. Insulation: applicable / not applicable
5. Is the plant existing or green field?
6. Plant building/equipments soft copies are available?
7. Site Visit is required or not.
8. Budget for engineering of ducting.
9. Material to be conveyed–Coal, Lime, Cement, Sponge iron etc.
10. If Coal then necessity of any explosion vent.
11. Type of ducting – normal / self cleaning type.
12. Moisture content in the gas / dust.
13. Gas volume for Bag-filter.
DOCUMENT NO REVISION NO PAGE NUMBER
TM-B-DCT-001 0 28
THERMAX ENVIRO
TECHNOLOGY MANUAL
AUX - BF
TH ER MA X
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
14. Gas volume and St. Pressure for fan are predefined or to be
worked out.
15. Excel Sheet of Gas volume for Suction points is available with
proposals?
16. Various equipments / conveyors involved in the system.
17. Belt width of belt conveyors.
18. Maximum spaces available at conveyor discharge/reception for
mounting of suction hoods.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
16.1.1 Do’s
Always provide the shortest route for the duct.
Always provide minimum bends in the duct route.
Always provide minimum bend radius as 1.5D
Always provide min 30º entry or exit to the branch.
Always provide gradual enlargement or reduction for the smooth gas flow in
the duct.
Always think for operational levels of dampers.
Provide canopy for exhaust duct, as applicable.
Always provide minimum 6D to 8D straight length upstream & minimum 4D
straight lengths down stream the sampling ports, in the exhaust duct.
Always check for the feasibility of standard pipes to be used in place of
fabricated ducts.
Always check for electrical / cable tray fouling with duct locations, if
information for the same is available.
Always provide meaningful titles for plan / sections / levels
i.e. Plan @ 0.000 m Lvl, Section-AA, View from-B, etc.
16.1.2 Don’ts
Do not provide bend radius less than 1.0D, if required due to space
constraint.
Do not block the passages with ducts / duct supports.
Do not allow sudden enlargement or reduction for the duct.
Do not forget to provide sampling ports with accessibility for exhaust stack.
Do not provide any ducting / structure nearby ID fan, which will be a
constraint for the removal of the fan impeller.
Do not decide the orientation I D fan unless it is confirmed by customer.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
11. Check for provision hoses/expansion joints, if required for the equipments like
screen, crushers, silo top etc.
12. Provide notes to clear hood size, in case of movement for handles of
equipments like slide gate etc.
13. All elevation & change in direction should be marked w.r.t. building/existing
equipment.
14. Check fouling of ducts with equipment & building.
15. Check that ducting is not rotated in two planes simultaneously, as far as
possible.
16. Provide flange joints, cleaning hatches as required.
17. All branches should enter the main ducting not to exceed 45° with 30°
preferred inclination.
18. Provide bends for ducting with min. radius of 1.5d.
19. Provide 100 NB 2 Nos. at 90º apart ports at both Inlet & Outlet of Bagfilter.
20. Provide 100 NB 2 Nos. at 90º apart sampling ports at least 8 stack or duct
diameters downstream and 2 diameters upstream from any flow disturbance
for exhaust duct, with platform/access.
21. Provide duct supports with Load Data (Load Data in revised drawing).
22. Provide adequate clearance between ducts and ceilings walls and floors for
installation and maintenance.
23. Provide standard general notes for customer reference.
24. Check the pressure loss in the ducting matches with fan selection with
minimum 15% margin.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
will be dictated by the duct diameter, which is proportional to its weight per lineal
foot.
For instance, wire hangers are only recommended for duct diameters up to 10
inches. For larger diameters (up to 36 inches), straps or rods should be used.
Typically, a strap hanger is run from the upper attachment, wrapped around the
duct, and secured by a fastener (the lower attachment). A rod hanger also
extends down from the ceiling. Unlike strap hangers, they are fastened to the
duct via a band or bands that are wrapped around the circumference. Duct of
diameters greater than 3 feet should be supported with two hangers, one on
either side of the duct, and be fastened to two 1-12 circumferential bands, one
atop and one below the duct. Moreover, supports for larger ductwork should also
allow for both axial and longitudinal expansion and contraction, to accommodate
thermal stresses.
18. INSULATION
Insulation can be either installed on the outer surface of ductwork or the ductwork
itself can be fabricated with built-in insulation. In the first case, the amount of
insulation required will depend on several heat transfer variables, such as: the
temperature, velocity, composition, and other properties of the waste gas; the
ambient temperature; the duct diameter, wall thickness, and thermal conductivity;
and the desired surface (“skin”) temperature.
Insulation Thickness Calculation as per IS-7413 (1981)
L = (K / F) x [(T h – Te) / (T e – Tm)]
Where, L = Insulation thickness in cm
K = Conductivity value in mW/cm ºC = 0.4187 for Mineral Wool
having average density of 100-200kg/m3
F = Surface coefficient in mW/cm2 ºC = 0.57 for Al cladding
Th = Gas design Temperature in ºC
Te = Expected Skin Temperature in ºC
Tm = Maximum Ambient Temperature in ºC
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
For Allowable Stress values refer Table-1 & Corrosion Allowance refers Table-2.
Table-1 Allowable Stress Value for IS:2062
Temperature in ºC Allowable Stress in Kg/cm2
Up to 50 1400
Up to 100 1400
Up to 150 1360
Up to 200 1230
Up to 250 980
Up to 300 900
Up to 350 810
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
Among the values from these four criteria, the minimum value is identified as the
maximum stiffener spacing. Then for each stiffener size, the span (depth or
width) to be stiffened can be calculated using stress criterion (Eqn.5), Stiffener
deflection (Eqn.6) and Stiffener vibration methods (Eqn.7).
Stiffener stress criterion
L ≤ √(8MB/PS) + S2/3 (5)
For each individual panel of the duct shell, for different channel / beam size, the
stiffener size is selected from the stiffener table.
Taking a duct made of 4mm plate for analysis, stiffener spacing and stiffener
sizes are calculated for a maximum transport length of duct as 2500mm.
Applying Eqn. 1,2,3 and 4 for Stress criterion, Static Plate deflection, Dynamic
plate deflection and Vibration criterion for the specified conditions the values
obtained are 1962mm, 1093.6mm, 1195mm and 698mm. The minimum value is
found to be maximum stiffener spacing which is 698mm for the case considered
for analysis.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
Table 2 is prepared for number of stiffeners required to stiffen the duct span
keeping the duct length as 2500mm. The data are found for uniform and non-
uniform stiffener spacing.
Table 2: Stiffener requirement and spacing for various duct plate thickness
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
30 0.08VP 0.16VP
45 0.06VP 0.15VP
60 0.08VP 0.17VP
90 0.15VP 0.25VP
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
2. There is little degree of flexibility for future equipment 2. Depending on the Fan and motor selected, there is
changes or additions. The duct is ‘tailor made’ for the somewhat greater flexibility for future changes or
job. addition s.
3. The choice of exhaust flow rates for a new operation 3. Correcting improperly estimated exhaust flow rates is
may be incorrect. In such cases, some duct revision relatively easy within certain ranges.
may be necessary.
4. No unusual erosion or accumulation problems will 4. Partially closed dampers may cause erosion thereby
occur. changing resistance or causing particulate
accumulation.
5. Duct will not plug if velocities are chosen correctly. 5. Duct may plug if damper insertion depth has been
adjusted improperly.
6. Total flow rate may be greater than design due to 6. Balance may be achieved with design flow rate,
higher air requirements. however the net energy required may be greater than
for the Pressure balancing method.
7. The system must be installed exactly as designed, 7. Moderate variation in duct layout is possible.
with all obstructions cleared and length of runs
accurately determined.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
22.
ELEVATION
ELEVATION
TM-B-DCT-001
DOCUMENT NO
ELEVATION PLAN
PH-1 - PIPE 50NB UPTO 300NB DUCT PH-1 - PIPE 50NB UPTO 300NB DUCT
PH-4 - PIPE 200 NB ABOVE Ø1000 mm PH-4 - PIPE 200 NB ABOVE Ø1000 mm
TECHNOLOGY MANUAL
CHAPTER : DUCTING
0
MANUFACTURING
REVISION NO
GROUP
AUX - BF
JSG SK PGD A3 20
04.04.2013 04.04.2013 04.04.2013 FOR FABRICATION & ERECTION OF DUCTING
ENGINEERING
THERMAX ENVIRO
1 1 E100412009 0
48
TH ER MA X
PAGE NUMBER
THERMAX
23.
VOLUME : B
TM-B-DCT-001
DOCUMENT NO
23.1
SAMPLE DRAWINGS
TECHNOLOGY MANUAL
CHAPTER : DUCTING
0
FLOW DIAGRAM
REVISION NO
GROUP
AUX - BF
ENGINEERING
THERMAX ENVIRO
49
TH ER MA X
PAGE NUMBER
THERMAX
THERMAX ENVIRO
TECHNOLOGY MANUAL
AUX - BF
TH ER MA X
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
DCC-2
HAMMER MILL
FLUX PRIMARY GRINDING
CL
DCC-2
FLUX PRIMARY GRINDING
TM-B-DCT-001
DOCUMENT NO
23.3
TECHNOLOGY MANUAL
CHAPTER : DUCTING
0
REVISION NO
DUCTING LAYOUT (SHHET-1)
51
TH ER MA X
PAGE NUMBER
THERMAX
THERMAX ENVIRO
TECHNOLOGY MANUAL
AUX - BF
TH ER MA X
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
23.8 REDUCER
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
TM-B-DCT-001
DOCUMENT NO
BILL OF MATERIAL OF SUP-01-01 FOR EACH SET BILL OF MATERIAL OF SUP-02-01 FOR EACH SET BILL OF MATERIAL OF SUP-03-01 FOR EACH SET
TECHNOLOGY MANUAL
0
BILL OF MATERIAL OF SUP-04-02 FOR EACH SET
REVISION NO
23.1.1 INTERNAL DUCT SUPPORT
GROUP
AUX - BF
BAGFILTER
ENGINEERING
1 1 EPAH350024 0
59
TH ER MA X
PAGE NUMBER
THERMAX
THERMAX ENVIRO
TECHNOLOGY MANUAL
AUX - BF
TH ER MA X
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
Conclusion
It is cleared from the above report, the System can not run properly and dust choking
also occurred if the system will run with so much problems and deviations from
actual design at various areas.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
1: Attitude
The tree from which many dust collection problems stem isn’t mechanical, it’s the
attitude behind the system’s purchase. Customers purchase systems without having
analyzed the plant’s requirements.
4: Noise
Noise is something that needs to be considered inside and outside of the plant, which
gets a lot of calls from customers saying that their neighbors are complaining of the
noise.
6: Poor ducting
What a lot of people forget is that the duct system is as critical as the dust collector itself.
If your duct system is wrong, you are only going to get 60 percent, maybe less, of what
the system is capable of collecting.
Generally, bad duct design is the result of two things: machinery additions and the use of
improper materials.
a) First: Changes in your machinery layout or machinery additions need to be
accompanied by the same modifications to your ducting systems. Often the original duct
design is fine, but then machines are added or moved around and the original design no
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
longer applies. When this happens, bringing in the original planner or another expert to
make a few modifications to the ducts will often cure the problem.
b) Second: Professionals should handle the system’s ducting.
A lot of people just don’t know that there are right and wrong pipes to use. They think
that a pipe is just a pipe and they end up using heating ducts with 90 degree
intersections, short elbows or the corrugated black-plastic pipe used for gutters. While
improper ducting is a large problem, there are bigger mistakes that can be made. If you
do your own duct work and make a big mistake.
7: Poor zoning
Dust collection has to start at the dust’s source. You need to pick up the dust as you are
making it, and nine times out of 10, people piecemeal things together and then the dust
is escaping the hood, or, even worse, it isn’t getting collected at all.
8: Bad filtration
Air-to-cloth ratio, that is, the total air volume divided by the square meter of cloth, should
not exceed 1 to 1.5.
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX
ENGINEERING
VOLUME : B CHAPTER : DUCTING GROUP
THERMAX