UNIVERSAL DIFFERENTIAL
PRESSURE SWITCH
Type SPU
Spec No. 131-X-XXX
Applications
Can be used to signal when the pressure difference is too high due to
a blocked filter; too low due to flow failure, or for level control in a
pressurised vessel. Not suitable for use on a vacuum.
Conduit
Thread
Adjusting
Nut
Weight:
1.4 Kg (SPU 1201)
1.8 Kg (SPU 1202)
Type A B C D E F G H J K
Low Low SPU 1201 100 38 92 17.0 18.6 53.2 1⁄4"BSP 77 21.4 14.5
SPU1202 SPU1201 SPU 1202 92.4 42.9 100 17.0 18.6 52.6 1⁄8"BSP 90 16.2 12.5
High Dimensions in mm
High
SPECIFICATION
Type: SPU 1201 Universal Pressure Switch – Specification No. 131-1-201
SPU 1202 Universal Pressure Switch – Specification No. 131-1-202
Maximum Line Pressure: 34 bar
SPU 1201
Pressure Range: 0.2 to 4 bar
Reset Differential: 0.1 bar approx.
Maximum Differential Pressure Overload: 16 Bar
SPU 1202
Pressure Range: 12 to 250 mbar
Reset Differential: 7 mbar approx.
Maximum Differential Pressure Overload: 1 Bar
ELECTRICAL RATING
Single pole, double throw microswitch: 5 A at 250Vac (Resistive)
2 A at 440Vac (Resistive)
Earth Connection Provided
Ambient Temperature Limits: –10°C to +80°C
CONSTRUCTION
Diaphragm: Beryllium Copper
Seals: Nitrile Rubber
Pressure Chambers: Brass
Pressure Connections: SPU 1201 1⁄4" BSP
SPU 1202 1⁄8" BSP
Microswitch Housing: Zinc Diecast
Top Cover: Steel with Neoprene Gasket
Mounting Bracket: Steel zinc plated
Degree of Protection: IP65
Terminals: Accept 1mm2 wire. Larger sizes are not recommended.
Cable Entry: 20mm conduit thread adaptor supplied. SPU thread also suitable for a cable gland nut.
Pressure Medium: Air, Nitrogen, Inert Gases, Water, Steam or Mineral Oils
01/97 2 DS 21.02
Mounting Considerations
The mounting bracket is fitted as standard.
Wiring Instructions
1. Ensure the switch is isolated.
2. Remove the lid and terminal cover.
3. User terminals 1 and 2 (or C and NC) for closed circuit below
operating pressure.
Two Slots 6.7 Wide
4. Use terminals 1 and 3 (or C and NO) for closed circuit above 12.7 Long
operating pressure.
Dimensions in mm Fig.1
5. Ensure Earth connection is used.
Adjustment WIRING
Normally Open Contact
A quarter turn of the adjusting nut will give a change in setting of
approximately 10% of the range of the SPU. (400 mbar on the
SPU 1201, 25 mbar on SPU 1202). Fig. 3.
Fig.2
ADJUSTMENT
INCREASE
Adjusting Nut
Operating
Pressure
Adjustment
DECREASE
Fig.3
CAUTION
• This is a mains operated device. Local wiring regulations and usual safety precautions must be observed. Note earthing
requirements.
• Not suitable for use on a vacuum.
• Observe maximum ambient temperature.
• Interference with those parts under sealed covers renders the guarantee void.
• Design and performance of Satchwell equipment are subject to continual improvement and therefore liable to alteration without notice.