allow extra evapoatin in the return air plenum

ASHRAE Method L= width Room conditions 26 deg C, 50% RH


air flow Estimate of surface area
Wp= A(0.0887+0.07815v)/Y(pw-pa)
total l/s = Wp /(1.2*(Wi- Ws))*1000 Length = m
area =A= Pool 40 85 m2 Width = m
Wi = 0.0108 area = 10 m2
v = velocity of air over water 0.2 m/s Ws 0.0081
wetted dro 35 say
c1 = 0.0887
c2 = 0.07815 l/s = 2213
Y = latent heat required to change water to vapour
at surface water temperature kJ/kg 2436.92 kJ/kg

air temp 26 air sat 3.3631 50 RH pa = 1.68155 kPa


water temp 27 pw = 3.5673 kPa

Wp = evaporation of water kg/s 0.006862 kg/sec Latent load (kW) 17.92521


16.7 kW sensible capacity 30539.25 w
compare 30.5 kW
No off Latent load = 17.47293 kW less RSH 98.2
people load 15 50 750 W 98.2
0.000308 kg/sec -165.9

total = 0.00717 kg/sec


200000 w 75.31291

air flow (RSH) = 12531 l/s


simplified formula
Wp = 4.0E-5 x A (Pw-Pa)xFa 0.006412 kg / sec l/s = 1978.873

Fa = 1 latent load kW 16.02888 kW


(usage factor)
return air plenum
allow extra evapoatin in the return air plenum
ASHRAE Method L= width Room conditions 26 deg C, 55% RH
air flow Estimate of surface area
Wp= A(0.0887+0.07815v)/Y(pw-pa)
total l/s = Wp /(1.2*(Wi- Ws))*1000 Length = m
area =A= Pool 40 85 m2 Width = m
Wi = 0.0117 area = 10 m2
v = velocity of air over water 0.15 m/s Ws 0.0081
wetted dro 35 say
c1 = 0.0887
c2 = 0.07815 l/s = 1464
Y = latent heat required to change water to vapour
at surface water temperature kJ/kg 2436.92 kJ/kg

air temp 26 air sat 3.3631 55 RH pa = 1.849705 kPa


water temp 27 pw = 3.5673 kPa

Wp = evaporation of water kg/s 0.006016 kg/sec Latent load (kW) 15.81016


14.7 kW
compare
No off Latent load = 15.41124 kW
people load 15 50 750 W
0.000308 kg/sec

total = 0.006324 kg/sec

simplified formula
Wp = 4.0E-5 x A (Pw-Pa)xFa 0.00584 kg / sec l/s = 1351.811

Fa = 1 latent load kW 14.59956 kW


(usage factor)
return air plenum
allow extra evapoatin in the return air plenum
ASHRAE Method L= width Room conditions 27 deg C, 60% RH
air flow Estimate of surface area
Wp= A(0.0887+0.07815v)/Y(pw-pa)
total l/s = Wp /(1.2*(Wi- Ws))*1000 Length = m
area =A= Pool 40 85 m2 Width = m
Wi = 0.0129 area = 10 m2
v = velocity of air over water 0.2 m/s Ws 0.0081
wetted dro 35 say
c1 = 0.0887
c2 = 0.07815 l/s = 1032
Y = latent heat required to change water to vapour
at surface water temperature kJ/kg 2436.92 kJ/kg

air temp 27 air sat 3.3631 60 RH pa = 2.01786 kPa


water temp 27 pw = 3.5673 kPa

Wp = evaporation of water kg/s 0.005638 kg/sec Latent load (kW) 14.8656


13.7 kW
compare
No off Latent load = 14.49051 kW
people load 15 50 750 W
0.000308 kg/sec

total = 0.005946 kg/sec

simplified formula
Wp = 4.0E-5 x A (Pw-Pa)xFa 0.005268 kg / sec l/s = 914.6

Fa = 1 latent load kW 13.17024 kW


(usage factor)
return air plenum
Coil off Conditions

BF = (Tldb - Tadp) / (Tedb -Tadp)

BF used in calcs 0.1

Tldb = 12.7

Tadp 9

Tedb 46

BF = 0.1

Moisture

BF = (Wla-Wadp)/(Wea-Wadp)

Wla = 0.0081

Wadp = 0.0071

Wea = 0.0162

BF = 0.10989